PVI Industries 1000P1250A-TPGO - Manual
PVI Industries 1000P1250A-TPGO – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Product is patented in the U.S., Canada, and Mexico.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 6520 02/25/04
(800) 784-8326
•
www.pvi.com
LOW NO
x
TURBOPOWER
®
• PACKAGED WATER HEATER
POLYSHIELD
®
POLYMER-LINED STORAGE TANK
TANK SERIES 1250 GALLONS VERTICAL
Recovery gph
c
Dimensions
(inches)
Blower
Motor
MODEL
NUMBER
40° - 120°F 40° - 140°F
INPUT
Btu/h
Min. Inlet
Flow Gas
Pressure
" W.C.
d
SCAQMD Energy
Model No.
A B
C HP Amps
Shipping
Weight
#
1000 P 1250A-TPL
1000
800
800,000
4.5
8TPL
800 MBtu/h
33
8
1
1/2
7
4570
1500 P 1250A-TPL
1500
1200
1,200,000
4.5
12TPL
1200 MBtu/h
33
8
1-1/4
1
14
4580
c
Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss.
d
With standard gas train
* The information presented is for natural gas 0.6 S.G.
Dimensions are in inches unless otherwise specified.
For standard and optional equipment, see form #PV 6453.
STANDARD GAS PRESSURE REQUIREMENTS:
SEE TABLE FOR MINIMUM PRESSURE BY MODEL.
MAXIMUM STATIC INLET GAS PRESSURE IS 10.5" W.C.
FOR GAS PRESSURES OUTSIDE OF THIS RANGE,
CONTACT YOUR PVI REPRESENTATIVE.
VENTING REQUIREMENTS:
-.02" TO -.06" W.C. (NEGATIVE PRESSURE).
TYPE B VENTING.
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON
THE VENT CONNECTION DIAMETER EXCLUSIVELY. CHECK
NATIONAL FUEL GAS CODE UNDER "FAN ASSISTED."
STANDARD ELECTRICAL REQUIREMENTS:
VOLTAGE:
120V, 1Ø, 60 HZ., 20 AMPS.
OTHER VOLTAGES REQUIRE AN EXTERNAL
STEPDOWN TRANSFORMER.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND
SPECIFICATION WITHOUT NOTICE.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.