A

Building Safety. Building Security.

Description

The addressable Monitor Module ÜMS-55000-841

serves for the line-monitored integration of special

detectors, such as beam smoke detectors, into the

bidirectional communication on the ADM loop with Apol-

lo/Discovery protocol. The module is fi tted into a plastic

case. The address is easily selected by means of an

integrated DIL switch. The module provides an output

for resetting the connected detectors. Status LEDs indi-

cate the condition of the monitored line and the built-in

dual-isolator.

The connected detectors must be supplied through an

external power unit.

• ADM loop technology with

Apollo/Discovery protocol

• One line-monitored input
• Integration of special detectors into

the ADM loop

• Output for resetting of detector
• Setting of module address by means

of address switch

• Integrated dual-isolator

Specifi cations

Operating voltage

Supply through loop voltage

Current consumption

1.2mA (quiescent)

Ambient temperature

-20°C to +70°C

Dimensions L × W × H

150 × 90 × 48 (mm)

Colour

white

Weight

240g

Approval

VdS G201033

Order number

249072

Order name

Monitor Module/Anal./XP95/Apo ÜMS-55000-841