Toshiba LF470- Manual

Toshiba LF470

Toshiba LF470– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
Page: / 9

Table of Contents:

  • Page 2 – Two outputs (DO1 and DO2) are needed for
  • Page 3 – Consumption electric current of bus:less than 16mA; Avoid using the flowmeter in an
  • Page 4 – Installation; Dimensions; Figure4. LF470 Mounting Board; Cable glands are not provided for LF622F cFMus approved type.
  • Page 5 – Figure 6. Separate type LF470/LF622 flowmeters wiring Diagram
  • Page 6 – Piping Precautions; To select the meter size:; Make sure the full-scale flow rate used for the; About establishment environment
  • Page 7 – Calibration Range; Table 3. Standard Flow Range; Ordering Information; When ordering the LF470 flowmeters, refer to
  • Page 9 – Table 6. Communication function and output selection table
Loading the manual

EJL-142A

Field Intelligent Device Series

Electromagnetic Flowmeter

LF470/LF622

2.5,4,6mm (1/10",1/6”,1/4")


Introduction

The electromagnetic flowmeter uses Faraday’s Law of
electromagnetic induction to measure the process flow.
The device consists of two units: a detector, through
which

the

fluid

to

be

measured

flows

and

in

which

low-level signals proportional to flow rates are
obtained; and a converter, which supplies excitation
current to the

detector,

and

amplifies

the

signals

from

the

detector and

then

processes

and

converts

the

signals

into

the

4–20

mA

dc current

signal. The LF470

is a small meter size detector designed to measure a
small amount of fluids containing substances such as
chemicals.
The wetted materials for the LF470 are corrosion
resistant ceramic and platinum electrodes and are
applicable to almost any kind of fluids. The LF470 is a
lightweight palm-sized detector.
Combining with a LF622

multifunctional

converter

which

has

an

improved

noise-suppression circuit and

advanced algorithms. The LF470 is highly resistant to
noise and provides a stable output even for fluids
containing slurries. IR (Infrared) switches enable
parameter setting of the converter without removing
the cover. Flow direction can be set in either way, and
its unique 128 x 128 dot matrix LCD display allows
the LCD to be rotated electronically to 90, 180 and 270
degrees without opening the cover
The AF900 hand-held terminal (HART*

1

communicator) can be used to communicate with the
flowmeter from a remote place. PROFIBUS-PA*

2

or

Modbus*

3

interface is available as an option.

*1 : HART protocol (Highway Addressable Remote Transducer) is a

commu nication protocol for indu strial sensors recommended by the

HCF (HART Commu nication Foundation).

*2 : PROFIBUS is the commu nication protocol for factory and process

automation that the PROFIBUS Organization recommends. Instead of

analog control with a conventional analog signal (4 -20mA), it is

fieldbus which digitizes all signals. Flowmeters su pport

PROFIBUS-PA.

*3 : Modbus is the commu nication protocol that Modicon Inc. developed.

Physical layer is RS485.

Figure 2. Electromagnetic Flowmeter

LF470/LF622

Specifications

Overall Specifications

Measurement range in terms of flow velocity:

0–0.3 m/s to 0–10 m/s. (0–1.0ft/s to 0–32.8ft/s).

Accuracy:

The overall accuracy combined with the

LF622 converter is shown in the following table.

Accuracy

Flow rate as a
percent of range

0.3-1.0m/s

(1.0-3.3ft/s)

1.0-10m/s

(3.3-32.8ft/s)

50

100

±

0.8% of FS

±

0.8% of rate

0

50

±

0.8% of FS

±

0.4% of FS

Note:

The accuracy is measured under standard

operating conditions at Toshiba's calibration facility.

Fluid conductivity:

50µS/cm minimum

Fluid temperature:

Pipe connection material Fluid temperature

Stainless steel and other metals

10

℃〜+

120

(

14 to 248 

°

F

)

Polyvinyl chloride
(shock -resistant)

10

℃〜+

60

(14 to 140 

°

F)

Ambient temperature:

–10 to +60

°C

(14

to

140

°F)

Structure:

IP67

Power consumption:

When combined with the LF622 converter:

Standard:10W(14VA)

at AC100V and Excitation current:0.2A

MAX:15W (22VA)

Fluid to be
measured

Signal cable

Excitation cable

Power supply

4-20mA dc output
and pulse output

LF622 Converter

LF470
Detector

Figure 1. Configuration Diagram

LF470

LF622

Certification number

Z01207

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Two outputs (DO1 and DO2) are needed for

LF470/LF622 2 MAX:17W(24VA) with PROFIBUS Model LF470 Detectors Fluid pressure: -0.1 to 1 MPa Pipe connection port: Standard – Rc (PT) 1/4 thread Option – See Table 4 Principal materials: Measurement tube – Alumina ceramics Electrodes – Platinum Pipe connection port: Standard – 316 stainless steel O...

Page 3 - Consumption electric current of bus:less than 16mA; Avoid using the flowmeter in an

LF470/LF622 3 Communications output: ・ HART(std.) Digital signal is superimposed on 4–20mAdc current signal as follows: Conforms to HART protocol Load resistance: 240 to 750 Load capacitance: 0.25µF maximum Load inductance: 4mH maximum • PROFIBUS(opt.) Protocol : PROFIBUS-PA Baurate : 31.25kbps Bus ...

Page 4 - Installation; Dimensions; Figure4. LF470 Mounting Board; Cable glands are not provided for LF622F cFMus approved type.

LF470/LF622 4 Installation Dimensions If a mounting plate is needed for the LF470, fix the plate (a) above to the bottom of the LF470. Depending on which pair of screw holes used, the mounting angle changes by 90 ° . Figure3. LF470 Dimensions 30 (1.18) 75 (2.95) 86 (3.39) ** ** * * 2-φ6 (φ0.24) hole...

Other Toshiba Models