Table of Contents:

  • Page 2 – AG-150 CENTRALIZED CONTROLLER SPECIFICATIONS; WEB BROWSER REQUIREMENTS
  • Page 3 – AG-150 CENTRALIZED CONTROLLER DIMENSIONS; A type installation plate
  • Page 4 – HVAC Advanced Products Division; 400 Lawrenceville Suwanee Rd.; Specifications are subject to change without notice.; External dimension; PAC-SC51KUA POWER SUPPLY DIMENSIONS
Loading the manual

Job Name:

Location:

Drawing Reference:

Schedule No.

System No.:

Date:

Model:

AG-150

(AG-150 Standard Package)

AG-150 STANDARD PACKAGE

• AG-150 Centralized Controller

• PAC-SC51KUA Power Supply

• SW-Mon: PC Monitoring

• SW-Sch: PC Scheduling

• SW-Email: Online Error Email

• SW-Maint: Online Maintenance Tool

• SW-TG-2000: TG-2000 Software

Optional Software

• SW-Charge: Tenant billing

• SW- Pweb: Online Personal Browser

Software Features

• SW-Mon: Monitoring enables building manager to

customize and operate all indoor units from a network PC’s

web browser for up to 50 units per AG-150.

• SW-Sch: PC Scheduling enables building manager to

customize daily, weekly and annual schedules from a

network PC’s web browser from up to 50 indoor units per

AG-150. Schedules can be applied to a single indoor unit, a

group of indoor units or collectively (batch) to all indoor

units controlled by the AG-150.

• SW-Email: Online Error Email Distribution when an error

occurs on the CITY MULTI system monitored by the

AG-150. The fault will be detected and a detailed alert will

be sent via email to the necessary personnel.

• SW-Maint: Online Maintenance Tool software performs

maintenance diagnostics via network PC and AG-150

Centralized Controller. Does not require CMS-MNG-E

convert/cable.

• SW-TG-2000: TG-2000 Integrated System Software enables

the building manager to control up to 40 AG-150 Central

Controllers with a maximum of 2,000 indoor units across

multiple CITY MULTI outdoor units. Requires a dedicated

networked PC and AG-150 software licenses (per AG-150

per function.)

Optional Software Features

• SW-Charge: Tenant “Charge” Billing calculates per tenant

CITY MULTI energy usage in kWh and in monetary amount

based on the energy consumption of the outdoor unit(s)

divided among the associated indoor units. Requires

TG-2000 software on a dedicated network PC connected to

RS-485 watt hour meter (WHM.)

• SW-Pweb: Online Personal Web Browser allows individual

user (up to 50) to control his/her zone conditioning via

personal networked PC with or without a remote controller.

OVERVIEW OF CITY MULTI

®

CONTROLS

NETWORK (CMCN)

• Consists of TG-2000 integrated system software, AG-150/

GB-50ADA/GB-24/TC-24 centralized controllers, web

browsers, timers, remote controllers, and BMS interfaces.

• TG-2000 integrated system software supports up to 40

AG-150/GB-50ADA centralized controllers (licensed for

PC software features) for a maximum of 2,000 indoor

units from a single PC.

• AG-150 centralized controller operates up to 50 indoor

units with optional control via a field-supplied PC with

licensed software.

• GB-50ADA centralized controller operates up to 50

indoor units via a field-supplied PC with licensed

software.

• GB-24 central controller operates up to 24 indoor units

via a field-supplied PC with licensed software.

• TC-24 standalone centralized controller operates up to 24

indoor units via an integral touch screen interface.

• Remote controllers consist of Deluxe MA, Simple MA

Wireless MA, and ME.

• I/O controllers consist of DIDO (PAC-YG66DCA) and

AI (PAC-YG63MCA) for third-party equipment control.

• LonWorks

®

and BACnet

®

interfaces also available.

• Interlocking of LOSSNAY

®

ERV units for control via

the AG-150/GB-50ADA/GB-24/TC-24 centralized

controllers.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - AG-150 CENTRALIZED CONTROLLER SPECIFICATIONS; WEB BROWSER REQUIREMENTS

Model: AG-150 AG-150 CENTRALIZED CONTROLLER SPECIFICATIONS • 9 inch back lit, high resolution LCD color, touch panel display. • Manages up to 50 indoor units. Units can be controlled individually, in a group or in a collective batch operation. • Monitoring and Operation mode selection (Cool, Heat, A...

Page 3 - AG-150 CENTRALIZED CONTROLLER DIMENSIONS; A type installation plate

AG-150 CENTRALIZED CONTROLLER DIMENSIONS Model: AG-150 Unit:mm[in.] CENTRALIZED CONTROLLER AG-150A 185 (7-5/16) 272 (10-3/4) 300 (11-13/16) 44.7 (1-13/16) 25.6 (1-1/16) Back View 250 (9-7/8) 272 (10-3/4) 146 (5-3/4 ) 167 (6-5/8 ) 8 (3/8) 4.5(3/16) 290.8 (11-1/2) A type installation plate B type inst...

Page 4 - HVAC Advanced Products Division; 400 Lawrenceville Suwanee Rd.; Specifications are subject to change without notice.; External dimension; PAC-SC51KUA POWER SUPPLY DIMENSIONS

HVAC Advanced Products Division Mitsubishi Electric & Electronics USA, Inc. 3400 Lawrenceville Suwanee Rd. Suwanee, GA 30024 Tele: 678-376-2900 • Fax: 800-889-9904 Toll Free: 800-433-4822 (#4) www.mehvac.com Specifications are subject to change without notice. C SD - AG-150 Standard Package - 1 ...