Page 2 - RECOMMENDATIONS FOR PROPER PROTECTION; Devices Help Provide Proper Coverage for the Protected Premises.; in garages is not normally recommended.; Recommendations For Proper Intrusion Protection; ii
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscr...
Page 3 - Table Of Contents; AUXILIARY DEVICE CURRENT DRAW WORKSHEET; Interactive Mode Programming (; iii
Table Of Contents Features and Installation Highlights............................................................................................................1-1 Capabilities and Functions...............................................................................................................
Page 4 - Panic Keys; iv
Table Of Contents (continued) Data Field Programming .................................................................................................................................4-1 About Data Field Programming ........................................................................................
Page 5 - S E C T I O N 1; Features and Installation Highlights; This manual applies to the following Honeywell security systems:; unless otherwise noted.; Capabilities and Functions; ADEMCO VISTA-20P Series
S E C T I O N 1 Features and Installation Highlights This manual applies to the following Honeywell security systems: ADEMCO VISTA-20P/ADEMCO VISTA-20PSIA/ADEMCO VISTA-20PCN (collectively referred to as VISTA-20P series), ADEMCO VISTA-15P/ADEMCO VISTA-15PSIA/ADEMCO VISTA-15PCN (collectively referred...
Page 6 - Compatible Devices; Notes; Important Installation Highlights (Installer Please Read); This system provides various paging features. Refer to the
Compatible Devices Device VISTA-20P VISTA-15P Notes Addressable Keypads 8 8 6150 Fixed-Word Keypad, 6160 Alpha Keypad, 6150V Fixed-Word Display Voice Keypad, 6160V Alpha Display Voice Keypad, 6150RF Keypad/Transceiver Touch Screen (AUI) Devices 2 2 Touch Screen (AUI) devices are in addition to the 8...
Page 7 - S E C T I O N 2; Mounting and Wiring the Control; Installing the Control Cabinet and PC Board; Cabinet and Lock; Mount the control cabinet to a; Figure 1. Installing the Cabinet Lock; Figure 2. Mounting the PC Board; block RF transmissions from wireless transmitters.
S E C T I O N 2 Mounting and Wiring the Control Installing the Control Cabinet and PC Board Cabinet and Lock 1. Mount the control cabinet to a sturdy wall in a clean, dry area, which is not readily accessible to the general public, using fasteners or anchors (not supplied) with the four cabinet moun...
Page 8 - Figure 3. Mounting the PC Board and RF Receiver; DEVICE; CALIFORNIA STATE FIRE MARSHALL (CSFM) AND UL RESIDENTIAL FIRE; OUTPUT LIMITATIONS AND CORRESPONDING REQUIRED BATTERIES; Installation and Setup Guide
ANTENNA MOUNT (2 PLACES) ANTENNA (2) SCREW (2) BLACK MOUNTING CLIP RED MOUNTING CLIP WHITE MOUNTING CLIP GROUNDING LUG (2) NOTE A COMBINATION OF THESE MOUNTING CLIPS HAS BEENINCLUDED IN YOUR INSTALLATION KIT.USE THE APPROPRIATE CLIPS FOR MOUNTING. IF NO RF RECEIVER IS USED, MOUNT THE PC BOARD USINGE...
Page 9 - AC Power, Battery, and Ground Connections; Wire Run Chart; Up to 50 feet; Do not plug the transformer into the AC outlet; Canadian Installations:; UL
AC Power, Battery, and Ground Connections 1321 Transformer TO TERMINALS 1 AND 2 1321X10-001-V0 1 2 Connect the 1321 Transformer (1321CN in Canada) to terminals 1 and 2 on the control board. See Wire Run Chart for wire size to use. • Use caution when wiring the transformer to the control to guard aga...
Page 10 - Basic Connections; The 12VDC sounder output activates when an alarm occurs.; Supervised output; Connecting the Keypads and Other Addressable Devices; Connections; Keypads; Figure 6. Using a Supplementary Power Supply
Sounder (Bell) Connections Basic Connections spkr_conn-001-V0 ALARM OUTPUT 10.5 - 13.5 VDC 2A MAX. 3 4 Make sounder connections to alarm output terminals 3 (+) and 4 (–). • The 12VDC sounder output activates when an alarm occurs. • Total current drawn from this output cannot exceed 2 amps (going bey...
Page 11 - Table of Devices Addresses; See; The first keypad is address 16; TOTAL CURRENT DRAWN BY ALL DEVICES CONNECTED TO A SINGLE WIRE RUN; Size; Table of Device Addresses; This Device
Keypad Notes ARMED READY 1 OF F 4 MA X 7 INST ANT REA DY 2 AW AY 5 TES T 8 CO DE 0 3 STA Y 6 BYP ASS 9 CH IME # Set device addresses. Refer to the instructions included with the devices and set each address according to the Table of Devices Addresses . See Keypad Programming Fields (fields *190-*196...
Page 12 - Hardwire Zones and Zone Expansion; Double-Balanced Zones; Zone Doubling; Zone Doubling Table; Power
Hardwire Zones and Zone Expansion Hardwire Zones zones-001-V0 HI LO Normally Open Zones/ N.O. EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2. Enable normally open/EOLR zones using Zone Programming m...
Page 13 - Smoke Detector Notes; The control panel will “verify” a fire alarm by; Figure 9a. 4-Wire Smoke Detector Using Relay for Power Reset; Figure 9b. 4-Wire Smoke Detector Using Output 17 for Power Reset
Smoke Detector Notes •••• Fire Verification (zone type 16): The control panel will “verify” a fire alarm by resetting the smoke detectors after the first alarm trigger, and then waiting 90 seconds for a second alarm trigger. If the smoke detector or thermostat does not trigger again, the control wil...
Page 14 - Installing the RF Receiver and Wireless Transmitter Zones; Compatible Receivers; RF Receiver Notes
BRN GRN BLK (–) GROUND RED (+) 12VDC YEL 432 1 ZONES A B C D F G H DIP SWITCH FOR SETTING ADDRESSAND ZONE "A" RESPONSE TAMPER JUMPER POSITION 4229 IN CABINET(NOT TAMPER) 4229 REMOTE(TAMPER PROTECTED) TB1 4 2 2 9 TB2 WHT GR Y VIO BLK YEL ORG NO NC C GND NO NC C RLY 1 RLY 2 RELAYS OFF RELAY CO...
Page 15 - Testing the System; Limitations of This Alarm System
Installing a 5800TM Module • Use this module only if you are using one or more wireless bi-directional keypads or keyfobs with a wireless Receiver; 5800TM is not necessary if using a Transceiver (e.g., 5883). • The 5800TM must be set to address 28 (cut red-W1 jumper). • The 5800TM can be used in par...
Page 16 - Installing a Keyswitch; Using a standard keypad cable as shown:; Figure 12. Keyswitch Wiring Connections; Use only one keyswitch per partition.
Installing a Keyswitch Keyswitch Connections GREEN RED 1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8) terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone. 2. Using a standard keypad cable as shown: Connect the yellow and white keyswitch...
Page 17 - Connecting Keypads and Other Addressable; Figure 14. PSC04 Powerline Interface Connections
Connecting Relay Modules, Powerline Carrier Devices and Output Triggers 4204/4229 Relay Modules UL For UL installation requirements, refer to the Installation Instructions for the 4204. 1. Mount either remotely or in the control panel. 2. Connect each module to the control’s keypad terminals and set...
Page 18 - with SA4120XM-1 Cable for Use With; that draws less
On-Board Triggers Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip. • If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1 cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section fo...
Page 19 - Phone Line; connect cord and make all connections exactly as shown.; accessing the system from an on-premises phone.; Phone Module Problems
Phone Line/Phone Module, and Audio Alarm Verification (AAV) Connections Phone Line Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual. Wire colors represent the colors of the cable to...
Page 20 - Connections use one of the on-board triggers.
Audio Alarm Verification Connections (AAV, “listen-In”) • Refer to the connection diagrams below. One diagram shows connections when a 4285/4286 Phone Module is used, the other shows connections when the 4285/4286 is not used. • Connections use one of the on-board triggers. • Set field *91 for AAV a...
Page 21 - S E C T I O N 3; Programming Overview; About Programming; Section 5. Menu Mode; Mechanics of Programming
S E C T I O N 3 Programming Overview About Programming • You can program the system at any time, even at the installer's premises prior to the actual installation. • Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass down...
Page 22 - Entering Interactive Mode; Loading Factory Defaults/Initializing for Download; To Load Default Entries; Do not press; Zone Type Definitions; Zone Type
Interactive Mode Programming ( ∗∗∗∗ 56, *57, ∗∗∗∗ 58, ∗∗∗∗ 79, ∗∗∗∗ 80, ∗∗∗∗ 81, ∗∗∗∗ 82) Entering Interactive Mode Press [ ∗ ] + [Interactive Mode No.] (for example, ∗ 56) while in Program Mode. The Alpha display keypad will display the first of a series of prompts. After making the appropriate ent...
Page 25 - S E C T I O N 4; Data Field Programming; About Data Field Programming; must; Zone List Programming
S E C T I O N 4 Data Field Programming About Data Field Programming The following pages list this control’s data fields in numerical order. Valid entries for each field are shown in italics. Explanations and special notes are presented below the entries. Use the separate Programming Guide to record ...
Page 26 - feature always enabled field does; SIA; Enter up to 6 digits if PABX is needed to access an; Enter 4 or 10 digits, depending on selection in
*32 Fire Alarm Sounder Timeout 0 = yes; sounder timeout after time selected in field ∗ 33 1 = no timeout; sounds until manually turned off This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of th...
Page 28 - System Status Report Codes; ADEMCO Contact ID® Reporting:; With Contact ID format, the message will; before
System Status Report Codes Zone report codes are programmed using interactive ✱ 56 or ✱ 58 Zone Programming modes, while system status (non-alarm) codes and restore codes are entered in data fields *59 - *68, *70 - *76, *89. The actual report code digits that you enter depend upon the particular ins...
Page 29 - Always enabled. Field does not apply to other controls.; Miscellaneous System Fields; ALARM CANCELED
*69 Recent Closing Report V20PSIA/V15PSIA only Always enabled. Field does not apply to other controls. Similar to the Exit Error condition described in field *59, but occurs if an entry/exit door or interior zone is faulted within two minutes after the initial exit delay expires. Disarming the syste...
Page 30 - installer code only); Reentry; If an Event Logging selection is made in field; Call Waiting Disable:; = call waiting not used; = Same as “1” plus programmed output device STARTS.
*87 Misc. Fault Delay Time 0 = 15 secs 4 = 90 secs 8 = 4 min #+12 = 8 min 1 = 30 secs 5 = 2 min 9 = 5 min #+13 = 10 min 2 = 45 secs 6 = 2-1/2 min #+10 = 6 min #+14 = 12 min 3 = 60 secs 7 = 3 min #+11 = 7 min #+15 = 15 min Used with zones assigned to a configurable zone type with fault delay on (conf...
Page 31 - Unlimited Reports Enable:; = restrict reports to the setting in entry 1; field; Pager Programming Fields; Section 6. System Communication
*93 No. of Reports In Armed Period per Zone (Swinger Suppression) 0 = unlimited number of reports 1 = 1 report pair per zone per armed period 2 = 2 report pairs per zone per armed period Selection limits the number of alarm/alarm restore message pairs per zone sent to the CS in an armed period. SIA ...
Page 33 - Configurable Zone Type Fields; Configurable Zone Type 90; Important Notice on Report Codes:; System Communication; Configurable Zone Type 91; Configurable Zone Type Options
Configurable Zone Type Fields • The system allows you to define custom zone types (VISTA-20P supports 4 [types 90-93]; VISTA-15P supports 2 [types 90, 91]), based on the options described at right. • All configurable zone types can be programmed via the downloader. • Configurable zone types 90 and 9...
Page 34 - Configurable Zone Type Charts; Zone Conditions Represented; Configurable Zone Type Notes; both
Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Intact EOL RF zone normal Open RF zone N/A Shorted RF zn off-normal Auto Restore Vent Zone 0 = normal 1 = alarm 2 = trouble 3 = fault 0 = normal 4 = alarm 8 = trouble 12 = fault see note 5 0 = normal 1 = alarm 2...
Page 35 - AUI Compatibility Note:; Keypad Programming Fields; starting at address 16
Touch Screen Keypad (AUI) Enable The system supports up to two touch screen style keypads (e.g., Symphony Advanced User Interface (AUI), and 6270 Touch Screen keypad. NOTE: Use of touch screen devices does not affect the number of standard keypads supported. *189 AUI Device 1 and 2 Enable VISTA-20P:...
Page 37 - S E C T I O N 5; Menu Mode Programming; Zones and Partitions; Alpha Descriptor Programming; 6 Zone Programming Procedure; SET; Set to Confirm; We
S E C T I O N 5 Menu Mode Programming Zones and Partitions Each protection zone needs to be programmed with various attributes using *56 Zone Programming mode or ✱ 58 Expert Programming Mode. The VISTA-20P system can control two independent areas of protection (known as partitions) for use by indepe...
Page 38 - Zone Number; † if zone expanders are used.; Summary Screen; 0 Report Code; Hardwire Type; 2 Response Time
Enter Zn Num. (00 = Quit) 10 Zone Number VISTA-20P: wired 01-08 (and 09-48†); wireless 09-48; RF button zones 49-64 VISTA-15P: wired 01-06 (and 07-22†); wireless 09-34; RF button zones 49-56 Both Controls: 91 = addr. device report enable; 92 = duress report enable 95, 96, 99 =emerg. zones [ ∗ ] to c...
Page 39 - and cannot be edited.; Serial number Entry and Loop Number Entry; Used only when enrolling wireless transmitters.; Loop Number Change; Enter the loop number and press [; Enroll Summary
10 INPUT TYPE RF TRANS 3 Input Device type (In) 2 = AW (Aux wired zone) 3 = RF (supervised RF transmitter 4 = UR (unsupervised RF transmitter) 5 = Button type RF transmitter (unsupervised). [ ∗ ] to continue This prompt is skipped for zones 2-8, or 2-16 if zone-doubling was enabled at “Hardwire Type...
Page 40 - To Delete a Serial No.; Zn ZT RC In: L; ] to accept the zone information and continue.; Alpha Descriptors; If you want to program descriptors for zones now, enter; Next Zone Number; Completing Zone Programming; 8 Expert Programming Mode Procedures; Start Expert Programming mode by pressing; If
E n t d A 0 2 2 - 4 0 6 3 1 R c v d A 0 2 2 - 4 0 6 4 1 If Serial or Loop Numbers do not match after activating the transmitter [ ∗ ] to continue If the serial number transmitted does not match the serial number entered, a display similar to the one shown appears. If the loop number does not match, ...
Page 41 - OR [D] to go to prompts for wireless key programming templates; If programming a wireless key,; Zn; Zone Programming; A X X X - X X X –; Serial number; To Delete a Serial Number; Confirm
Zn ZT P RC HW: RT 01 09 1 10 EL 1 Zn ZT P RC IN: L 10 00 1 10 :RF – Summary Screen 01-64 = zone number; [ ∗ ] to continue; 00 = quit OR [D] to go to prompts for wireless key programming templates A summary screen appears, showing zone 1’s currently programmed values. Enter the zone number being prog...
Page 42 - If the loop number does; Zn ZT P RC In L; Wireless Key Programming Templates; This procedure programs the wireless keys,; but a key is not active for arming/disarming until it is; System Operation; PARTITION; To quit this mode; INPUT S/N L
Entd A022-4063 Rcvd A022-4064 If Serial or Loop Numbers do not match after activating the transmitter [ ∗ ] to continue I f the serial/loop number combination transmitted does not match the serial and loop number entered, a display similar to the one below will appear. If the loop number does not ma...
Page 43 - Not Confirmed; ONE; Wireless Key Predefined Default Templates; 804 Wireless Key Transmitter; Transmitter
XMIT TO CONFIRM PRESS ✱ TO SKIP Confirm [ ∗ ] to continue • If “Yes” was entered at the SET TO CONFIRM? prompt previously (see first prompt following entry into the ∗ 58 Expert Programming Mode), the display on the left will appear. Confirm serial and loop numbers by activating the wireless key. IMP...
Page 44 - Programming Output Devices; This output...; Relays
About Output Device Programming (*79/*80 Menu Mode) Output Devices: The VISTA-20P system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mo...
Page 45 - (prompt appears only for Triggers 17 and 18); Module Addresses; Address Module
Start Output Device Mapping by pressing *79 while in Data Programming Mode. ∗∗∗∗ 79 Menu Mode ENTER OUTPUT NO. 00 = QUIT xx Device Output Number 01-18 = VISTA-20P relays/X-10; 01-08, 17, 18 = VISTA-15P relays/X-10 [ ∗ ] to continue; 00 to quit This is the logical (or reference) relay number as used ...
Page 46 - *80 Menu Mode: Defining Output Functions; Output Definition Components; Component; Prompt Entry; 1 (assuming this is the first output function); 1 A E P Trig; Trig; Zone List; Activated By
*80 Menu Mode: Defining Output Functions Use this mode to program output function definitions (up to 48 functions) that provide automated control of any of the output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an o...
Page 47 - CHOICES FOR ZONE TYPES:
“ A ” 01 Zn List 1 Zone List (prompt appears if zone list was selected) 01-08 = zone list; [ ∗ ] to continue Enter the desired zone list number associated with this output number. NOTE: Do not use pager zone lists 09-12 in output definitions. Enter the zone list event that will activate this output....
Page 48 - 2 A E P TRIG; Used for...; 1 while in Data Programming mode.
Enter Output No. R02 02 Output Number 01-16 = VISTA-20P output no.; 01-08 = VISTA-15P output no.; 17-18 = on-board triggers Enter the device output number (programmed in *79 Menu Mode) you want associated with this output. Press [ ✱ ] to continue. 02 A E P TRIG R02 1 1 3 ZL=00 Summary Screen A summa...
Page 49 - Programming Function Keys; Start Function Key Programming mode by pressing; Press Key to Pgm; Function Key; A key programmed as a function; Partition Numbe; Enter the partition in which the function key is active.; Define Key Function; ] to returns to key number prompt with the next
About Function Keys (*57 Menu Mode) The system provides the ability to program each of the four keypad function keys to perform one of 12 system operations. The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds. Typical functions (listed below) i...
Page 50 - . The phone module will not provide annunciation of the other words.; boldface; in the Alpha; Programming Zone Descriptors (Menu Mode; following the prompts.; When defining descriptors:; P r o g r a m A l p h a ?; Program Alpha; C u s t o m W o r d s ?; Custom Words; Z N 0 1 B A C K
About Descriptor Programming (*82 Menu Mode) The system lets you assign zone descriptors for protection zones, keypad panics, and RF receiver supervision faults. Each description can be composed of a combination of words (up to 3) selected from a vocabulary of 196 words stored in memory (see a follo...
Page 51 - Accept First Word; if this is; Accept Second Word; if these are; ten; Assigning Partition/Custom Message Descriptors
✱ Z N 0 1 B A C K Accept First Word 6 = save word and go to next word in this descriptor; 8 = save word and go to next zone Press [6] to accept the selected word and continue to the next word, or press [8] if this is the only word you are using for the descriptor. ✱ Z N 0 1 B A C K D O O R Second 3-...
Page 52 - ALPHA VOCABULARY LIST; boldface type; Italicized; VISTA-20SE Installation Instructions
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) 000 (Word Space) – A – • 001 AIR • 002 ALARM ∗∗∗∗ 004 ALLEY 005 AMBUSH • 006 AREA • 007 APARTMENT • 009 ATTIC ∗∗∗∗ 010 AUDIO – B – • 012 BABY ∗∗∗∗ • 013 BACK ∗∗∗∗ • 014 BAR • 016 BASEMENT ∗∗∗∗ • 017 BATHROOM ∗∗∗∗ • 018 BED • 019 BEDROOM ∗∗∗∗ 020 ...
Page 53 - Programming Installer and User Schedules
Programming Installer and User Schedules The system provides schedules, which can be used to automatically control 11 types of system events at pre-defined times. Some events are reserved for the installer only. VISTA-20P: Provides up to 32 schedules: 16 schedules for use by the end-user, 16 for use...
Page 54 - Stop Time; forward, then press “1” to select the day.; Repeat Option; Randomize
S T O P S M T W T F S H H M M A M 0 0 1 0 0 0 0 Stop Time (For events 01-relay on/off; 02-user access; 03-latch key report) 01-12 = hour; 00-59 = minute; 0 = AM; 1 = PM; Days = place “1” under days Press [ ∗ ] to continue. Enter the event’s stop time and days of the week to occur. To select days, po...
Page 55 - S E C T I O N 6; System Communication and Operation; Panel Communication with Central Station; FORMAT; FORMAT TYPE
S E C T I O N 6 System Communication and Operation Panel Communication with Central Station This system accommodates several formats for reporting alarms and other system conditions to the Central Station. The process of a successful transmission consists of both the method of communication between ...
Page 57 - Ademco Contact ID; TABLE OF CONTACT ID EVENT CODES; Code
Ademco Contact ID ® The Ademco Contact ID ® Reporting Format comprises the following: 4-digit or 10-digit subscriber number (depending on format selected). 1-digit event qualifier (“new” or “restore”). 3-digit event code. 2-digit Partition No. 3-digit zone number, user number, or system status numbe...
Page 58 - System Security Codes; Partition Master codes, and 45 general user codes.; Authority Levels; Level; keyfob must be enrolled in system first; Wireless Key
System Security Codes The systems provides one Installer code, one System Master code, plus a set of other user codes intended for other users of the system. These codes can each be assigned one of 5 authority levels, which determine the functions each code can perform as listed in the table below. ...
Page 59 - Keypad Functions; Voice Keypads; The 6150V/6160V Voice Keypads provide the following features:; Keypad Commands; Function
Keypad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. For Touch Screen style keypad users, refer to the separate Touch Screen keypad (AUI) User’s Guide. Voice Keypads The 6150V/6160V Voice Keypads provide ...
Page 60 - SUMMARY OF ARMING MODES; Features for Each Arming Mode; The Panic keys are identified by the system as follows:; Setting the Real-Time Clock; Set the time and date by doing the following:; Time/date editing display
SUMMARY OF ARMING MODES Features for Each Arming Mode Arming Mode Exit Delay Entry Delay Perimeter Armed Interior Armed AWAY Yes Yes Yes Yes STAY Yes Yes Yes No NIGHT-STAY Yes Yes Yes only those zones listed in Night- Stay zone list INSTANT Yes No Yes No MAXIMUM Yes No Yes Yes Panic Keys There are t...
Page 61 - Various System Trouble Displays; Alpha Display
Various System Trouble Displays Alpha Display Fixed Disp. Meaning ALARM CANCELED CA will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay time. The alarm sounder and ke...
Page 63 - S E C T I O N 7; About Test Procedures; Automatic battery tests are performed by the system.; System Test; necessary, so that the “READY” message is displayed.; TEST; Checking Transmitter Enrollment (Sniffer Mode); that transmitter disappears from the display.
S E C T I O N 7 Testing the System About Test Procedures After the installation is complete, you should perform the following tests: System Test: Checks that all zones have been installed properly and the system responds to faults. Dialer Test: Checks that the phone connection to the central station...
Page 64 - one; Dialer Communication Test and Periodic Test Reports; Automatic Periodic Test Report; = test report sent every 24 hours
NOTES: • All BR type units must physically be activated to clear the display. • When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to other buttons on that transmitter are cleared from the display. This also applies to 5816 and 5817 transmitters, which have multiple lo...
Page 65 - S E C T I O N 8; Specifications & Accessories; Security Control; not; Long Range Radio
S E C T I O N 8 Specifications & Accessories Security Control 1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, ADEMCO 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 4AH (sealed lead acid type). Charging Vo...
Page 66 - Detector Type; System Sensor
2-Wire Smoke Detector: Detector Type System Sensor Model No. Photoelectric w/heat sensor, direct wire 2300TB Photoelectric, direct wire 2400 Photoelectric w/heat sensor, direct wire 2400TH Photoelectric 2451 w/B401B base Photoelectric w/heat sensor 2451TH w/B401B base Ionization, direct wire 1400 Io...
Page 67 - 800 Series Transmitter Input Loop Identification; The following transmitters are; Compatible 5800 Series Transmitters Table; Model Product
5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones). 5802MN ENROLL AS "UR&...
Page 68 - Compatible 5800 Series Transmitters Table (continued)
Compatible 5800 Series Transmitters Table (continued) Model Product Input Type Description 5817 Multi-Point Universal Transmitter RF Has three unique input (loop) codes: one for a “Primary” contact loop with programmable options; the others for two “auxiliary” closed circuit contact loops. 5818 Rece...
Page 69 - S E C T I O N 9; Regulatory Agency Statements; RADIO FREQUENCY EMISSIONS; Federal Communications Commission (FCC) Part 15; TELEPHONE/MODEM INTERFACE; Industry Canada; Ringer Equivalence Number Notice:; Industrie Canada
S E C T I O N 9 Regulatory Agency Statements RADIO FREQUENCY EMISSIONS Federal Communications Commission (FCC) Part 15 This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device mus...
Page 70 - UL NOTICES; 6) cannot be greater than 30 seconds for UL; Notes for SIA Installations; disable option in field *91 must be set.
UL NOTICES 1. Entry Delay No. 1 and No. 2 (fields ✱ 35, ✱ 36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds. 2. F...
Page 75 - S E C T I O N 1 0; Limitations and Warranty; WARNING; alarm sensor or disconnect an alarm warning device.
S E C T I O N 1 0 Limitations and Warranty WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compr...
Page 77 - – INDEX –
– INDEX – 1-9 1321 AC Transformer ...... 1-2, 2-3, 2-11 1361X10 ................. 2-3, 2-11, 2-12, 8-2 24-Hour Audible Alarm .................... 3-3 24-Hour Auxiliary Alarm ................... 3-3 24-Hour Silent Alarm ....................... 3-3 3+1 and 4+1 Standard Formats ..... 6-1 42041-2, 2-2, ...
Page 79 - Figure 17. Summary of Connections
CLASS 2 PLUG-IN TRANSFORMER 16.5V A C , 25V A (e .g. ADEMCO No . 1321). (USE No . 1321CN IN CANAD A) T O 110V A C UNSWITCHED OUTLET (24HR) + THIS EQ UIPMENT SHOULD BE INST ALLED IN A CCORD ANCE WITH THE NA TIONAL FIRE PR O TECTION ASSOCIA T ION'S ST AND ARD 72, CHAPTER 2 (NA T IONAL FIRE PR O T EC...
Page 80 - LIMITED WARRANTY; or other events occurring without providing an alarm, but
LIMITED WARRANTY Honeywell International Inc., acting through its Security & Custom Electronics business ("Seller") 165 Eileen Way, Syosset, New York 11791, warrants its product(s) to be in conformance with its own plans and specifications and to be free from defects in materials and wor...