LST 2251EIS - Manual

LST 2251EIS

LST 2251EIS – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
Page: / 2
Loading the manual

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

Ex-Sys200_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

IS Optical Smoke Detector 2251EIS

Specifi cations

Ignition protection

intrinsically safe

Ex classifi cation

EEx ia IIB T5

Operating voltage

Supply through loop voltage

Current consumption at 24V

330µA

Ambient temperature

-25°C to +70°C

Relative humidity

5 – 95% (no condensation)

Dimensions ø × H

103 × 43 (mm)

Colour

cream

Weight

110g

Approval

BASEEFA03ATEX0157X

LPCB 199m

Order number

241025

Order name

IS Optical Smoke Detector/Anal./200/SS 2251EIS

The addressable Intrinsically Safe Optical Smoke Detec-

tor 2251EIS (fi g. A) uses the scattered light principle

and was developed for the detection of smoke particles

in hazardous areas. The modern design of the sensing

chamber allows to reliably evaluate the characteristics

of fi re.

The proven ADM loop technology with System Sen-

sor/200 protocol establishes a permanent communica-

tion between the fi re detection control panel and the

detector. That ensures a periodical function testing of

the detector. In the control panel all types of fi res are

detected by continuously comparing fi re patterns.

Intelligent evaluation algorithms use the current condi-

tion of the sensing chamber to predict the likely time

of the next maintenance. Thus the alarm threshold is

automatically adjusted within the permissible range, de-

pending on the contamination. With that, the constant

response sensitivity of the detector is ensured for a

long time.

The two LEDs with 360° visibility indicate the activated

condition of the detector. The detector address is selec-

ted with two decadic rotary switches, thus allowing to

change the detector without additional tools.

A detector function test can be conveniently conducted

using a magnet or test gas. The detector can be pro-

tected against theft.

• Optical smoke detector
• Safety barrier with galvanic isolation
• Protocol interface for communication

with the fi re detection control panel

• ATEX certifi ed

fi g. A

fi g. B

fi g. C