• Addressable conventional technology
• Individual detector identifi cation with
optional address module
• Allows for connection of external
remote indicator
• Anti-tamper locking feature on
detector base
• Double dust trap and insect screen
• Function check by means of test
magnet or test gas
Description
Specifi cations
The Optical Smoke Detector FC600/O is based on the
IR light scattering principle and offers superior wide-
spectrum detection of smoke aerosols generated by
the majority of fi res. A symmetrical detection chamber
allows for optimal smoke sensitivity from all directions.
Any alarm will be transmitted to the fi re detection pa-
nel in conventional technology. An individual detector
identifi cation can be obtained with the optional Address
Module NG58-1.
The detector is equipped with an LED indicator which
is visible from all sides at any angle and thus facilitates
easy identifi cation of the alarming detector. In addition,
a remote indicator can also be connected.
An automatic drift compensation keeps the response
sensitivity of the detector constant for a long period.
The double dust trap effectively protects the detector
FC600/O against false alarms resulting from dust con-
tamination and ambient light. An insect screen prevents
insects from interfering with the detection chamber.
Several types of detector bases are available to faci-
litate quick and easy installation. To prevent unautho-
rized removal of the detector, all detector bases are
equipped with an anti-tamper locking feature.
A detector function test can be conveniently conducted
by using either a test magnet or test gas.
Operating voltage
10 – 30VDC (supply through detector line voltage)
Current consumption
typ. 75µA (normal condition)
Ambient temperature
-30°C to +70°C
Relative humidity
max. 95% (no condensation)
Dimensions ø × h (without base)
106 × 46 (mm)
Colour
white
Weight
80g
Approvals
LPCB 603a/01
0832-CPD-0125
Order number
241070
Order name
Optical Smoke Detector/Conv./FC600 FC600/O