TB6980/TB7980
1/6
1. Introduction
The TB6980/TB7980 digital thermostats provide proportional plus
integral individual space temperature control in zoned commercial
HVAC systems such as hydronic and pressure dependent VAV with
or without reheat. There are four different models:
Depending on the models, the thermostat can have up to three out-
puts for the following applications:
Floating or Modulating damper/valve actuator control
Damper/valve actuator control with duct reheat and auxiliary
heat (B models only)
Hydronic systems (room control, perimeter heating and cool-
ing)
Accessories
R841 family of electromechanical relays
T7770A3002 remote room sensor
50014156-002 remote room sensor
32004800-001 bare thermistor
50014157-001 duct temperature sensor
2. Installation
2.1 Mounting Instructions
1.
Remove the thermostat from its base by unscrewing the cap-
tive screw and tilting the bottom of the thermostat up. The
screw cannot be completely removed.
2.
Pass the wires through the center hole of the base and secure
the base to the wall or onto an electrical box.
3.
Wire the thermostat. See section 2.2 for terminal designations
and section 3 for typical wiring diagrams.
4.
Reinstall the thermostat onto its base and secure with the cap-
tive screw.
2.2 Terminal Designations
The designations of the terminals vary according to the particular
model of thermostat. Refer to the following table for the description
of each terminal.
• TB7980A (single output, modulating)
• TB6980A (single output, floating)
• TB7980B (multiple output modulating)
• TB6980B (multiple output, floating)
Configuration and status display
Heating mode
Temperature display
Output power display
Temperature
adjustment
button
Cooling mode
Override button
TERMINAL
DESCRIPTION
1
2
24 VAC
COM
Power supply
3
4
AN1
COM
Output 1
TB7980 models
3
4
OPEN
CLOSED
TB6980 models
5
6
T2/AN2
T2/COM
Output 2 (TB6980B and TB7980B models)
7
8
T3
T3
Output 3 (TB6980B and TB7980B models)
9
10
COM
SENSOR
External sensor input. (For applications requiring
an external sensor, see section 4.2.)
9
11
COM
C-Over
Mode Changeover input (N.O. contact). See sec-
tion 5.5.2.
9
12
COM
NSB
Night Setback activation input (N.O. contact).
See section 5.6.
Note
: To configure the terminals, see section 4.
TB6980/TB7980
Installation and User Guide
ZonePRO Thermostats
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
TB6980/TB7980 2/6 3. Typical Applications FIGURE 1 : Damper control with electric reheat and auxiliary baseboard heating. FIGURE 3 : Damper control with automatic changeover, electric reheat and central cooling FIGURE 5 : Changeover and NSB inputs sharing the same 24-Vac transformer FIGURE 6 : Chang...
TB6980/TB7980 3/6 4. Configuration 4.1 Configuration Menus (See following pages for explanations) TB7980A model Application (section 4.2) Default mode & Output 1 type (section 4.3.1) NSB value (section 5.6) Output 1 min. opening (section 4.3.2) Maximum setpoint (section 4.6) Minimum setpoint (se...
TB6980/TB7980 4/6 4.2 Application Types The following table shows the different thermostat applications andtheir corresponding settings in the configuration menu. 4.3 Output 1 Output 1 is used to control a damper. It controls heating when thethermostat is in heat mode or cooling when the thermostat ...