PRODUCT DATA
65- 0237- 1
CP-UM-5109E
® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved
C6097A,B
Pressure Switches
APPLICATION
The C6097 Pressure Switches are safety devices used in
positive-pressure or differential-pressure systems to sense
gas or air pressure changes.
FEATURES
• For use with natural gas, liquid propane (LP) gas,
or air.
• Diaphragm-actuated safety-limit switch.
• Switch can be wired to turn on alarm.
• C6097A models break control circuit at setpoint
on pressure fall.
• C6097B models break control circuit at setpoint
on pressure rise.
• Lockout with manual reset and recycle options.
• Lockout models have external manual reset
button.
• Removable transparent cover protects scaleplate
and adjusting knob.
• Pipe tappings allow selection of positive
pressure, differential pressure (air only) or
venting connections (NPT mount only).
• 1/4 in. NPT or flange mount models for direct
mounting to Honeywell Integrated Valve Train.
• Optional switch position indicator lamp available.
• IP54 enclosure standard.
• Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in.
wc or 1.5 to 7 psi.
• Surge orifice.
Contents
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Settings and Adjustments .................................................
Operation and Checkout ..................................................
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
C6097A,B PRESSURE SWITCHES 65-0237—1 2 ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,...
C6097A,B PRESSURE SWITCHES 65-0237—1 4 Table 2. Switch Ratings (Amperes) Table 3. Alternate Electrical Ratings when used with Honeywell Flame Safeguard Programmers. Fig. 2. C6097 Flange Mount dimensions in in. (mm). INSTALLATION WARNING Explosion or Fire Hazard. Can cause severe personal injury, dea...
C6097A,B PRESSURE SWITCHES 5 65-0237—1 WIRING WARNING Electrical Shock Hazard. Can cause serious personal injury or death. Disconnect power supply before beginning installation. More than one disconnection can be involved. Make sure that all wiring agrees with all applicable local codes, ordinances ...