LST HFM-XP95 - Manual
LST HFM-XP95 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
0786–CPD–20356
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
HFM-XP95_DBL_LST_EN_0819.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The manual call point according to EN 54-11/B is desi-
gned for use in ADM loops with Apollo/Discovery proto-
col and is accommodated in a robust die-cast aluminium
case. In comparison with plastic cases, the aluminium
case proves to be of advantage even after years of use,
thanks to its resistance to environmental impact: It is
virtually unbreakable, form stable and hardly changes
its colour in sunlight.
A built-in LED optically indicates the activated condition
of the manual call point. The detector address can be
set by means of a push-button and the entered address
is displayed by an LED. The detector is provided with a
dual-isolator, which disconnects the adjacent loop ele-
ments fast and safely in case of a short circuit.
The hinged door can be opened up to an angle of 180°
and it is provided with a replaceable pane of glass. If
the detector has been activated, an integrated locking
device prevents the closing of the door.
Custom versions with different colours, designs, func-
tions and internal wirings are available on inquiry. By
means of the optional Protection Kit HFM/HM-ZS-IP54,
the protection class can be increased to IP54.
• ADM loop technology with
Apollo/Discovery protocol
• Robust die-cast aluminium case
• LED indicates activation
• Integrated dual-isolator
• Operating instructions by means of
standardised symbols
• Increase of protection class to IP54
by using optional protection kit
Specifi cations
Operating voltage
Supply through loop voltage
Current consumption
180µA (quiescent)
Ambient temperature
-20°C to +60°C
Protection class
IP43
Dimensions W × H × D
125 × 125 × 33 (mm)
Colour
fl ame red, RAL 3000
Weight
400g
Approval
VdS G204003
0786-CPD-20356
Order number
245402
Order name
Manual Call Point/EN 54/Red/Anal./Apo HFM/3/32/02
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.