• Addressable conventional technology
• Individual detector identifi cation with
optional address module
• Alarm temperature 78°C
• Allows for connection of external
remote indicator
• Anti-tamper locking feature on
detector base
• Function check by means of test
magnet
Description
Specifi cations
The Thermal Max Detector FC600/TMAX/78 recogni-
ses a temperature of 78°C as alarm threshold and is
compliant to EN 54 -5 (class BS) standards. It can be
used in rooms with a height of up to 6m. Any alarm
will be transmitted to the fi re detection panel in con-
ventional technology. An individual detector identifi ca-
tion can be obtained with the optional Address Module
NG58-1.
The detector is equipped with an LED indicator which
is visible from all sides at any angle and thus facilitates
easy identifi cation of the alarming detector. In addition,
a remote indicator can also be connected.
Several types of detector bases are available to faci-
litate quick and easy installation. To prevent unautho-
rized removal of the detector, all detector bases are
equipped with an anti-tamper locking feature. A de-
tector function test can be conveniently conducted by
using a test magnet.
Operating voltage
10 – 30VDC (supply through detector line voltage)
Current consumption
typ. 40µA (normal condition)
Alarm temperature
78°C
Operating temperature
max. +60°C
Ambient temperature
-30°C to +70°C (continuous operation)
Relative humidity
max. 95% (no condensation)
Dimensions ø × h (without base)
106 × 46 (mm)
Colour
white
Weight
80g
Approvals
LPCB 603b/01
0832-CPD-0126
Order number
242071
Order name
Thermal Max Detector/Conv./FC600 FC600/TMAX/78