Greenheck OFSD-212 - Manual

Greenheck OFSD-212

Greenheck OFSD-212 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
Page: / 6

Table of Contents:

  • Page 2 – Pressure drop data; AMCA Test Figures
  • Page 3 – AMCA 5.2 Pressure drop
  • Page 4 – AMCA 5.3 Pressure drop
  • Page 5 – AMCA 5.5 Pressure drop
  • Page 6 – Actuator Space Envelopes; Application data; Sleeve Information; Specifications
Loading the manual

APPLICATION

Model OFSD-212 is an ‘out of the wall’ high performance combina-

tion fire smoke damper with 3V style blades. OFSD-212 is approved

for use in walls, partitions, and floors with fire resistance ratings less

than 3 hours. Removal of wall grille allows access to actuator and

other components. This model's operational ratings of 2000 fpm (10.2

m/s) and pressures to 4 in. wg (1 kPa). OFSD-212 shall be installed

vertically (with blades running horizontal) or horizontally and is rated

for airflow and leakage in either direction.

Ratings

UL555 Fire Resistance Rating:

Fire Rating:

1

1

2

hours in walls

Dynamic Closure Rating: Actual ratings are size dependent

Max. Velocity:

2000 fpm (10.2 m/s)

Max. Pressure:

4 in. wg (1 kPa) - differential

pressure

UL555S Leakage Rating:

Leakage Class:

II

Operational Rating:

Actual ratings are size dependent

Max. Velocity:

2000 fpm (10.2m/s)

Max. Pressure:

4 in. wg (1 kPa)

Max. Temperature:

3

50ºF (177ºC)- depending upon the

actuator

STANdARd CONSTRuCTION

Frame:

5 in. x 1 in. (127mm x 25mm)

galvanized steel hat channel with

reinforced corners. A low profile head

and sill are used on sizes less than

17 in. (432mm) high.

Blades:

16 ga. (1.5mm) galvanized steel,

reinforced with 3 longitudinal

structurally designed vee's.

Seals:

Extruded silicone rubber blade seals.

Flexible stainless steel jamb seals

Linkage:

Concealed in jamb

Closure device:

UL listed 165°F (74ºC) RRL

Axles:

1

2

in. (13mm) dia. plated steel

Bearings:

Bronze sleeve type

Sleeve:

Galvanized; wrapped with thermal

blanket

Size Limitations:

Minimum Size:

12 in. W x 12 in. H

(305mm x 305mm)

Maximum Size:

Single section: 36 in. W x 36 in. H

(914mm x 914mm)

Optional Features:

• POC retaining Angles

• RRL/OCI (open closed indication switches)

• 165ºF (74ºC), 212ºF (100ºC), 250ºF (121ºC), 350ºF (177ºC) RRL’s

available

• TOR (remote override allows damper to perform smoke

management functions during fire emergency.)

• Electric actuators

• Momentary switch

• Security bars

• Sealed transition and sleeves

Model OFSd-212

Out Of Wall Combination

FIRE SMOKE dAMPERS

Steel 3V Blades

UL 555S Leakage Class II

UL 555 1

1

2

Hour Fire Resistance Rating

Horizontal or Vertical Mount

“uL CLASSIFIEd (see complete marking on

product)”

“uL CLASSIFIEd to Canadian safety standards

(see complete marking on product)”

Standard 555 & 555S (Listing #R13317)

* W & H dimensions furnished approximately ¼ in. (6mm) undersize.

(Add blanket thickness (1⁄8 in.[3mm]) and sleeve thickness for overall

sleeved damper dimension)

Oversize wall opening as follows:

Nominal damper size plus 3⁄8 in.(9.5mm) (see Page 6)

Model OFSD-212 meets the requirements for fire

dampers, smoke dampers and combination fire

smoke dampers established by:

National Fire Protection Association

NFPA Standards 80, 90A, 92A, 92B, 101 & 105

IBC International Building Codes
ICBO uniform Building Codes
CSFM California State Fire Marshal

Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)

New York City

(MEA listing #260-91-M)

R

Greenheck Fan Corporation certifies that the

model OFSD-212 shown herein is licensed to bear

the AMCA Seal. The ratings shown are based on

tests and procedures performed in accordance

with AMCA Publication 511 and comply with the

requirements of the AMCA Certified Ratings Pro-

grams. The AMCA Certified Ratings Seal applies to

air performance ratings only.

Installation instructions available at www.greenheck.com

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Pressure drop data; AMCA Test Figures

Pressure drop data OFSd-212 This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft 3 (1.201 kg/m 3 ). Actual pressure drop found in any HVAC system is a com...

Page 3 - AMCA 5.2 Pressure drop

R Greenheck Fan Corporation certifies that the model OFSD-212 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams. The AMCA Cert...

Page 4 - AMCA 5.3 Pressure drop

R Greenheck Fan Corporation certifies that the model OFSD-212 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro- grams. The AMCA Cert...

Other Greenheck Models