Product Specifications
INPUT Voltage
120Vac
Voltage Range
80V~144V (+20% to -33%)
Frequency
50/60 Hz Auto Sensing
Synchronization window
± 3Hz
Power Factor
Greater than 0.97
THD Current
Less than 9% at Full Load
Topology
True On-Line, Double Conversion, Input PF Correction
OUTPUT Voltage
100/110/115/120/127Vac
Capacity
(VA) 1500VA
Capacity
(W)
1050W
Voltage Regulation
± 2%
Voltage Distortion
Less than 5% THD at Full Non-Linear Load. Less than 3% THD at full Linear Load.
Step Load
± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Rated
Current
12.5A
Overload Capacity
125% for 1 minute, 150% for 10 seconds
Crest Factor
3.0 at full load
Frequency
50/60 Hz Auto Sensing
Frequency Regulation
± 0.25Hz
Wave Form
Sine wave, Zero Transfer Time
Load
Power
Factor
0.7
Efficiency AC to AC
Greater than 86%
BATTERY DC
Voltage
36V
Backup Time
6 min (full load) 18 min (half load)
Battery type
Yuasa Flame Retardant Lead Acid 9Ah/12V
Number
of
batteries
3
Recharge time
<4 hours to 90%
1000 Series 1500VA 120V Rackmount 2U -
UT1A1A015C6RKB2
1500VA 120V/120V Rackmount 2U. The 2U Rackmount has all the great
standard features with battery cabinet additions for a longer run-time.