APPLICATION

Model FSD-311V is a vertical blade class I leakage rated combi-

nation fire smoke damper. High strength airfoil blades ensure the

lowest resistance to airflow in HVAC systems with velocities to 4000

fpm (20.3m/s) and 4 in. wg (1.0 kPa).

RATINgs

UL 555 Fire Resistance Rating:

Fire Rating:

1½ hours

Dynamic Closure Rating:

Actual ratings are size dependent

Max. Velocity:

up to 4000 fpm (20.3 m/s)

Max. Pressure:

4 in. wg (1 kPa)

UL555S Leakage Rating:

Leakage Class:

I

Operational Rating:

Actual ratings are size dependent

Max. Velocity:

up to 4000 fpm (20.3m/s)

Max. Pressure:

4 in. wg (1 kPa)

Maximum Temperature:

350°F (177°C)- depending upon

the actuator

sTANdARd CONsTRuCTION

Frame:

5 in. x 1 in. (127mm x 25mm)

galvanized steel hat channel with

reinforced corners. A low profile

head and sill are used on sizes less

than 17 in. (432mm) high to

maximize free area and

performance.

Blades:

Double skin airfoil shape of

galvanized steel with full length

structural reinforcement. 14 ga.

(2 mm) equivalent thickness.

seals:

Extruded silicone rubber blade

seals. Flexible stainless steel jamb

seals.

Closure device:

RRL 165°F (74°C)

Linkage:

Concealed in jamb.

Axles:

1

/

2

in. (13mm) dia. plated steel.

Bearings:

304 stainless steel

sIze LImITATIONs:

minimum size:

6 in. W x 8 in. H

(152mm W x 203mm H)

maximum size-

Single Section:

50 in. W x 32 in. H

(1270mm W x 813mm H)

Multiple Section:

100 in. W x 32 in. H

(2540mm W x 813mm H)

OPTIONAL FeATuRes

• OCI (Open closed indication switches)

• Electric or pneumatic actuators to accomplish smoke

management and system functions.

• Transitions (R, C, O)

• POC retaining angles

• Momentary Switch

• Sealed transitions and sleeves

• RRL/OCI (Open closed indication switches)

• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL's

available

• TOR (remote override closure allows damper to perform smoke

management functions during a fire emergency.)

• PRV (pneumatic relief valve)

• Security Bars

• Sealed transitions and sleeves

model Fsd-311V

Combination

FIRe smOKe dAmPeRs

Steel Airfoil Blades

UL 555S Leakage Class I

UL555 1 1/2 Hour Fire Resistance Rating

*W&H dimensions furnished approximately

1

/

4

in. (6mm) undersize.

W*

H*

Model FSD-311V meets the requirements for fire

dampers, smoke dampers and combination fire

smoke dampers established by:

National Fire Protection Association

NFPA Standards 80, 90A, 92A, 92B, 101 & 105

IBC International Building Codes

ICBO uniform Building Codes

CsFm California state Fire marshal

Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)

New York City

(MEA listing #260-91-M)

“uL CLAssIFIed (see complete marking on

product)”

“uL CLAssIFIed to Canadian safety standards

(see complete marking on product)”

Standard 555 & 555S (Listing #R13317)

Installation instructions available at www.greenheck.com

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Pressure drop data; AmCA Test Figures

Pressure drop data Fsd-311V This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft 3 (1.2 kg/m 3 ). Actual pressure drop found in any HVAC system is a combi...

Page 3 - AmCA 5.2 Pressure drop

12x12 24x24 AmCA 5.2 Pressure drop Fsd-311V 5D 6D 5D D 4 (W) (H) 3.14 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.03 500 0.01 500 0.01 500 0.01 500 ...

Page 4 - AmCA 5.3 Pressure drop

12x12 24x24 * Sizes are in inches. AmCA 5.3 Pressure drop Fsd-311V 5D 6D 5D D 4 (W) (H) 3.14 Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) Velocity (fpm) Pressure Drop (in. wg) 500 0.01 500 0.01...