LST 55000-588 - Manual

LST 55000-588

LST 55000-588 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
Page: / 1
Loading the manual

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

55000-588_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

The addressable Module 55000-588 serves for the

line-monitored integration of three contact detectors,

such as manual call points, sprinkler system contacts

or supervising contacts, into the bidirectional communi-

cation on the ADM loop with Apollo/Discovery protocol.

Furthermore, it can be used to actuate external devices

by means of three relay outputs, each with a single-pole

dry change-over contact, via the ADM loop.

The address is easily selected by means of a built-in DIL

switch. Individual status LEDs indicate the condition of

every input and output. The module has an integrated

dual-isolator and is fi tted into a plastic case.

• ADM loop technology with

Apollo/Discovery protocol

• 3 line-monitored inputs and

3 dry relay outputs

• Setting of module address by means

of address switch

• Integrated dual-isolator
• Status LED for each input and output

Specifi cations

Operating voltage

Supply through loop voltage

Current consumption

approx. 3mA (quiescent)

Contact rating

1A/30VDC or AC

Ambient temperature

-20°C to +70°C

Dimensions L × W × H

250 × 175 × 75 (mm)

Colour

white

Weight

621g

Approval

VdS G202052

Order number

249077

Order name

Module 3xSurv.In 3xRel.Out/Apo 55000-588