A

Building Safety. Building Security.

Description

• ADM loop technology with

System Sensor/200 protocol

• Monitored analogue input with

sensing range 4 – 20mA

• Connection of analogue sensors such

as gas detectors or fl ame detectors

• Current-limited sensor circuit
• Mounting by means of

Surface Mounting Box SMB500

The Monitor Module M510E-4-20 is designed for the

connection of analogue sensors with a 4 – 20mA

current interface.

With that, all sensors that are equipped with a corres-

ponding analogue output – for example, gas detectors

or fl ame detectors – can be integrated into a fi re detec-

tion system. By means of the module, sensors in 2- or

3-wire technology can be connected.

The sensor circuit is powered by connecting an exter-

nal power supply to the module. The integrated current

limiter prevents overloading of the module if the power

supply for the sensor is short-circuited. In addition, the

current-limited analogue input is monitored for wire

breakage.

The Monitor Module M510E-4-20 is integrated into

an ADM loop with System Sensor/200 protocol and

occupies one address in the number range of detector

addresses.

The two-coloured status LED is actuated by the fi re

detection control panel and indicates the activated con-

dition and fault condition of the sensor.

The module is designed for mounting in a Surface

Mounting Box SMB500.

Specifi cations

Operating voltage

Supply through loop voltage

Current consumption on the loop

max. 700µA (normal communication)

External power supply

12 – 28VDC

Current consumption external power supply

typ. 10mA (24V, without sensor)

Current limiting, sensor supply (3-wire technology)

500mA

Current limiting, analogue input

25mA

Ambient temperature

-10°C to +60°C (no icing)

Relative humidity

10 – 95% (no condensation)

Dimensions L × W × H

121 × 107 × 32 (mm)

Weight

100g

Order number

249112

Order name

Monitor Module 1xAnalog In/SS M510E-4-20