White Rodgers 1127 - Manual

White Rodgers 1127

White Rodgers 1127 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
Page: / 6

Table of Contents:

  • Page 2 – WIRING
  • Page 3 – SETTING THE CONTROL; CONTROLS WITH ADJUSTABLE DIFFERENTIAL; CONTROLS WITH FIXED DIFFERENTIAL
  • Page 4 – COMMANDE D’EAU CHAUDE; INSTRUCTIONS D’INSTALLATION; DESCRIPTION; Directives d’installation :; INSTALLATION
  • Page 5 – CÂBLAGE; Schéma pour chaudière à serpentin
  • Page 6 – RÉGLAGE DE LA COMMANDE; COMMANDES À DIFFÉRENTIEL RÉGLABLE; COMMANDES À DIFFÉRENTIEL FIXE
Loading the manual

WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, FAX (314) 577-1517

9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625

Printed in U.S.A.

PART NO. 37-1209B

Replaces 37-1209 & 37-9122

9547

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.

INSTALLATION INSTRUCTIONS

TYPE 1127

HOT WATER CONTROL

Surface Type - S.P.D.T.

If the boiler manufacturer recommends a control location, follow
such recommendations. If none is offered, the following informa-
tion gives suggested locations.

On a domestic heating system, surface mounted controls
may be attached to either a horizontal or a vertical riser approxi-
mately 18 inches above the boiler.

On a unit heater application, they may be attached to the base
of the coil directly in the air path or on the return line.

Installation Rules:

1. Remove the insulation on the pipe or tank where the control

is to be mounted.

2. All rough spots, scale, rust, or paint should be removed with

a file or similar tool.

3. Mount the control to the pipe by means of the two clamps

provided. They should be pulled up snugly.

4. Replace the insulation, entirely embedding the shield which

is around the sensitive element of the control.

INSTALLATION

THESE CONTROLS MUST BE INSTALLED BY A QUALIFIED
INSTALLER.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes and
ordinances.

This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.

This control has been accurately calibrated at the factory. Any
attempt to calibrate this control will void the White-Rodgers
warranty.

WARNING

Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.

CAUTION

To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.

PRECAUTIONS

This control is designed for use on Hot Water Heating systems.

The highly sensitive Hydraulic-Action element is held snugly in
contact with the pipe or tank to provide quick response to
changes in water temperature.

Type 1127 has single-pole, double-throw switch action, offering
terminals that have open-on-rise switch action as well as close-
on-rise switch action. This control may be used as a high limit
control, low limit control, circulator control, or as a combination
low limit and circulator control.

DESCRIPTION

WHITE-RODGERS

Operator: Save these instructions for future use!

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - WIRING

2 INSTALLATION CONT. The R-B contacts of the low-limit circulator control maintaindomestic hot water at the desired temperature year-round. When the thermostat calls for heat, the burner starts. Thecirculator also starts if the R-W contacts of the low-limit circulatorcontrol are closed. If excessive...

Page 3 - SETTING THE CONTROL; CONTROLS WITH ADJUSTABLE DIFFERENTIAL; CONTROLS WITH FIXED DIFFERENTIAL

3 SETTING THE CONTROL CONTROLS WITH ADJUSTABLE DIFFERENTIAL The left-hand indicator points to the temperature at which thecontacts open on high limit and low limit applications. Oncirculator applications, the left-hand indicator points to thetemperature at which the circulator will start. On combina...

Page 4 - COMMANDE D’EAU CHAUDE; INSTRUCTIONS D’INSTALLATION; DESCRIPTION; Directives d’installation :; INSTALLATION

ATTENTION Afin de prévenir les chocs électriques et les dommagesmatériels pendant l’installation, coupez l’alimentationélectrique au panneau de distribution principal. AVERTISSEMENT N’installez pas cet appareil sur des circuits qui dépas-sent la tension nominale. Une tension trop élevée peutendommag...