Table of Contents:

  • Page 2 – INSTALLATION; Position “A” is good if it is sufficiently close to the unit; WIRING; CEILING; Figure 2
  • Page 3 – OPERATION; Remove thermostat from mounting plate.; NOTE; Figure 7; Figure 6; Figure 5; Figure 4
  • Page 4 – Pour le chauffage, à cadran extérieur; PRÉCAUTIONS; ATTENTION; Installer le thermostat à l’écart des portes et fenêtres.; Figure 1
  • Page 5 – PLAFOND; AÉROTHERME; qui régissent les installations électriques.
  • Page 6 – MODE D’EMPLOI
Loading the manual

Printed in U.S.A.

WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, FAX (314) 577-1517

9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.

DESCRIPTION

These room thermostats are especially designed for
controlling heating equipment operating on line voltage
with heavy electrical loads. They are suitable for opera-
tion of unit heaters, boilers, furnaces, electric heaters,
etc., or any similar application requiring a heavy duty room
thermostat.

TYPE 152, 176, 196

ROOM THERMOSTATS

Heating Service, External Dial

INSTALLATION INSTRUCTIONS

PRECAUTIONS

THESE CONTROLS MUST BE INSTALLED BY A
QUALIFIED INSTALLER.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical
codes and ordinances.

This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.

This control has been accurately calibrated at the factory.
Any attempt to calibrate this control will void the White-
Rodgers warranty.

To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.

CAUTION

Do not use on circuits exceeding specified
voltages. Higher voltages will damage control
and could cause shock or fire hazard.

WARNING

INSTALLATION

The proper location of a heavy duty room thermostat is
very important to assure good performance. The following
general rules will help in determining the proper location:

1. Make sure that it is in a place where air circulates

around it freely. This is important.

2. Never install it on or near an outside wall.

3. Keep it away from windows or doors.

4. Don’t locate it too close to a strong light or any other

false source of heat such as direct sunlight, steam
lines, etc.

5. Mount it on a post or a partitioning wall, but make sure

that there are no pipes or duct work in that wall or
directly behind it.

6. If the electrical conduit leads into a cooler or a warmer

room, plug up the space around the wires in the conduit
with rock wool.

,

,

,

,

,

,

,

,

,

CONCRETE

PLASTER

JUNCTION BOX

THERMOSTAT

CONDUIT
ALONG WALL

CONDUIT

INSIDE WALL

WALL INSTALLATION

The mounting plate for this thermostat has two
holes 3

5

/

16

”apart for attaching the control on a

standard switch box.

Figure 1

WHITE-RODGERS

Operator: Save these instructions for future use!

90

80

70

60

50

40

W

H

I T

E

- R

O D G E R S

PART NO. 37-1116B

Replaces 37-1116-1 & 37-9113

9550

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - INSTALLATION; Position “A” is good if it is sufficiently close to the unit; WIRING; CEILING; Figure 2

2 INSTALLATION If the thermostat is used with unit heaters, the followingsuggestions may help. (See Fig. 2). 1. Position “A” is good if it is sufficiently close to the unit heater so that the return air to the heater flows over thethermostat. 2. Position “B” is good if it is not necessary to make fr...

Page 3 - OPERATION; Remove thermostat from mounting plate.; NOTE; Figure 7; Figure 6; Figure 5; Figure 4

3 OPERATION To set the thermostat, simply move the dial so that theindicating line on the case points to the temperature atwhich the contacts are to open. Some of these thermostats are equipped with a specialscrew “C” and disk “B” for making locked dial or limitedmaximum setting. Instructions for ma...

Page 4 - Pour le chauffage, à cadran extérieur; PRÉCAUTIONS; ATTENTION; Installer le thermostat à l’écart des portes et fenêtres.; Figure 1

DESCRIPTION Ces thermostat d’ambiance ont été conçus spécialementpour commander des installations de chauffage fonction-nant avec des charges électriques élevées à la tension duréseau. Ils conviennent à l’utilisation d’aérothermes, dechaudières, de générateurs d’air chaud, d’appareils dechauffage él...

Other White Rodgers Models