LST MGE8-1 - Manual

LST MGE8-1

LST MGE8-1 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
Page: / 1
Loading the manual

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

MGE8-1_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

With the Detector Zone Extension MGE8-1 the fi re de-

tection control panel Series BC016 can be extended

from 8 to 16 addressable detector zones. Up to 64

detectors (addresses) per detector line can be indivi-

dually identifi ed with the aid of an address module. In

the event of an alarm, the fi re detection control panel

indicates the number of the detector that triggers the

alarm fi rst.

Depending on the type of detector (manual call point,

automatic fi re detector with or without alarm verifi cati-

on, fault message contacts as well as contacts for tech-

nical messages), the function of the detector zone can

be set separately for each detector line. Each input of

the Detector Zone Extension is protected against over-

voltage and thus provides high system stability.

• Extends fi re detection control panels

Series BC016 to 16 detector lines in

addressable conventional technology

• Individual detector addressing with

optional address module

• Individual setting of detector zone

function

• Lines monitored for wire breakage,

short circuit, and short to earth

Specifi cations

Current consumption at 24V

typ. 32mA (8 zones terminated, without detectors)

Line voltage

typ. 20.0V

Line current

typ. 3.8mA

End-of-line resistance

5.6k

Ω

or 3,3k

Ω

(depending on setup)

Line resistance

max. 50

Ω

per core

Ambient temperature

-5°C to +50°C

Dimensions L × W × H

100 × 65 × 15 (mm)

Weight

80g

Part No.

210110

Order name

Detector Zone Extension MGE8-1