Greenheck SMD-301V - Manual
Greenheck SMD-301V – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Pressure Drop Data; AMCA Test Figures
- Page 3 – AMCA 5.2 Pressure Drop
- Page 4 – AMCA 5.3 Pressure Drop
- Page 5 – AMCA 5.5 Pressure Drop
- Page 6 – Transitioned Damper Dimensions; Specifications
Model SMD-301V meets the requirements for smoke
dampers established by:
National Fire Protection Association
NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
New York City
(MEA listing #260-91-M)
CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing (#3230-0981:104)
Application
Model SMD-301V is a vertical blade low leakage rated smoke
damper. High strength airfoil blades insure lowest resistance to
airflow in HVAC systems with velocities to 4000 fpm (20.3m/s) and
4 in. wg (1.0 kPa).
UL555S Leakage Rating
Leakage Class:
I
Operational Rating
Maximum Velocity:
2000 fpm (20.3 m/s) up to
100 in. x 32 in. H
(2540mm x 813mm) or
4000 fpm (20.3 m/s) up to
50 in. x 32 in. (1270mm x 813mm)
Maximum Pressure:
4 in. wg (1 kPa)
Maximum Temperature:
350ºF (177ºC)
Standard Construction
Frame:
5 in. x 1 in. (127mm x 25mm)
galvanized steel hat channel with
reinforced corners. A low profile
head and sill are used on sizes
less than 17 in. (432mm) high to
maximize free area and
performance.
Blades:
Double skin airfoil shape of
galvanized steel with full length
structural reinforcement. 14 ga.
(2 mm) equivalent thickness.
Seals:
Extruded silicone rubber blade
seals. Flexible stainless steel
jamb seals.
Linkage:
Concealed in jamb.
Axles:
1
/
2
in. (13mm) dia. plated steel.
Bearings:
304 stainless steel
Size Limitations:
Minimum Size:
6 in. W x 8 in. H
(152mm W x 203mm H)
Maximum Size:
Single Section:
50 in. W x 32 in. H
(1270mm W x 813mm H)
Multiple Section:
100 in. W x 32 in. H
(2540mm W x 813mm H)
Optional Features:
• OCI (Open closed indication switches)
• Electric or pneumatic actuators to accomplish smoke
management and system functions.
• Transitions (R, C, O)
• POC retaining angles
• Momentary Switch
• Sealed transitions and sleeves
Model SMD-301V
Smoke Dampers
Steel Airfoil Blades
UL 555S Leakage Class I
*W&H dimensions furnished approximately
1
/
4
in. (6mm) undersize.
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555S (
Listing #R13317)
W*
H*
Installation instructions available at www.greenheck.com
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Pressure Drop Data SMD-301V This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft 3 (1.2 kg/m 3 ). Actual pressure drop found in any HVAC system is a combi...
12x12 24x24 AMCA 5.2 Pressure Drop SMD-301V 5D 6D 5D D 4 (W) (H) 3.14 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.03 500 0.01 500 0.01 500 0.01 500 ...
* Sizes are in inches. 12x12 24x24 AMCA 5.3 Pressure Drop SMD-301V 5D 6D 5D D 4 (W) (H) 3.14 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.01 500 0.01...