Omega PSW-180 - Manual
Omega PSW-180 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
PSW-180 SERIES
Differential Pressure Switches
I N S T R U C T I O N
S H E E T
M-1477/0500
N E V E R T I G H T E N B Y T U R N I N G T H E
CONTROL INTO THE FITTING.
MODELS PSW-181, 182, 185, 186 HAVE
A POLYSULPONE PORT WITH 1/4” NPSF
T H R E A D. A 1 / 4 N P T O R 1 / 4 N P S
F I T T I N G M AY B E U S E D W I T H T H I S
CONNECTION. HOWEVER, IN BOTH CASES, THE
MATING FITTING WILL BOTTOM-OUT IN THE
PRESSURE CONNECTION. THEREFORE, WITH
T H E S E M O D E L S, T E F LO N TA P E M U S T B E
APPLIED TO FITTING FOR A TIGHT SEAL. DO
NOT OVER TIGHTEN. CONNECTION TORQUE
M U S T N OT E XC E E D 2 F T. / L B S. O V E R
TIGHTENING MAY DAMAGE THE PORT.
WIRING
ALL LIVE SUPPLY CIRCUITS MUST BE
DISCONNECTED BEFORE WIRING THE
C O N T RO L . F O R E N C LO S E D U N I T S ,
C O N N E C T T H E C O N D U I T TO T H E H O L E I N
ACCORDANCE WITH NATIONAL AND LOCAL
CODES. BRING WIRES UP TO THE TERMINALS
FROM THE REAR. MAXIMUM RECOMMENDED
WIRE SIZE IS 16 AWG.
Unscrew terminal just enough to put stripped
wire under terminal block clamp.
Tools Needed
Screwdriver
Use screwdriver to turn external adjusting screw
on the side. Turn “in” (clockwise) to increase
pressure setting. For best setting accuracy, set the
s w i t ch u s i n g t h e a c t u a l w o r k i n g p r e s s u r e s
encountered in the application.
GENERAL
The PSW-180 differential pressure switch utilizes
dual diaphragm sensors to monitor the difference
in pressure between two sources.
Tools Needed
Screwdriver to accommodate
customer-supplied mounting screws
Adjustable wrenches (2)
MOUNTING
LOCATE SWITCH WHERE VIBRATION,
SHOCK, AND AMBIENT TEMPERATURE
F LU C T UAT I O N S A R E M I N I M A L . TO
AVOID DAMAGE TO CONTROL, ALWAYS HOLD
THE WRENCH ON THE WRENCH FLATS OR HEX
P O RT I O N O F T H E P R E S S U R E C O N N E C T I O N
WHEN TIGHTENING.
The control can be mounted in any position. Locate
where ambient temperature is above 30°F and
below 160°F.
Surface Mounting
Inser t two #6 screws through mounting ear holes
o n 2 ” c e n t e r s ( Re c o m m e n d e d m o u n t i n g fo r
maximum vibration resistance).
Pipe Mounting
M o u n t u n i t f r o m i t s p o r t ( s ) . A l w a y s h o l d a
wrench on pressure por t when making pressure
connection.
Making Pressure Connection
Use a wrench on the pressure por t and thread a
1 / 4 ” N P T M f i t t i n g i n t o t h e p o r t . B e s u r e t o
connect high pressure source to por t labeled
“HIGH”. Similarly, connect low pressure source
to “LOW”.
Part I - Installation
Part II - Adjustments
Dimensions
MODEL
PORT
DIM A.
DIFFERENTIAL
PRESSURE
PSW-181, 182,
1/4” NPSF
185, 186
Polysulphone
2.75” (69.9 mm)
PSW-183,
184, 187, 188
1/4” NPTF Brass
3.125” (79.4 mm)
IMPSW180-01
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.