Greenheck SEFSD-211 - Manual

Greenheck SEFSD-211

Greenheck SEFSD-211 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
Page: / 7

Table of Contents:

  • Page 2 – Pressure Drop Data; AMCA Test Figures
  • Page 3 – AMCA 5.2 Pressure Drop; Pressure Drop
  • Page 4 – AMCA 5.3 Pressure Drop
  • Page 5 – AMCA 5.5 Pressure Drop
  • Page 6 – Damper Sleeve Dimensional Data; Application Data; Actuators and Accessories
  • Page 7 – Damper Sizing Information; Specifications; Transitioned Damper
Loading the manual

Model SEFSD-211 meets the requirements for fire

dampers, smoke dampers and combination fire

smoke dampers established by:

National Fire Protection Association

NFPA Standards 80, 90A, 92A, 92B 101 & 105

ICBO Uniform Building Codes
IBC International Building Codes
New York City

(MEA listing #260-91-M)

California State Fire Marshall

Listing #: 3225-0981:103 (fire)
Listing #: 3230-0981:104 (smoke)

Application

Model SEFSD-211 is a severe environment 316SS combination

fire smoke damper with 3V style blades. The SEFSD-211 has

been qualified to 2000 fpm (10.2 m/s) and 4 in. wg (1.0 kPa) for

operation and dynamic closure in emergency fire smoke situations.

Model SEFSD-211 may be installed vertically (with blades running

horizontal) or horizontally and is rated for airflow and leakage in

either direction.

Ratings

UL 555 Fire Resistance Rating

Fire Rating:

1

1

2

Hours

Dynamic Closure Rating:

Actual ratings are size dependant

Maximum Velocity:

2000 fpm (10.2 m/s)

Maximum Pressure:

4 in. wg (1.0 kPa)

UL 555S Leakage Rating

Leakage Class:

I

Operational Rating:

Actual ratings are actuator

dependant

Maximum Velocity:

2000 fpm (10.2 m/s)

Maximum Pressure:

4 in. wg (1.0 kPa)

Maximum Temperature:

350ºF (177°C) —Depending on

actuator

Standard Construction

Frame:

5 in. x 1 in.(127mm x 25mm) 16 ga.

(1.5mm) 316 stainless steel hat

channel with reinforced corners . A

low profile head and sill are used on

sizes less than 17 in. (432mm) high

to maximize free area and

performance.

Blades:

16 ga. (1.5mm) 316 stainless steel,

reinforced with 3 longitudinal

structurally designed vee’s.

Seals:

Extruded silicone rubber blade

seals. Flexible 316 stainless steel

jamb seals.

Linkage:

316 stainless steel, concealed in

jamb.

Axles:

1/2 in. (13mm) diameter 316

stainless steel.

Bearings:

316 stainless steel sleeve type.

Closure Device:

165º F (74ºC) RRL

Size Limitations

Minimum Size:

8 in. W x 6 in. H

(203mm W x 152mm H)

Maximum

Size:

Single Section:

24 in. W x 30 in. H

(Horizontal or Vertical Mount)

(610mm W x 762mm H) or

22 in. W x 36 in. H (Vertical Mount)

(559mm x 914mm)

Multiple Section:

48 in. W x 30 in. H

(Horizontal or Vertical Mount)

(1219mm W x 762mm H) or

88 in. W x 72 in. H (Vertical Mount)

2235mm x 1829mm)

Optional Features

• OCI (Open closed indication switches) - not 316SS
• 165º F (74°C), 212ºF (100°C), and 350ºF (177°C) RRL available -

thermal device not 316SS.

• TOR (remote override of 165ºF [74°C] closure allows damper to

perform smoke management functions during a fire emergency)
-not 316SS.

• Electric or pneumatic actuators to accomplish smoke management

and system functions.

Model SEFSD-211

Combination

FIRE SMOKE DAMPERS

316 Stainless Steel 3V Blades

UL 555S Leakage Class I

UL 555 1

1

2

Hour Fire Resistance Rating

* W & H dimensions furnished approximately 1/4 in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.

H*

W*

LH

RH

“UL CLASSIFIED (see complete marking on

product)”

“UL CLASSIFIED to Canadian safety standards

(see complete marking on product)”

Standard 555 &555S (Listing #R13317)

Greenheck Fan Corporation certifies that the model

SEFSD-211 shown herein is licensed to bear the

AMCA Seal. The ratings shown are based on tests

and procedures performed in accordance with

AMCA Publication 511 and comply with the require-

ments of the AMCA Certified Ratings Programs. The

AMCA Certified Ratings Seal applies to air perfor-

mance ratings only.

R

Installation instructions available at www.greenheck.com

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Pressure Drop Data; AMCA Test Figures

Pressure Drop Data SEFSD-211 This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft 3 (1.201 kg/m 3 ). Actual pressure drop found in any HVAC system is a co...

Page 3 - AMCA 5.2 Pressure Drop; Pressure Drop

AMCA 5.2 Pressure Drop SEFSD-211 5D 6D 5D D = 4 (W) (H ) 3.14 Figure 5.3 Figure 5.2 Figure 5. 5 R Greenheck Fan Corporation certifies that the model SEFSD-211 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publica...

Page 4 - AMCA 5.3 Pressure Drop

AMCA 5.3 Pressure Drop SEFSD-211 5D 6D 5D D = 4 (W) (H ) 3.14 Figure 5.3 Figure 5.2 Figure 5. 5 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.02 500 0.01 500 0.01 500 0.01 1000 0.09 1000 0...

Other Greenheck Models

All Greenheck Other