A
Building Safety. Building Security.
Description
The addressable Module 55000-588 serves for the
line-monitored integration of three contact detectors,
such as manual call points, sprinkler system contacts
or supervising contacts, into the bidirectional communi-
cation on the ADM loop with Apollo/Discovery protocol.
Furthermore, it can be used to actuate external devices
by means of three relay outputs, each with a single-pole
dry change-over contact, via the ADM loop.
The address is easily selected by means of a built-in DIL
switch. Individual status LEDs indicate the condition of
every input and output. The module has an integrated
dual-isolator and is fi tted into a plastic case.
• ADM loop technology with
Apollo/Discovery protocol
• 3 line-monitored inputs and
3 dry relay outputs
• Setting of module address by means
of address switch
• Integrated dual-isolator
• Status LED for each input and output
Specifi cations
Operating voltage
Supply through loop voltage
Current consumption
approx. 3mA (quiescent)
Contact rating
1A/30VDC or AC
Ambient temperature
-20°C to +70°C
Dimensions L × W × H
250 × 175 × 75 (mm)
Colour
white
Weight
621g
Approval
VdS G202052
Order number
249077
Order name
Module 3xSurv.In 3xRel.Out/Apo 55000-588