CAUTION

Disconnect power supply before beginning instal-
lation to prevent electrical shock or equipment
damage.

LOCATION

Locate the thermostat about 5 ft [1.5 m] above the floor

on an inside wall in an area with good air circulation at
average temperature.

Do not mount the thermostat where it can be affected by:
— drafts or dead spots behind doors or in corners.
— hot or cold air from ducts.
— concealed pipes and chimneys.
— radiant heat from the sun, fireplaces, or appliances.
— unheated (uncooled) areas behind the thermostat,

such as an outside wall.

MOUNTING AND WIRING

Disconnect power supply before beginning installation

to prevent electrical shock or equipment damage.

All wiring must comply with local codes and ordi-

nances.

T822A,D,F,G and TS822A Thermostats are designed to

be mounted vertically on a wall or a vertical outlet box.
T8022D is designed to be mounted horizontally on a wall.

In a 250 or 500 mV application, use No. 14 wire if

possible and make the run as short as possible; remember
this when selecting a location. For maximum wire lengths
of a 750 mV application, see Table 1.

TABLE 1—WIRE LENGTH.

Max. Combined

Wire

Max. Length

Length

Size

2-Wire Cable

2-Single Wires

ft

m

ft

m

No. 18

30

9.0

60

18.0

No. 16

50

15.0

100

30.0

No. 14

80

24.5

160

40.0

1. In replacement applications, check the existing ther-

mostat wires for cracked or frayed insulation. Replace any
wires in poor condition. If the wire is plastered into the
wall, make a hole next to the wires and loosen the wires so
they can be pushed back into the wall later.

2. In new installations, run wiring (if necessary) to the

thermostat location.

3. Connect the wires to the terminals on the back of the

thermostat. See Figs. 1 through 6 for internal schematics
and typical hookup diagrams.

Application

T822A,D,F, TS822A, and T8022D Thermostats pro-

vide control of heating systems. T822G provides control of
AC heating or cooling appliances.

The T822A two-wire switch thermostat provides low

voltage control of heating systems and features a fixed heat
anticipator.

The T822D and T8022D two-wire, mercury switch

thermostat provides low voltage control of heating systems
and features an adjustable heat anticipator.

The T822F three-wire, mercury switch thermostat pro-

vides low voltage control of heating systems and features
an adjustable heat anticipator and AUTO-ON fan switch-
ing.

The T822G three-wire, mercury switch thermostat pro-

vides low voltage control of AC heating and cooling appli-
ances and features an adjustable heating anticipator and
nonadjustable cooling anticipator.

The TS822A two-wire, mercury switch thermostat pro-

vides millivoltage control of heating systems.

T822A,D; TS822A, and T8022D Thermostats are avail-

able with a positive OFF switch. All models are available
with temperature range stops.

Recycling Notice

If this control is replacing a control that contains mer-

cury in a sealed tube, do

not

place your old control in

thetrash.

Contact your local waste management authority for

instructions regarding recycling and the proper disposal of
this control, or of an old control containing mercury in a
sealed tube.

If you have questions, call Honeywell Inc. at

1-800-468-1502.

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazardous condi-
tion.

2. Check the ratings given in the Instructions and on the

product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced service tech-

nician.

4. After installation is complete, check out product

operation as provided in these Instructions.

CAUTION

J. H. • Rev. 2-01 • • ©Honeywell Inc. 2001 • Form Number 69-0510—4

T822A,D,F,G; TS822A; and T8022D

Low Voltage Thermostats

M3375

M3375

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Fig. 4—T822F in typical heating application.; Remove thermostat cover by pulling outward on

2 Fig. 3—T822A,D and T8022D in typical oilheating application. Fig. 4—T822F in typical heating application. Fig. 5—T822G in typical heating or coolingapplication. POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. T822D, T8022D ADJUSTABLE HEAT ANTICIPATOR SHOWN. T822A HAS A ...

Page 3 - Setting and Adjustment; TEMPERATURE SETTING; longer; Checkout; CAUTION

3 69-0510—4 Fig. 6—TS822A in typical millivoltage heatingapplication. Setting and Adjustment TEMPERATURE SETTING Move the temperature setting lever to the desired control point on the temperature scale. On positive off models, thecontrol circuit is broken when the lever is moved to theextreme low en...

Page 4 - RECALIBRATION; farther; Automation and Control Solutions

4 Move the temperature setting lever about 10 ° F [6 ° C] below room temperature. Cooling and fan should startimmediately. Move temperature setting lever about 10 ° F [6 ° C] above room temperature. Cooling and fan should stop immediately. RECALIBRATION These thermostats are calibrated at the factor...