Page 3 - Introduction
34020201EN/AB - Page 3 Introduction Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment. The Power Management Module (PMM) has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features o...
Page 4 - Foreword
Page 4 - 34020201EN/AB Structure of this document Mandatory instructions General instructions, advice, help Indication Action Symbols Information may be found via: ◗ the contents, ◗ the index. Earth cables Other cables Foreword
Page 5 - Contents
34020201EN/AB - Page 5 Contents 1. Presentation 1.1 250 A PMM modules .................................................................................................................... 6 1.2 Access to the circuit breakers ...............................................................................
Page 6 - Module characteristics
Page 6 - 34020201EN/AB 1. Presentation 1.1 250 A PMM modules Height in mm 1900 1900 1900 1900 1900 1900 Module characteristics Width in mm 1215 1215 1215 1215 1215 1215 Depth in mm 825 825 425 825 825 425 Number of circuits 126 126 126 60 (with EL protection) 60 (with EL protection) 60 (with EL prot...
Page 7 - Access to the circuit breakers; Version with 126 circuit breakers (doors open)
34020201EN/AB - Page 7 A-01 A-03 A-05 A-07 A-09 A-11 A-13 A-15 A-17 A-19 I 0 I 0 I 0 I 0 I 0 I 0 Q1 Q2 B-01 B-03 B-05 B-07 B-09 B-11 B-13 B-15 B-17 B-19 C-01 C-03 C-05 C-07 C-09 C-11 C-13 C-15 C-17 C-19 A-02 A-04 A-06 A-08 A-10 A-12 A-14 A-16 A-18 A-20 B-02 B-04 B-06 B-08 B-10 B-12 B-14 B-16 B-18 B-...
Page 8 - MGE UPS SYSTEMS; CRITICAL POWER MONITORING SYSTEM; Access to connections; Example showing the version with 126 output circuits:
Page 8 - 34020201EN/AB Q2 Q1 MGE UPS SYSTEMS CRITICAL POWER MONITORING SYSTEM DOWN UP SELECT METER NEXTPARAMETER PREVIOUSPARAMETER HOLDREADING SCROLLMETERS SETUP MODE ALARM MENU Ph-A CH01 2.637BCM CH02 4.215 1. Presentation 1.3 Access to connections Remove the eight cover panels (each secured with t...
Page 9 - Setting up the module; Footprint of module
34020201EN/AB - Page 9 PMM ≥ 720 mm ≥ 400 mm 2. Installation 2.1 Setting up the module Module 825 mm deep 1. Install the lower base panels 23 on the sides that will not be accessible (notmandatory).2. Position the module.3. Level the module using the adjustable feet 24 . 4. Install the lower base pa...
Page 12 - Input power connections; Module with isolation transformer; B C; PE
Page 12 - 34020201EN/AB 2. Installation Specifications for protection devices and cables are provided in section 6 (Appendices, technical data sheet).To access the connections, see section 1.3. Connection cables are not supplied. 2.2 Input power connections Module with isolation transformer 1. Conne...
Page 14 - Ph
Page 14 - 34020201EN/AB Q2 Q1 1 2 3 4 5 6 1 2 3 3 2. Installation 2.3 Output circuit connections 2.4 Alarm and remote shutdown connections 1. Connect the NO remote shutdown contactto terminals 1 and 2 on terminal block 13 . 2. The alarm signals are transmitted by drycontacts (Umax = 250 V AC / 30 V ...
Page 15 - Communication connections; Communication connector details; wires
34020201EN/AB - Page 15 Q2 Q1 RS-232 RS-485 1 2 3 2. Installation 2.5 Communication connections 1. Connect the communication cable to theRS232 or RS485 connector on the right-hand door of the module.2. Run the cable as shown in the figureopposite.3. Tie the cable down to the module frame. Communicat...
Page 16 - Turning on the PMM module; Metering mode; BCM
Page 16 - 34020201EN/AB 3. Operation 3.1 Turning on the PMM module 1. Close the upstream switching device (external and not supplied) on the circuit supplying the PMM module. 2. In a module with an isolation transformer, close ("I" or ON position) circuit breaker Q1 5 (see page 7) . 3. Make ...
Page 17 - MCM; Output-circuit metering; WARNING
34020201EN/AB - Page 17 GENE KWH 0000.0 MCM KW 0000.0 Ph-A CH01 0.000 BCM CH02 0.000 3. Operation 3.4 Alarms Alarm text: WARNING : indicates that the current on the indicated circuit (number 25, phase B) is between 60 and 80% of the maximum value. Access alarm mode by pressing simultaneously the SEL...
Page 18 - Communication settings; Turning off the PMM module
Page 18 - 34020201EN/AB 3. Operation 3.5 Setup Communication settings Settings include: ◗ Routing Address (ON, OFF): internal setting reserved for MGE UPS SYSTEMS, must not be modified (ON). ◗ Modbus Address (1 to 225): Modbus address, must be selected from 1 to 225 (by steps of 16). ◗ Upstream Type...
Page 20 - This product has been designed to respect the environment.; Recycling at the end of service life
Page 20 - 34020201EN/AB 5. Environment This product has been designed to respect the environment. It does not contain CFCs or HCFCs. Recycling at the end of service life MGE UPS SYSTEMS undertakes to have all products recovered at the end of their service life recycled by certifiedcompanies in compl...
Page 21 - Technical data sheets
34020201EN/AB - Page 21 6. Appendices 6.1 Technical data sheets Electrical characteristics Rated input current: 250 A per phase and 400 A for the neutral Rated output current: 16 A per phase Input voltages: ◗ Rated voltage: 380 V / 400 V / 415 V ◗ Maximum voltage: 457 V (415 V +10%) ◗ Minimum voltag...
Page 22 - Simplified diagrams; Version with isolation transformer
Page 22 - 34020201EN/AB MX F2 Q2 F1 MX F2 Q1 Q2 F1 6. Appendices 6.2 Simplified diagrams Version with isolation transformer Version without isolation transformer Control and display electronics OutputcircuitsCH01 AC inputpower CH02 CH03 CH42 Remoteshutdown Type 1 alarm (contact open orclosed) Commun...
Page 23 - Auxiliary contact functions; Access to communicated information; Modbus communication information
34020201EN/AB - Page 23 6. Appendices 6.3 Auxiliary contact functions Normal operation Downgraded operation Overload or overvoltage Other fault Type 2-alarm contact OFF OFF OFF ON Cause Current on at least one outputcircuit between 60% and 80% ofmax. value for the circuit. ◗ Current on at least one ...
Page 31 - Card MCM (general status and measurements)
34020201EN/AB - Page 31 Card MCM (general status and measurements) # Bit Float. R/W NV Coeff. Description 1 257/258 R/W NV 0.1 Energy consumed in kWh (least significant bit of the word)* 2 259/260 R/W NV 6553.6 Energy consumed in kWh (most significant bit of the word)* 3 261/262 R 0.1 Total active p...