LST MS-55000-841 - Manual
LST MS-55000-841 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
UMS-55000-841_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The addressable Monitor Module ÜMS-55000-841
serves for the line-monitored integration of special
detectors, such as beam smoke detectors, into the
bidirectional communication on the ADM loop with Apol-
lo/Discovery protocol. The module is fi tted into a plastic
case. The address is easily selected by means of an
integrated DIL switch. The module provides an output
for resetting the connected detectors. Status LEDs indi-
cate the condition of the monitored line and the built-in
dual-isolator.
The connected detectors must be supplied through an
external power unit.
• ADM loop technology with
Apollo/Discovery protocol
• One line-monitored input
• Integration of special detectors into
the ADM loop
• Output for resetting of detector
• Setting of module address by means
of address switch
• Integrated dual-isolator
Specifi cations
Operating voltage
Supply through loop voltage
Current consumption
1.2mA (quiescent)
Ambient temperature
-20°C to +70°C
Dimensions L × W × H
150 × 90 × 48 (mm)
Colour
white
Weight
240g
Approval
VdS G201033
Order number
249072
Order name
Monitor Module/Anal./XP95/Apo ÜMS-55000-841