LST FC600/BREL - Manual
LST FC600/BREL – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
FC600-BREL_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
• Suitable for automatic detectors in
conventional technology
• Relay output with dry changeover
contact
• Designed for indoor surface
mounting
• Terminals for connection of external
remote indicator
• Anti-tamper locking feature
Description
Specifi cations
Operating voltage
10 – 28VDC
Current consumption
max. 3µA (normal condition), 17mA (active)
Contact rating
1A at 30VDC
Ambient temperature
-30°C to +70°C
Relative humidity
5 – 95% (no condensation)
Dimensions ø × h
111 × 27 (mm)
Colour
white
Weight
58g
Order number
246072
Order name
Detector Relay Base/FC600 FC600/BREL
The detector base FC600/BREL is designed for the easy
connection of automatic detectors of Series FC600 in
conventional technology. Thanks to its robust sharable
connection terminals, the detectors can be durably wi-
red in secure screw joints with virtually no effort. The
base provides an easy connection option for an exter-
nal remote indicator and is designed for wall mounting
in dry rooms. The integrated relay output with a dry
changeover contact is active when the detector is in
the alarm condition. By breaking out a plastic bolt in
the base, the detector that has been inserted can be
secured against unauthorized removal.