A
Building Safety. Building Security.
Description
• Conventional technology
• Optional connection of remote
indicator
• Extremely fl at design
• Function testable with test gas
• ATEX certifi ed
Specifi cations
Ignition protection
intrinsically safe
Ex classifi cation
EEx ia IIC T5
Current consumption at 24V
typ. 50µA (quiescent)
Ambient temperature
-10°C to +55°C
Relative humidity
10 – 95% (no condensation)
Dimensions ø × H (incl. base)
100 × 46 (mm)
Colour
cream
Weight
115g
Approval
BAS01ATEX1281
LPCB 164a
Order number
241090
Order name
IS Optical Smoke Detector/Conv. SLR-E-IS
The Intrinsically Safe Optical Smoke Detector SLR-E-IS
uses the scattered light principle and was developed
for the detection of smoke particles in explosion-prone
rooms.
The modern design of the sensing chamber al-
lows to reliably evaluate the characteristics of fi re.
Conventional technology is used for alarm transmission
to the fi re detection control panel. In conjunction with the
Safety Barrier ES58-2, the detector reaches the given
Ex classifi cation. The two LEDs with 360° visibility indi-
cate the activated condition of the detector. By means
of an auxiliary module, the connection to an ADM loop
is possible.
A detector function test can be conducted by using test
gas. The detector is attached to the IS Detector Base
YBN-R/4IS.