LST 2251TEM - Manual
LST 2251TEM – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
2251TEM_DBL_LST_EN_0819.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The addressable Multisensor 2251TEM uses the
scattered light principle as well as a separate thermal
detection unit. It was developed to detect the charac-
teristics of fi re in a wide range of applications, and to
avoid deceptive alarms. The modern design of both
measurement systems and the analysis of the parame-
ters by means of a special algorithm allow to reliably
evaluate the characteristics of fi re.
The sensitivity of the detector can be individually adjus-
ted in 5 steps between 1.5%/m and 5.2%/m according
to the application. Three steps have a fi xed sensitivity,
whereas two self-learning steps automatically adjust the
sensitivity to short-term changes of the environmental
conditions. Furthermore, the optical detection unit can
be completely disabled for a thermal-only operation.
The proven ADM loop technology with System Sen-
sor/200 protocol establishes a permanent communi-
cation between the fi re detection control panel and the
detector. That ensures a periodical function testing of
the detector.
The infl uence of contamination on the optical measu-
rement system is compensated for by using intelligent
evaluation algorithms. With that, the response sensiti-
vity of the detector is kept constant for a long time –
a further effective step to avoid false alarms.
The two LEDs with 360° visibility indicate the activated
condition of the detector. The detector address is se-
lected with two decadic rotary switches, thus allowing
to change the detector without additional tools.
A detector function test can be conveniently conducted
using a magnet. The detector can be attached to va-
rious bases and it can be protected against theft.
• ADM loop technology with
System Sensor/200 protocol
• Combination of optical and thermal
characteristics of fi re
• Two self-learning and three fi xed
sensitivity levels
• Thermal-only operation
• Constant response sensitivity
• Function testable with magnet
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.