LST FC600/TMAX/78 - Manual

LST FC600/TMAX/78

LST FC600/TMAX/78 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
Page: / 1
Loading the manual

0832–CPD–0126

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

FC600-TMAX-78_DBL_LST_EN_0850.PDF • PAGE 1

A

Building Safety. Building Security.

• Addressable conventional technology
• Individual detector identifi cation with

optional address module

• Alarm temperature 78°C
• Allows for connection of external

remote indicator

• Anti-tamper locking feature on

detector base

• Function check by means of test

magnet

Description

Specifi cations

The Thermal Max Detector FC600/TMAX/78 recogni-

ses a temperature of 78°C as alarm threshold and is

compliant to EN 54 -5 (class BS) standards. It can be

used in rooms with a height of up to 6m. Any alarm

will be transmitted to the fi re detection panel in con-

ventional technology. An individual detector identifi ca-

tion can be obtained with the optional Address Module

NG58-1.

The detector is equipped with an LED indicator which

is visible from all sides at any angle and thus facilitates

easy identifi cation of the alarming detector. In addition,

a remote indicator can also be connected.

Several types of detector bases are available to faci-

litate quick and easy installation. To prevent unautho-

rized removal of the detector, all detector bases are

equipped with an anti-tamper locking feature. A de-

tector function test can be conveniently conducted by

using a test magnet.

Operating voltage

10 – 30VDC (supply through detector line voltage)

Current consumption

typ. 40µA (normal condition)

Alarm temperature

78°C

Operating temperature

max. +60°C

Ambient temperature

-30°C to +70°C (continuous operation)

Relative humidity

max. 95% (no condensation)

Dimensions ø × h (without base)

106 × 46 (mm)

Colour

white

Weight

80g

Approvals

LPCB 603b/01

0832-CPD-0126

Order number

242071

Order name

Thermal Max Detector/Conv./FC600 FC600/TMAX/78