White Rodgers 1F80-24 - Manual

White Rodgers 1F80-24

White Rodgers 1F80-24 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
Page: / 6

Table of Contents:

  • Page 2 – INSTALLATION; REMOVE OLD THERMOSTAT; labels enclosed with the new thermostat.; ELECTRIC HEAT OR HEAT PUMP SYSTEMS; ATTACH THERMOSTAT BASE TO WALL; BATTERY LOCATION; Figure 1. Back of thermostat base; HEATING SYSTEMS; Figure 2. Thermostat base
  • Page 3 – CHECK THERMOSTAT OPERATION; Fan Operation; NOTE; Heating System
  • Page 4 – Cooling System; OPERATION; THE THERMOSTAT BASE; The Thermostat Buttons and Switches; CAUTION
  • Page 5 – OPERATING FEATURES; C CONVERTIBILITY — Press SET TIME and HOLD; PROGRAMMING YOUR THERMOSTAT
  • Page 6 – Entering Your Program; Set Current Time and Day; Enter Heating Program; Enter Cooling Program; If the outside temperature is below 50; CHECK YOUR PROGRAMMING
Loading the manual

WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398

1F80-24

Programmable Electronic Digital Thermostat

INSTALLATION AND

OPERATION INSTRUCTIONS

Printed in U.S.A.

PART NO. 37-5287E

Replaces 37-5287D

9901

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

Your new White-Rodgers Digital Thermostat uses the technol-
ogy of a solid-state microcomputer to provide precise time/
temperature control. This thermostat offers you the flexibility to
design heating and cooling programs that fit your needs.

Features:

• Battery powered (3 “AA” Energizer

®

alkaline batteries in-

cluded)

• Same program for all days of the week
• Simultaneous heat and cool program storage
• Four separate time/temperature settings per program
• Preprogrammed temperature control

• LCD continuously displays set point, and alternately dis-

plays time and room temperature

• Temperature override until next program period
• Manual program override (HOLD temperature)
• User may select either 12- or 24-hour clock display

°

F/

°

C convertibility

• Temperature range 45

°

to 90

°

F

• Standard five terminals for single or dual transformer

systems

• B & O terminals for single stage heat pumps or damper

operation

WHITE-RODGERS

SPECIFICATIONS

ELECTRICAL DATA
Electrical Rating:

8 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.5 Amps (Load per terminal)
1.5 Amps Maximum Total Load (All terminals combined)

THERMAL DATA
Setpoint Temperature Range:

45

°

F to 90

°

F (7

°

C to 32

°

C)

Operating Ambient Temperature Range:

32

°

F to 105

°

F

Operating Humidity Range:

0 to 90% RH (non-condensing)

Shipping Temperature Range:

-40

°

F to 150

°

F

APPLICATIONS
For use with:

• Standard heat/cool or heat only systems
• Electric heat systems
• Gas or oil fired systems
• Gas systems with intermittent ignition devices (I.I.D.) and/

or vent dampers

• Hydronic (hot water or steam) systems
• Single-stage heat pump systems
• Millivolt systems

DO NOT USE WITH:

• Multi-stage systems
• Systems exceeding 30 VAC and 1.5 amps
• 3-wire zoned hydronic heating systems

PRECAUTIONS

Operator: Save these instructions for future use!

This thermostat is intended for use with a low voltage system; do
not use this thermostat with a line voltage system. If in doubt
about whether your wiring is millivolt, line, or low voltage, have
it inspected by a qualified heating and air conditioning contractor
or electrician.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes and
ordinances.

This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.

To prevent electrical shock and/or equipment dam-
age, disconnect electric power to system at main fuse
or circuit breaker box until installation is complete.

Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.

Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will damage
thermostat and could cause personal injury and/or
property damage.

CAUTION

!

WARNING

!

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - INSTALLATION; REMOVE OLD THERMOSTAT; labels enclosed with the new thermostat.; ELECTRIC HEAT OR HEAT PUMP SYSTEMS; ATTACH THERMOSTAT BASE TO WALL; BATTERY LOCATION; Figure 1. Back of thermostat base; HEATING SYSTEMS; Figure 2. Thermostat base

2 INSTALLATION REMOVE OLD THERMOSTAT 1. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected. 2. Remove the front cover of the old thermostat. With wires still attached, remove wall plate from the wall. If the oldthermostat has a wall...

Page 3 - CHECK THERMOSTAT OPERATION; Fan Operation; NOTE; Heating System

3 CHECK THERMOSTAT OPERATION If at any time during testing your system does not operateproperly, contact a qualified serviceperson. Fan Operation If your system does not have a G terminal connection, skip toHeating System. 1. Turn on power to the system. 2. Move FAN switch to ON position. The blower...

Page 4 - Cooling System; OPERATION; THE THERMOSTAT BASE; The Thermostat Buttons and Switches; CAUTION

4 Cooling System This thermostat has a built-in short-term (5-minute) time delay.This feature is activated after the compressor shuts down andthe setpoint is changed within the 5-minute period. During this5-minute period, COOL will flash on the display indicating thatthe thermostat has locked out th...

Other White Rodgers Models

All White Rodgers Other