Building Safety. Building Security.

Description

The Optical-Thermal Detector ECO1002 uses both the

scattered light principle as well as a separate thermal

detection unit. It was developed to detect the charac-

teristics of fi re in a wide range of applications, and to

avoid deceptive alarms. The modern design of both

measurement systems and the analysis of the parame-

ters by means of a special algorithm allow to reliably

evaluate the characteristics of fi re. This makes it an

all-rounder that is used in virtually all fi elds of fi re de-

tection.

An internal drift compensation adjusts the alarm thres-

hold by continually evaluating the contamination of the

detector. With that, the sensitivity of the detector is

kept constant for a long time.

Addressable conventional technology is used for alarm

transmission to the fi re detection control panel. By

means of the Address Module NG58-1, each detector

can be addressed individually.

A test activation of the detector can be carried out

using the Remote Test Unit ECO1000RTU. The detec-

tor can be attached to various detector bases and it

can be protected against theft.

• Addressable conventional technology
• Combination of optical and thermal

characteristics of fi re

• Drift compensation
• Individual detector addressing by

means of optional address module

• Optional connection of remote

indicator

• Function testable with Remote Test

Unit ECO1000RTU

Specifi cations

Operating voltage

Supply through the detector line voltage

Current consumption

typ. 80µA (quiescent)

Alarm temperature

58°C (maximum-heat component)

Operating temperature

max. +45°C

Ambient temperature

-30°C to +70°C

Relative humidity

5 – 95% (no condensation)

Dimensions ø × H

102 × 40.5 (mm)

Colour

white

Weight

75g

Approval

VdS G201067

Order number

241046

Order name

Optical-Thermal Detector/Conv./1000/SS ECO1002