Page 3 - Table of Contents; Introduction
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com i Table of Contents 1 Introduction 1-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Co...
Page 4 - Warranty
TABLE OF CONTENTS EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com ii 4.5 UPS Sidecar Operation – Maintenance Bypass Configuration 4-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 5 - List of Figures; Figure 2-3. UPM 1 to UPM 2 Joining Brackets
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com iii List of Figures Figure 1-1. Powerware 9390 UPS (40–80 kVA) with UPS Sidecar 1-2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-2....
Page 6 - This page intentionally left blank.
LIST OF FIGURES EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com iv This page intentionally left blank.
Page 7 - Chapter 1; Configurations
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 1-1 Chapter 1 Introduction The Eaton ® Powerware ® 9390 UPS Sidecar is designed for use with the Powerware 9390 80 kVA 208/208V and 480/480V and 160 kVA 480/480V three-phaseuninterruptible power ...
Page 10 - Using This Manual
INTRODUCTION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 1-4 1.2 Using This Manual This manual describes how to install and operate the Powerware 9390 UPS Sidecar.Read and understand the procedures described in this manual to ensure troubl...
Page 11 - Conventions Used in This Manual; Bold type
INTRODUCTION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 1-5 1.3 Conventions Used in This Manual This manual uses these type conventions: S Bold type highlights important concepts in discussions, key terms in procedures, and menu options. ...
Page 12 - Safety Warnings; IMPORTANT SAFETY INSTRUCTIONS; D A N G E R; LETHAL VOLTAGES; AUTHORIZED SERVICE PERSONNEL ONLY; W A R N I N G; C A U T I O N; For More Information
INTRODUCTION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 1-6 1.4 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance ...
Page 13 - Getting Help; Call your local service representative
INTRODUCTION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 1-7 1.6 Getting Help If help is needed with any of the following: S Scheduling initial startup S Regional locations and telephone numbers S A question about any of the information in...
Page 15 - Section I; Installation
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 1-1 Section I Installation
Page 17 - Chapter 2; Installing the UPS Sidecar; Installation Plan and Unpacking; UPS Sidecar Installation – Maintenance Bypass Configuration; Installing the UPS Cabinet with UPS Sidecar
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 2-1 Chapter 2 Installing the UPS Sidecar 2.1 Installation Plan and Unpacking Refer to the applicable Powerware 9390 installation and operation manual, listed inparagraph 1.5, for installation pla...
Page 20 - UPS Sidecar Installation – Parallel Redundant Configuration
INSTALLING THE UPS SIDECAR EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 2-4 2.4 UPS Sidecar Installation – Parallel Redundant Configuration The method used to install the UPS Sidecar depends on the type of installation beingundertaken. The ...
Page 24 - Standalone Parallel Redundant Installation
INSTALLING THE UPS SIDECAR EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 2-8 2.4.3 Standalone Parallel Redundant Installation Use this procedure to install separately located UPMs (see Figure 2-4). UPM 1 has theSidecar installed. The UPS Sid...
Page 25 - Installing Standalone Parallel Redundant Power Wiring
INSTALLING THE UPS SIDECAR EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 2-9 2.4.4 Installing Standalone Parallel Redundant Power Wiring NOTE Remove the UPS Sidecar top or bottom conduit landing plate to drill or punch conduit holes, or remo...
Page 26 - Installing UPS Sidecar TB1 Interface Connections; Initial Startup
INSTALLING THE UPS SIDECAR EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 2-10 2.4.5 Installing UPS Sidecar TB1 Interface Connections NOTE When installing control wiring (such as Pull Chain and MOB auxiliary contacts) to the UPS Sidecar inter...
Page 27 - Installation Checklist
INSTALLING THE UPS SIDECAR EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 2-11 Installation Checklist - All conduits and cables are properly routed to the UPS Sidecar. - All power cables are properly sized and terminated. - UPS Sidecar auxili...
Page 28 - Notes
INSTALLING THE UPS SIDECAR EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 2-12 Notes _________________________________________________________________________ _________________________________________________________________________ _________...
Page 29 - Section II; Operation
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 2-13 Section II Operation
Page 31 - Chapter 3; Understanding Operation; Maintenance Bypass Configuration; UPS Mode; UPS SIDECAR; Figure 3-1. Path of Current Through the UPS Sidecar in UPS Mode
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 3-1 Chapter 3 Understanding Operation The UPS Sidecar can be configured for either maintenance bypass or parallelredundant operation. 3.1 Maintenance Bypass Configuration 3.1.1 UPS Mode When the ...
Page 32 - Maintenance Bypass Mode with UPS Sidecar; Parallel Redundant Configuration
UNDERSTANDING OPERATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 3-2 3.1.2 Maintenance Bypass Mode with UPS Sidecar An MBP is used to safely supply utility power to the critical load during periods ofUPS maintenance or repairs. The bypa...
Page 33 - Chapter 4; UPS Sidecar Features, Controls, and Operation; UPS Sidecar Standard Features; Expansion; Options
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 4-1 Chapter 4 UPS Sidecar Features, Controls, and Operation 4.1 UPS Sidecar Standard Features The UPS Sidecar has many standard features that provide cost-effective andconsistently reliable power...
Page 34 - Symbols
UPS SIDECAR FEATURES, CONTROLS, AND OPERATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 4-2 4.2.2 Rectifier Input Breaker (RIB) Maintenance bypass configurations have an optional RIB for dual-feed systems. TheRIB provides a single point ...
Page 35 - UPS Sidecar Controls
UPS SIDECAR FEATURES, CONTROLS, AND OPERATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 4-3 4.4 UPS Sidecar Controls Figure 4-1 through Figure 4-8 identify and show the location of the controls on thePowerware 9390 UPS Sidecar. NOTE Read...
Page 36 - with MBP and MIS
UPS SIDECAR FEATURES, CONTROLS, AND OPERATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 4-4 Maintenance BypassSwitch (MBP) Maintenance Isolation Switch (MIS) Interlock Plate Figure 4-1. UPS Sidecar Controls (Bypass) – 40/20, 40/30, 40/40...
Page 37 - with Optional BIB and RIB
UPS SIDECAR FEATURES, CONTROLS, AND OPERATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 4-5 Optional Bypass InputBreaker (BIB) Optional Rectifier InputBreaker (RIB) Maintenance BypassSwitch (MBP) Maintenance Isolation Switch (MIS) Interl...
Page 42 - with MOBs and Optional SLB
UPS SIDECAR FEATURES, CONTROLS, AND OPERATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 4-10 Optional System LoadBreaker (SLB) Module Output Breaker 2(MOB 2) Module Output Breaker 1 (MOB 1) Figure 4-7. UPS Sidecar Controls (Parallel Redu...
Page 45 - UPS Sidecar Operation – Maintenance Bypass Configuration; Using the UPS when a UPS Sidecar is Installed; Transferring the UPS to Maintenance Bypass; CONTROLS
UPS SIDECAR FEATURES, CONTROLS, AND OPERATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 4-13 4.5 UPS Sidecar Operation – Maintenance Bypass Configuration 4.5.1 Using the UPS when a UPS Sidecar is Installed NOTE Before starting the UPS wi...
Page 46 - Transferring the UPS from Maintenance Bypass; NORMAL
UPS SIDECAR FEATURES, CONTROLS, AND OPERATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 4-14 W A R N I N G Power is present inside the UPS cabinets. 6. Remove the screw securing the bottom of the UPS Sidecar front panel. Lift upthe panel...
Page 47 - UPS Sidecar Operation – Parallel Redundant Configuration; Maintaining the UPS Sidecar
UPS SIDECAR FEATURES, CONTROLS, AND OPERATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 4-15 4.6 UPS Sidecar Operation – Parallel Redundant Configuration 1. Remove the screw securing the bottom of the UPS Sidecar front panel. Lift upthe ...
Page 49 - Chapter 5; Limited Factory Warranty; Three-Phase Powerware UPS Products
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com 5-1 Chapter 5 Warranty Limited Factory Warranty Three-Phase Powerware UPS Products WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Electrical Inc., a Delaware Corpor...
Page 51 - Appendix A; Figur; Installation Information
EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-1 Appendix A Figur Installation Information The information in this appendix will help during the planning andinstallation of the UPS Sidecar. This appendix contains the followingdrawings: S 16...
Page 52 - SIDECAR; TYPICAL POWERWARE 9390 UPS SYSTEM
1 of 3 031505 A DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: BATTERY CABINET 80 kVA UPS CABINET 164201546 --- 1 TYPICAL MAINTENANCE BYPASS OR STANDALONE PARALLEL REDUNDANT CONFIGURATION SIDECAR TYPICAL POWERWARE 9390 UPS SYSTEM WITH UPS SIDECAR INSTALLATION INFORMATION EATON Powerware ® 9390 UPS ...
Page 53 - TYPICAL MAINTENANCE BYPASS OR
031505 A DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 164201546 --- 1 BATTERY CABINET 160 kVA UPS CABINET TYPICAL POWERWARE 9390 UPS SYSTEM WITH UPS SIDECAR 2 of 3 TYPICAL MAINTENANCE BYPASS OR STANDALONE PARALLEL REDUNDANT CONFIGURATION SIDECAR INSTALLATION INFORMATION EATON Powerware ® 9390 UPS...
Page 54 - BATTERY CABINET
031505 A DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 164201546 --- 1 TYPICAL POWERWARE 9390 UPS SYSTEM WITH UPS SIDECAR BATTERY CABINET 80 kVA UPS CABINET 1 80 kVA UPS CABINET 2 BATTERY CABINET TYPICAL LINE-UP-AND-MATCH PARALLEL REDUNDANT CONFIGURATION 3 of 3 SIDECAR INSTALLATION INFORMATION EAT...
Page 55 - PHYSICAL FEATURES AND REQUIREMENTS; Do not tilt cabinets more than 10; Table A. UPS Sidecar Clearances; Ambient Temperature Range:
DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 164201546 --- 2 1 of 1 PHYSICAL FEATURES AND REQUIREMENTS 031505 A INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-5 1. The UPS Sidecar equipment operating environment ...
Page 56 - UPS SIDECAR ONELINE DRAWINGS; MAINTENANCE BYPASS CONFIGURATION; WITH UPS SERIAL NUMBER SEVENTH DIGIT AT
UPS SIDECAR ONELINE DRAWINGS 062806 C DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: MAINTENANCE BYPASS CONFIGURATION 80/40, 80/50, 80/60 AND 80/80 kVA, 208/208V AND 480/480V WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “A” OR “B” K1 K5 K3 UPS Sidecar MAINTENANCE BYPASS SWITCH (MBP) AC INPUT TO BYPASS A...
Page 57 - WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “A”
UPS SIDECAR ONELINE DRAWINGS 062806 B DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: MAINTENANCE BYPASS CONFIGURATION 120/100 AND 120/120 kVA, 480/480V 160/100, 160/120, AND 160/160 kVA, 480/480V WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “A” K1 K5 K3 Powerware 9390 UPS CABINET UPS Sidecar MAINTENANCE...
Page 58 - WITH UPS SERIAL NUMBER SEVENTH DIGIT
UPS SIDECAR ONELINE DRAWINGS 062806 B DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: K1 K5 K3 Powerware 9390 UPS CABINET UPS Sidecar MAINTENANCE BYPASS SWITCH (MBP) AC INPUT TO BYPASS A MAINTENANCE ISOLATION SWITCH (MIS) AC INPUT TO UPS E1, E2, E3 SINGLE-FEED JUMPER (REMOVE FOR DUAL-FEED) E6, E7, E...
Page 60 - MAINTENANCE BYPASS WITH BIB CONFIGURATION; WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “A” OR “B”
UPS SIDECAR ONELINE DRAWINGS 062806 B MAINTENANCE BYPASS WITH BIB CONFIGURATION 40/20, 40/30, 40/40, 80/40, 80/50, 80/60, AND 80/80 kVA, 208/208V AND 480/480V WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “A” OR “B” DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: K1 K5 K3 Powerware 9390 UPS CABINET UPS Si...
Page 62 - UPS ONLINE ONELINE DRAWINGS; WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “B” OR HIGHER
UPS ONLINE ONELINE DRAWINGS 062806 B MAINTENANCE BYPASS WITH BIB CONFIGURATION 120/100 AND 120/120 kVA, 480/480V WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “B” OR HIGHER DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: K1 K5 K3 Powerware 9390 UPS CABINET UPS Sidecar MAINTENANCE BYPASS SWITCH (MBP) AC IN...
Page 64 - MAINTENANCE BYPASS WITH BIB AND RIB
UPS SIDECAR ONELINE DRAWINGS 092107 C MAINTENANCE BYPASS WITH BIB AND RIB 40/20, 40/30, 40/40, 208/208V, 120/100, 120/120 kVA, 480/480V and 160/100, 160/120, 160/160 kVA, 480/480V DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: K1 K5 K3 Powerware 9390 UPS CABINET UPS Sidecar MAINTENANCE BYPASS SWITC...
Page 66 - TYPICAL PARALLEL REDUNDANT SYSTEM
DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 031505 A OUTPUT TO CRITICAL LOAD E4. E5 FUSE K5 STATIC SWITCH FUSE K3 FUSE BATTERY CONVERTER RECTIFIER INVERTER K1 UPM 2 E1 E2 E3 E6 E7 E8 E12 A B SEE NOTE 2 UPS Sidecar E4. E5 FUSE K5 STATIC SWITCH FUSE K3 FUSE BATTERY CONVERTER RECTIFIER INVERTER K1 ...
Page 67 - POWER WIRING INSTALLATION NOTES; Table B; Units
1 of 10 POWER WIRING INSTALLATION NOTES 092107 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: D 164201546 --- 4 INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-17 Table B . INPUT/OUTPUT Ratings & External Wiring...
Page 68 - Table C
POWER WIRING INSTALLATION NOTES 061507 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: D 164201546 --- 4 2 of 10 INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-18 Table C . INPUT/OUTPUT Ratings & External Wiring...
Page 69 - Table D. INPUT/OUTPUT Ratings & External Wiring Requirements for; Table E. INPUT/OUTPUT Ratings & External Wiring Requirements for
POWER WIRING INSTALLATION NOTES 092107 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: D 164201546 --- 4 3 of 10 INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-19 Table D. INPUT/OUTPUT Ratings & External Wiring ...
Page 70 - rated for parallel redundant service only. DO NOT use as a parallel; drawings; found in the appendix of the applicable Powerware 9390; ensures approximate equal current sharing when in Static bypass
POWER WIRING INSTALLATION NOTES 061507 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: C 164201546 --- 4 4 of 10 INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-20 Read and understand the following notes while planni...
Page 71 - Table F. UPS Sidecar Maintenance Bypass Power Cable Terminations
POWER WIRING INSTALLATION NOTES 092107 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: D 164201546 --- 4 5 of 10 INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-21 Table F. UPS Sidecar Maintenance Bypass Power Cable ...
Page 72 - Table I. UPS Sidecar Maintenance Bypass Power Cable Terminations
POWER WIRING INSTALLATION NOTES 092107 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: D 164201546 --- 4 6 of 10 INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-22 Table I. UPS Sidecar Maintenance Bypass Power Cable ...
Page 75 - maximum rating for bypass input circuit breakers.; Table P. Maximum UPS Sidecar Bypass Input Circuit Breaker Ratings; UPS Sidecar Model; To reduce the risk of fire, connect only to a circuit provided with
POWER WIRING INSTALLATION NOTES 062206 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: C 164201546 --- 4 9 of 10 INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-25 15. Table O lists the maximum rating for rectifier i...
Page 76 - MIS and SLB breakers on the 40 kVA UPS Sidecar are non-adjustable.; Breaker
POWER WIRING INSTALLATION NOTES 063006 B 164201546 --- 4 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 10 of 10 INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-26 16. The MIS and SLB breakers on the 80 kVA, 120 kVA...
Page 77 - CONDUIT AND WIRE ENTRY LOCATIONS; TOP VIEW
1 of 3 CONDUIT AND WIRE ENTRY LOCATIONS 031505 A 164201546 --- 5 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: TOP VIEW BOTTOM VIEW UPS SIDECAR BOTTOM ENTRYCONDUIT LANDING FOR AC INPUT AND OUTPUT.(REMOVE PANEL TO DRILL OR PUNCH CONDUIT HOLES.) UPS SIDECAR TOP ENTRYCONDUIT LANDING FOR AC INPUT AND ...
Page 79 - RIGHT SIDE VIEW
CONDUIT AND WIRE ENTRY LOCATIONS 031505 A DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 164201546 --- 5 INTER-CABINET WIRING ACCESS KNOCKOUTS. REMOVE KNOCKOUTS, AS REQUIRED, TO ROUTE WIRES BETWEEN CABINETS. (INSTALL NYLON GROMMET AFTER REMOVAL OF KNOCKOUTS.) INSIDE PANEL 3 of 3 HANGER BRACKET LOCA...
Page 80 - POWER TERMINAL LOCATIONS; MAINTENANCE BYPASS CONFIGURATION WITH BIB OPTION
1 of 34 POWER TERMINAL LOCATIONS 092107 D 164201546 --- 6 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: NOTE Metal shields covering wiring terminals must be removed to gain access to terminals. MAINTENANCE BYPASS SWITCH (MBP) (SEE SHEET 21 of 34 FOR DETAILS) 40/20, 40/30, 40/40 KVA, 480/480V MAINT...
Page 81 - MAINTENANCE BYPASS CONFIGURATION WITH BIB AND RIB OPTIONS
POWER TERMINAL LOCATIONS 092107 D DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: NOTE Metal shields covering wiring terminals must be removed to gain access to terminals. 164201546 --- 6 2 of 34 MAINTENANCE BYPASS SWITCH (MBP) (SEE SHEET 21 of 34 FOR DETAILS) 40/20, 40/30, 40/40 KVA, 480/480V MAINT...
Page 84 - MAINTENANCE BYPASS CONFIGURATION WITH OPTIONAL BIB
POWER TERMINAL LOCATIONS 092107 D DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: NOTE 1. Metal shields covering wiring terminals must be removed to access terminals. 2. 80/40 must be wired as 80/50. 164201546 --- 6 40/20. 40/30, 40/40 KVA, 208/208V AND 80/40, 80/50, 80/60, 80/80 KVA, 480/480V MAINT...
Page 90 - PARALLEL REDUNDANT CONFIGURATION
POWER TERMINAL LOCATIONS 092107 E DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: NOTE Metal shields covering wiring terminals must be removed to access terminals. 164201546 --- 6 MODULE OUTPUT BREAKER 2 (MOB 2) (SEE SHEET 29 of 34 FOR DETAILS) 40/20, 40/30, 40/40 KVA 480/480V PARALLEL REDUNDANT CON...
Page 91 - PARALLEL REDUNDANT CONFIGURATION WITH SLB
POWER TERMINAL LOCATIONS 092107 E DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: NOTE Metal shields covering wiring terminals must be removed to access terminals. 164201546 --- 6 MODULE OUTPUT BREAKER 2 (MOB 2) (SEE SHEET 29 of 34 FOR DETAILS) 40/20, 40/30, 40/40 KVA 480/480V PARALLEL REDUNDANT CON...
Page 95 - PARALLEL REDUNDANT CONFIGURATION W/SLB
POWER TERMINAL LOCATIONS 092107 E DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 164201546 --- 6 (SEE SHEET 31 of 34 FOR DETAILS) 40/20, 40/30, 40/40 KVA, 208/208V PARALLEL REDUNDANT CONFIGURATION W/SLB MODULE OUTPUT BREAKER 1 (MOB 1) AC INPUT FROM UPM 2 (A, B, C) NEUTRAL GROUND MODULE OUTPUT BREAK...
Page 105 - UPS SIDECAR MAINTENANCE BYPASS CONFIGURATION
POWER TERMINAL LOCATIONS 092107 D 164201546 --- 6 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 40/20, 40/30, 40/40 KVA, 208/208V AND 80/40, 80/50, 80/60, 80/80 KVA, 480/480V UPS SIDECAR MAINTENANCE BYPASS CONFIGURATION RECTIFIER AND BYPASS INPUT TERMINAL DETAIL 26 of 34 AC OUTPUT TO CRITICAL LOAD...
Page 112 - PARALLEL REDUNDANT CONFIGURATION TERMINAL DETAIL
POWER TERMINAL LOCATIONS 062806 C 164201546 --- 6 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 80/40, 80/50, 80/60, 80/80 KVA, 208/208V AND 160/100, 160/120, 160/160 KVA, 480/480V UPS SIDECAR PARALLEL REDUNDANT CONFIGURATION TERMINAL DETAIL MOB 1 33 of 34 MOB 2 PHASE A AC INPUT FROM UPM 2 PHASE C...
Page 114 - for parallel redundant configurations.; Table R. TB1 Terminals – 1+1 Parallel Redundant Configuration; UPS
1 of 4 INTERFACE AND CONTROL WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS 063006 D DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: 164201546 --- 7 INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-64 1. Use Class 1...
Page 115 - INTERFACE AND CONTROL WIRING; Alarm displays as Building Alarm 2 on the UPS Control Panel
063006 D DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: UPS SIDECAR TERMINAL TB1 FOR PARALLEL REDUNDANT CONFIGURATIONS 1 10 TB1 NOT USEDNOT USED INTERFACE AND CONTROL WIRING INSTALLATION NOTES AND TERMINAL LOCATIONS NOTE 1. Alarm displays as Building Alarm 2 on the UPS Control Panel Display Screen,...
Page 116 - BackUp Control (Pull Chain) Wiring Terminations; From; +1 PARALLEL REDUNDANT
INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-66 BackUp Control (Pull Chain) Wiring Terminations From To UPM 1 TB2–1 (Bldg Alm 2) UPS Sidecar TB1–5 (MOB 1 Aux 2 NO) UPM 2 TB2–1 (Bldg Alm 2) UPS Sidecar TB1–9 (MOB 2...
Page 117 - Module Output Breaker Monitoring Wiring Terminations
INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S 164201586 Rev E www.powerware.com A-67 Module Output Breaker Monitoring Wiring Terminations From To UPM 1 Can Bridge Card J3–1 (Bldg Alm) UPS Sidecar TB1–3 (MOB 1 Aux 1 NC) UPM 1 Can Bridge Card J3–2 (Bld...
Page 118 - UPS SIDECAR DIMENSIONS; FRONT VIEW
1 of 4 UPS SIDECAR DIMENSIONS 092107 B 164201546 --- 8 DESCRIPTION: DATE: DRAWING NO: SHEET: REVISION: FRONT VIEW RIGHT SIDE VIEW Dimensions are in millimeters [inches] 40 kVA and 80 kVA UPS WITH SIDECAR INSTALLATION INFORMATION EATON Powerware ® 9390 UPS Sidecar Installation and Operation Manual S ...