Honeywell L - Manual
Honeywell L – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – SPECIFICATIONS
- Page 6 – INSTALLATION; WARNING
- Page 7 – Location; Humidity; Final Wiring Check
- Page 8 – Mounting R7140 Relay Module; Removing the Programmer
- Page 23 – SAFETY SHUTDOWN; any of the following occur during the; OPERATION; Sequence of Operation; Initiate
- Page 25 – SETTINGS AND ADJUSTMENTS; Selectable Site-Configurable
- Page 26 – STATIC CHECKOUT; Equipment Recommended
- Page 27 – CAUTION
- Page 28 – SYSTEM CHECKOUT
- Page 29 – Flame Signal Measurement; INITIAL LIGHTOFF CHECKS; Proved Pilot Systems
- Page 30 – Direct Spark Ignition Systems; PILOT TURNDOWN TEST (ALL
- Page 31 – IGNITION INTERFERENCE TEST; To Eliminate Ignition Interference
- Page 32 – Hot Refractory Hold-in Test; IGNITION SPARK RESPONSE; Response To Other Ultraviolet
- Page 33 – SAFETY SHUTDOWN TESTS
INSTALLATION INSTRUCTIONS
66-1153-03
R7140G,L,M
Burner Control Modules
APPLICATION
The Honeywell R7140G,L,M Burner Control Modules are
microprocessor-based integrated burner controls for
automatically fired gas, oil or combination fuel single burner
applications. The Burner Control Module system consists of a
Relay Module, Q520A Subbase, Amplifier and Purge Card.
Options include S7800 Keyboard Display Modules (KDM).
The R7140 Burner Control Modules directly replace many
BC7000 PM720G,L,M, and many R4150G,L,M and
R4140G,L,M units using the existing Q520A 20-terminal
Wiring Subbase.
The R7140 can be demonstrated or tested on the FSP5004
tester. Note that the R7849 UV Amplifier or the R7851 Optical
Flame Amplifier cannot be tested.
The R7140G,L,M is programmed to provide a level of safety,
functional capability and features beyond the capacity of
conventional controls.
Functions provided by the R7140G,L,M include automatic
burner sequencing, flame supervision, system status
indication, system or self-diagnostics and troubleshooting.
FEATURES
• Device status available to ModBus™ through S7810M
card or S7800A1001 Series 5 Keyboard Display.
• Safety features:
— Interlock check.
— Closed loop logic test.
— Dynamic AMPLI-CHECK™.
— Dynamic input check.
— Dynamic safety relay test.
— Dynamic self-check logic.
— Expanded safe-start check.
— High Fire Purge Switch test (R7140L only).
— Internal hardware status monitoring.
— Low Fire Start Switch test.
— Tamper resistant timing and logic.
• Application flexibility.
• 0.8 or 3.0 second Flame Failure Response Time (FFRT),
depending on amplifier selected.
• Dependable, long-term operation provided by
microcomputer technology.
• Five LEDs for sequence information. See Fig. 1.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Nonvolatile memory; history files and sequencing
status are retained after loss of power and can be
viewed using the Keyboard Display Module
S7800A1001 (sold separately).
• Report generation (optional) through modbus™.
NOTE: Check Service Notes on page 7 and Static Check-
out on page 26 prior to installation of R7140.
• Burner controller data (optional):
— Lockout/alarm status.
— Total cycles of operation.
— Total hours of operation.
• Status of configuration jumpers.
• Status of Run/Test Switch.
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
R7140G,L,M BURNER CONTROL MODULES 66-1153—03 2 Fig. 1. Burner Control Module and sequence status LEDs. SPECIFICATIONS Electrical Ratings (See Table 1): Voltage and Frequency: 120 Vac (+10%/-15%), 50 or 60 Hz (±10%). Power Dissipation in the Run Mode: 10W maximum. Maximum Total Connected Load: 2000VA...
R7140G,L,M BURNER CONTROL MODULES 66-1153—03 6 a 30 seconds with JR2 clipped and jumper from terminal 8 to terminal 15. * STANDBY and RUN can be an infinite time period. ** PURGE will be determined by which ST7800A purge card is selected; 15 timings are available from 2 seconds to 30 minutes. NOTE: ...
R7140G,L,M BURNER CONTROL MODULES 7 66-1153—03 Location Humidity Install the relay module where the relative humidity never reaches the saturation point. The relay module is designed to operate in a maximum 85 percent relative humidity continuous, noncondensing moisture environment. Condensing moist...