LST AMS-58000-700 - Manual

LST AMS-58000-700

LST AMS-58000-700 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

AMS-58000-700_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

The addressable Optical-Thermal Detector AMS-

58000-700 uses the scattered light principle as well as

a separate thermal detection unit. It was developed to

detect the characteristics of fi re in a wide range of ap-

plications, and to avoid deceptive alarms. The modern

design of both measurement systems and the analysis

of the parameters by means of a defi ned algorithm al-

low to reliably evaluate the characteristics of fi re.

The response sensitivity and the operating mode of the

detector can be selected in 5 steps (optical-only ope-

ration, thermal-only operation as well as three multisen-

sor levels), via the fi re detection control panel.

The proven ADM loop technology with Apollo/Discove-

ry protocol establishes a permanent communication

between the fi re detection control panel and the de-

tector. That ensures a periodical function testing of the

detector.

The infl uence of contamination of the optical measure-

ment system is compensated for by using intelligent

evaluation algorithms. With that, the response sensiti-

vity of the detector is kept constant for a long time –

a further effective step to avoid false alarms.

The two LEDs with 360° visibility indicate the activa-

ted condition of the detector. The detector address

is selected by means of a code card in the detector

base. Therefore the detector can be changed without

additional tools.

The detector can be attached to various bases and it

can be protected against theft.

• ADM loop technology with

Apollo/Discovery protocol

• Combination of optical and thermal

characteristics of fi re

• Alarm temperature 58°C
• Several sensitivity levels as well

as thermal-only and optical-only

operation selectable

• Constant response sensitivity
• Sealed electronics