State Water Heaters Premium Heavy Duty - Manual

State Water Heaters Premium Heavy Duty

State Water Heaters Premium Heavy Duty – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
Page: / 4

Table of Contents:

  • Page 2 – RECOVERY RATES; Premium Heavy Duty Electric Water Heater
  • Page 3 – SPECIFICATIONS; ASME
  • Page 4 – Statesman Electric Water Heater Model Number Break Down; SUGGESTED SPECIFICATIONS
Loading the manual

COMMERCIAL

The Expert’s Choice

®

500 Lindahl Parkway, Ashland City, TN 37015 • www.stateind.com

Premium Heavy Duty Electric Water Heater

Other Standard Features

Simplified circuitry, color-coded for ease of service

Anode rod for corrosion protection

Immersion manual reset high limit

Brass drain valve

Hinged control compartment door

ASME T & P relief valve

Optional International Voltages

- 380, 415, 575 and 600 volts

three-phase available with Y connected elements.

Limited Warranty Outline

If the tank should leak any time during the first three years, under
the terms of the warranty. State Water Heaters will repair or replace
the heater; installation, labor, handling and local delivery extra.

– This Outline Is NOT A Warranty.

For complete information, consult

the written warranty or State Water Heaters.

Warranty does not apply to product installed out-side of the United
States of America or its territorial possessions and Canada.

Meets or exceeds the requirements of ASHRAE/IES-90.1-1999.

ASME Tank Construction

– 125 psi working pressure (65 thru 120

gallons), 150 psi working pressure (5 thru 50 gallons).

Foam Insulated

– To meet rigorous state codes.

Glass-Lined Tank

– Ten tank sizes available; 5 to 120 gallon. Tank

interior is coated with glass specifically developed for water heater
use. Tank cabinet has a baked enamel finish.

Incoloy Immersion Heaters

– Heavy-duty medium watt density

elements (three/immersion heater) have incoloy sheathing and
prewired leads: provide excellent protection against oxidation and
scaling. Input ranges from 3KW to 90KW available (see
accompanying chart).

Standard Voltages

– 208, 240 and 480 volt single and three phase.

Single phase 208 and 240 are convertible to three phase. All 208 and
240 volt at 24KW and below are supplied phase convertible (single to
three and vice versa). 277 volt single phase also available. Consult
factory for 120 volt power circuit availability.

Terminal Block

– To accept copper or aluminum leads (on units with

more than one contactor).

Immersion Thermostat

– Close differential immersion type

thermostat provides the accurate temperature control required for
commercial applications (adjustable through a range of 95° to 180°F).

120 Volt Control Circuit

– 120 volt control circuit powered by fused

transformer.

Magnetic Contactors

– Heavy-duty UL rated for 100,000 cycles.

Power Circuit Fusing (120 amp current draw and above)

– Meets

National Electric Code and UL requirements that water heaters must
have internal fusing when current draw exceeds 120 amps.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - RECOVERY RATES; Premium Heavy Duty Electric Water Heater

RECOVERY RATE IN GALLONS PER HOUR* - Temperature Rise ˚F Standard Btu/ KW Input Hour 30˚ 40˚ 50˚ 60˚ 70˚ 80˚ 90˚ 100˚ 110˚ 120˚ 130˚ 140˚ 3 10,239 41 31 24 20 17 15 13 12 11 10 10 9 6 20,478 82 62 49 41 35 31 27 25 22 21 19 18 9 30,717 123 92 74 62 53 46 41 37 34 31 28 26 12 40,956 164 123 98 82 70 ...

Page 3 - SPECIFICATIONS; ASME

Nominal Maximum Maximum Number* Dimensions In Inches Inlet Approx. Model Number Gallon KW of Immersion Heaters Inspection Outlet Relief Ship. Wt. Capacity Input A B C D Opening Opening Opening (Lbs.) SSE-5 5 3 1 20 1 ⁄ 4 16 1 ⁄ 4 20 1 ⁄ 8 5 82 SSE-10 10 6 26 1 ⁄ 8 18 3 ⁄ 4 22 3 ⁄ 4 7 116 SSE-20 20 1...

Page 4 - Statesman Electric Water Heater Model Number Break Down; SUGGESTED SPECIFICATIONS

Statesman Electric Water Heater Model Number Break Down Premium Heavy Duty Electric Water Heater Printed in U.S.A. EC/SSE/1004 ©2004 State Water Heaters In keeping with our policy of continuous product improvement, specifications are subject to change without prior notice. COMMERCIAL The Expert’s Ch...

Other State Water Heaters Models

All State Water Heaters Other