Specifi cations
The Network Redundant Alarm Converter NNU5-1 is
required in the network fi re detection control panel
BCnet216 for the alarm transmission according to
ÖNORM F 3000. It has to be installed in every sectional
control panel that is connected to the transmitting de-
vice to the fi re brigade. The componentry guarantees
the alarm transmission to a transmitting device despite
multiple line failures in the GSSnet.
• Monitors up to 126 members of
a Fire Detection Control Panel
BCnet216
• Circular redundant alarm line
monitored for wire breakage
• Meets redundancy requirements of
ÖNORM F 3000
• Easy installation in fi re detection
control panel Series BC216
Current consumption at 24V
typ. 4mA
BCnet redundant alarm line
2-core circular line
Line resistance
max. 1k
Ω
Ambient temperature
-5°C to +50°C
Dimensions L × W × H
75 × 40 × 15 (mm)
Weight
40g
Part No.
214031
Order name
Network Redundant Alarm Converter NNU5-1