- Page 2 – Two outputs (DO1 and DO2) are needed for
- Page 3 – Consumption electric current of bus:less than 16mA; Avoid using the flowmeter in an
- Page 4 – Installation; Dimensions; Figure4. LF470 Mounting Board; Cable glands are not provided for LF622F cFMus approved type.
- Page 5 – Figure 6. Separate type LF470/LF622 flowmeters wiring Diagram
- Page 6 – Piping Precautions; To select the meter size:; Make sure the full-scale flow rate used for the; About establishment environment
- Page 7 – Calibration Range; Table 3. Standard Flow Range; Ordering Information; When ordering the LF470 flowmeters, refer to
- Page 9 – Table 6. Communication function and output selection table
EJL-142A
Field Intelligent Device Series
Electromagnetic Flowmeter
LF470/LF622
2.5,4,6mm (1/10",1/6”,1/4")
Introduction
The electromagnetic flowmeter uses Faraday’s Law of
electromagnetic induction to measure the process flow.
The device consists of two units: a detector, through
which
the
fluid
to
be
measured
flows
and
in
which
low-level signals proportional to flow rates are
obtained; and a converter, which supplies excitation
current to the
detector,
and
amplifies
the
signals
from
the
detector and
then
processes
and
converts
the
signals
into
the
4–20
mA
dc current
signal. The LF470
is a small meter size detector designed to measure a
small amount of fluids containing substances such as
chemicals.
The wetted materials for the LF470 are corrosion
resistant ceramic and platinum electrodes and are
applicable to almost any kind of fluids. The LF470 is a
lightweight palm-sized detector.
Combining with a LF622
multifunctional
converter
which
has
an
improved
noise-suppression circuit and
advanced algorithms. The LF470 is highly resistant to
noise and provides a stable output even for fluids
containing slurries. IR (Infrared) switches enable
parameter setting of the converter without removing
the cover. Flow direction can be set in either way, and
its unique 128 x 128 dot matrix LCD display allows
the LCD to be rotated electronically to 90, 180 and 270
degrees without opening the cover
The AF900 hand-held terminal (HART*
1
communicator) can be used to communicate with the
flowmeter from a remote place. PROFIBUS-PA*
2
or
Modbus*
3
interface is available as an option.
*1 : HART protocol (Highway Addressable Remote Transducer) is a
commu nication protocol for indu strial sensors recommended by the
HCF (HART Commu nication Foundation).
*2 : PROFIBUS is the commu nication protocol for factory and process
automation that the PROFIBUS Organization recommends. Instead of
analog control with a conventional analog signal (4 -20mA), it is
fieldbus which digitizes all signals. Flowmeters su pport
PROFIBUS-PA.
*3 : Modbus is the commu nication protocol that Modicon Inc. developed.
Physical layer is RS485.
Figure 2. Electromagnetic Flowmeter
LF470/LF622
Specifications
Overall Specifications
Measurement range in terms of flow velocity:
0–0.3 m/s to 0–10 m/s. (0–1.0ft/s to 0–32.8ft/s).
Accuracy:
The overall accuracy combined with the
LF622 converter is shown in the following table.
Accuracy
Flow rate as a
percent of range
0.3-1.0m/s
(1.0-3.3ft/s)
1.0-10m/s
(3.3-32.8ft/s)
50
〜
100
%
±
0.8% of FS
±
0.8% of rate
0
〜
50
%
±
0.8% of FS
±
0.4% of FS
Note:
The accuracy is measured under standard
operating conditions at Toshiba's calibration facility.
Fluid conductivity:
50µS/cm minimum
Fluid temperature:
Pipe connection material Fluid temperature
Stainless steel and other metals
−
10
℃〜+
120
℃
(
14 to 248
°
F
)
Polyvinyl chloride
(shock -resistant)
−
10
℃〜+
60
℃
(14 to 140
°
F)
Ambient temperature:
–10 to +60
°C
(14
to
140
°F)
Structure:
IP67
Power consumption:
・
When combined with the LF622 converter:
Standard:10W(14VA)
at AC100V and Excitation current:0.2A
MAX:15W (22VA)
Fluid to be
measured
Signal cable
Excitation cable
Power supply
4-20mA dc output
and pulse output
LF622 Converter
LF470
Detector
Figure 1. Configuration Diagram
LF470
LF622
Certification number
Z01207
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
LF470/LF622 2 MAX:17W(24VA) with PROFIBUS Model LF470 Detectors Fluid pressure: -0.1 to 1 MPa Pipe connection port: Standard – Rc (PT) 1/4 thread Option – See Table 4 Principal materials: Measurement tube – Alumina ceramics Electrodes – Platinum Pipe connection port: Standard – 316 stainless steel O...
LF470/LF622 3 Communications output: ・ HART(std.) Digital signal is superimposed on 4–20mAdc current signal as follows: Conforms to HART protocol Load resistance: 240 to 750 Load capacitance: 0.25µF maximum Load inductance: 4mH maximum • PROFIBUS(opt.) Protocol : PROFIBUS-PA Baurate : 31.25kbps Bus ...
LF470/LF622 4 Installation Dimensions If a mounting plate is needed for the LF470, fix the plate (a) above to the bottom of the LF470. Depending on which pair of screw holes used, the mounting angle changes by 90 ° . Figure3. LF470 Dimensions 30 (1.18) 75 (2.95) 86 (3.39) ** ** * * 2-φ6 (φ0.24) hole...