A
Building Safety. Building Security.
Description
Specifi cations
The Safety Barrier ES58-2 for the galvanic isolation of
the detectors in the hazardous area serves for the de-
sign of an intrinsically safe electric circuit. The plastic
surface-mount housing allows to mount the safety bar-
rier near the hazardous area.
The built-in zener barrier limits the current and the vol-
tage of the detector line, as well as the electric energy
stored in the intrinsically safe circuit. The maximum
number of detectors depends on the country-specifi c
regulations and can be found in the Connection of De-
tectors.
Due to the galvanic isolation, the earth leakage moni-
toring can remain activated in the fi re detection control
panel. Thus, the installation can also be monitored in
the hazardous area.
• Allows to create intrinsically safe
circuits
• Galvanic isolation of the detector line
voltage
• Connection of intrinsically safe
detectors
• Industrial plastic surface-mount case
• ATEX certifi ed
Ignition protection
intrinsically safe
Ex classifi cation
EEx ia llC
Operating voltage
Supply through the detector line voltage
Quiescent current
approx. 5mA
Ambient temperature
-20°C to +60°C
Dimensions W × H × D
120 × 160 × 90 (mm)
Colour
light grey, similar to RAL 7035
Weight
650g
Approval
BASEEFA98ATEX7343
Order number
228003
Order name
Safety Barrier/Conv. ES58-2