LST RL58-2 - Manual

LST RL58-2

LST RL58-2 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

RL58_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

Specifi cations

The fi re detection control panels Series BC216 and

BC016, respectively, provide 16 freely programmable

open-collector control outputs. Eight of these outputs

are connected to a fl at cable connector. The Relay Mo-

dules RL58-1 and RL58-2 allow for the easy conversion

of these control outputs to dry changeover contacts.

The componentry is connected to the fi re detection con-

trol panel via a fl at cable.

The RL58-1 provides eight relay outputs with a maxi-

mum contact rating of 30W. The current is limited to 1A

and the voltage is limited to 60VDC. The RL58-2 offers

four relay outputs with a maximum of 5A/230VAC. The

terminal of the RL58-2 are designed for mains voltage.

Two relay modules RL58-2 are each cascadable via pin

connectors. The relay module is delivered with fl at ca-

ble and mounting accessories for easy installation.

• 8 or 4 relay outputs, respectively,

with one dry changeover contact

each

• Actuation display by LED for each

output

• Switch contacts on terminals
• Easy mounting on componentry

carrier

• Connection with control panel via fl at

cable

Operating voltage

20 – 31VDC

Current consumption at 24V

typ. 22mA per activated circuit

Control current

typ. 1.2mA per input

Ambient temperature

-5°C to +50°C

RL58-1

Switching power per contact

1A/60V/30W

Contact life

approx. 5 mill. switching cycles (unloaded)

approx. 300,000 switching cycles (at 24VDC/1A)

Dimensions L × W × H

85 × 65 × 37 (mm)

Weight

330g

Part No.

222004

Order name

Relay Module 8-Fold/60VDC RL58-1

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other LST Models

All LST Other