Description
The Thermal Max Detector ECO1005T recognises a
maximum temperature of 58°C as sign of fi re. It com-
plies with Class A2S and can be used up to a room
height of 6m.
Addressable conventional technology is used for alarm
transmission to the fi re detection control panel. By
means of the Address Module NG58-1, each detector
can be addressed individually.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. The detec-
tor can be attached to various detector bases and it
can be protected against theft.
• Addressable conventional technology
• Alarm temperature 58°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Function testable with Remote Test
Unit ECO1000RTU
Specifi cations
Operating voltage
Supply through the detector line voltage
Current consumption
typ. 75µA (quiescent)
Alarm temperature
typ. 58°C
Operating temperature
max. +45°C
Ambient temperature
-30°C to +70°C
Relative humidity
5 – 95% (no condensation)
Dimensions ø × H
102 × 40.5 (mm)
Colour
white
Weight
70g
Approval
VdS G201073
Order number
242046
Order name
Thermal Max Detector/Conv./1000/SS ECO1005T