Honeywell T775U- Manual
Honeywell T775U– Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Actuators; Product Selection Tool
- Page 3 – Controller Dimensions; BEFORE INSTALLATION; When Installing This Product; INSTALLATION AND SETUP; MOUNTING; Controller Mounting
- Page 4 – WIRING; Wiring Connections Access; CAUTION; Reset Temperature Control
- Page 5 – Temperature Sensor Wire Type and Size
- Page 6 – connection from Sensor A to 0-10 Vdc sensor
- Page 7 – Controller Wiring; WARNING; A separate earth ground is required.; Controller Wiring Method; Fig. 10. Attaching two or more wires at terminal
- Page 8 – Controller Wiring Details
- Page 9 – Fig. 13. Wiring for mod motor or direct coupled
- Page 10 – CHECKOUT; Power Loss
- Page 11 – INTERFACE OVERVIEW; Using the LCD Panel Interface; Home Button
- Page 12 – Up and Down Arrow Buttons (; HOME; Home Screen; Accessing the Menus; Setup Menu; Using the Menus; • Left arrow button
- Page 13 – PROGRAMMING OVERVIEW; Setpoint and Differential
- Page 14 – Setup Procedure; not
- Page 21 – all
- Page 22 – or
- Page 23 – each
- Page 25 – WITH NO
- Page 28 – WITH
- Page 33 – Creating a Schedule
- Page 35 – SCHEDULING EXAMPLE; DAY
- Page 36 – (exit from selected time period
- Page 37 – SUMMARY MENU; Error Message; EE; Diagnostic Messages; Blinking relay status; SPECIFICATIONS
- Page 38 – DoC; Emissions Compliance
- Page 40 – Automation and Control Solutions
INSTALLATION INSTRUCTIONS
62-0255-07
E4436
T775U Series 2000 Electronic
Stand-Alone Controller
PRODUCT DESCRIPTION
The T775 electronic stand-alone controllers are the next
generation of universal controls capable of remote
sensing of temperature, humidity, pressure, etc. and
providing switched and proportional outputs to various
types of loads. A built-in time clock is standard.
The T775U controller allows a wide range of sensors to
be configured. Humidity, pressure, temperature, or any
0-5 Vdc, 0-10 Vdc, or 4-20 mA input is supported.
A Reset function is available where the Sensor B
temperature (e.g. outside temperature) is used to provide
reset control for Sensor A (e.g. humidity). For example,
as the outside temperature gets colder, the setpoint can
automatically be adjusted to prevent condensation.
IMPORTANT
The T775U is an operating control, not a limit or
safety control. If used in applications requiring
safety or limit controls, a separate safety or limit
control device is required.
Table 1. T775U Controller Configurations.
Controller
Model
a
a
The T775U includes a digital input for use with the disable or setback option.
Description
Replaces
Output
Reset
SPDT
Relay
Outputs
Analog
(Mod)
Outputs
b
b
The modulating (analog) outputs may be 4-20 mA, 0-10 Vdc, 2-10 Vdc, or Series 90 selectable.
Sensor
Inputs
Nbr of
Sensors
Included Enclosure
T775U2006
Universal:
Humidity,
Pressure,
Temperature,
etc.
H775A1006
H775A1022
H775A1048
H775A1063
H775B1005
H775C1004
c
H775D1003
c
H775E1002
c
c
For the H775C1004, H775D1003, and H775E1002 model replacement, the T775U only partially replaces the function
of these devices. Check application for suitability.
Yes
2
2
2
d
d
For the sensor inputs, Sensor A can be 0-10Vdc, 4-20mA, or a standard temperature input. Sensor B is a standard
temperature sensor input only. Sensor B is used only for reset on the T775U2001.
None
NEMA 1
T775U2016
N/A
Yes
2
2
2
e
e
The T775U2016 can control Sensor A (universal) and Sensor B (temperature) independently, like other standard
T775 controllers.
None
NEMA 1
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Other Manuals for Honeywell T775U
Summary
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER 62-0255—07 2 Temperature Sensors a (Sensor A or B) The controller accepts 1,097 Ohms PTC at 77°F (25°C):• 50021579-001 – Standard sensor (included with all models except NEMA 4X models) • T775-SENS-WR – Water resistant with 5 foot leads (included w...
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER 3 62-0255—07 Controller Dimensions Fig. 1. T775U Dimensions in inches (mm). BEFORE INSTALLATION Review the “Specifications” on page 37 before installing the controller. When Installing This Product 1. Read these instructions carefully. Failure to f...
T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER 62-0255—07 4 Use a screwdriver to pry out only the knockouts that you will use. If mounting on DIN rail, be sure to remove the knockouts before mounting. See “Controller Wiring” on page 7 and Fig. 12 on page 9 for recommended knockout usage and loc...