Model FDR-510 meets the requirements for fire dampers

established by:

National Fire Protection Association

(NFPA Standards 80, 90A & 101)

Underwriters Laboratories Standard 555

(Listing #R-13317)

IBC International Building Codes

Model FDR-510

Static Rated

Round Fire Dampers

1

1

/

2

Hour Fire Resistance Rating

Copyright ©2008 Greenheck Fan Corporation

FDR-510 Rev. 6

Aug 2008

*

These dimensions are furnished approximately 1/8 in. (3mm)

smaller than nominal.

Features:

• Stainless steel closure springs
• Fusible links - 165ºF (74ºC) standard; 212ºF (100ºC) and 286ºF

(141ºC) available

• Can be mounted horizontally or vertically
• Only one retainer plate required (one retainer plate supplied

with damper)

• Additional retainer plate available
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve

Application and Design

Model FDR-510 is a round fire damper for use in walls or
partitions with less than 3 hour fire resistance rating. It is

qualified to be mounted vertically and horizontally. This

model carries a 1 1/2 hour UL fire damper label. UL555
classifies static rated fire dampers for use in HVAC systems
that are automatically shut down in the event of fire.

Ratings

Temperature:

165º F (74ºC)

Standard Construction

Frame/Sleeve: 20 ga. (1mm) galvanized steel

Blade: 20 ga. (1mm) galvanized steel

Closure Device: 165ºF (82ºC) Fusible Link

Axle:

1

/

2

in. (6mm) dia. plated steel.

Bearing: Stainless Steel sleeve type

Size Limitations

Minimum size: 4 in. (102mm) diameter

Maximum size: 24 in. (610mm) diameter

OPENING + 2.00 MIN.

FASTENERS

WALL/FLOOR

1.00 TYP.

= Nominal size + 7/8 Min.

OPENING

CLAMPING SCREW

RETAINING

PLATE ASSEMBLY

NUT

SCREW

CLAMPING

WALL THICKNESS

SLEEVE LENGTH

Up to 6.5

13.625

Up to 8.5

15.625

Up to 10.5

17.625

Over 10.5

Consult Greenheck

2 in.

TW

AIRFLOW

SLEEVE LENGTH

2 in.

6 in. max.

6 in. max.

(OPTIONAL)

RETAINER PLATE

DUCT CONNECTION

AREA

CLEARANCE FOR

EXPANSION

RETAINER PLATE

BLADE LATCH

ACCESS DOOR TO BE ON

SAME SIDE AS BLADE LATCH

DUCT CONNECTION

AREA

DO NOT PLACE RETAINER

PLATE IN THIS GROOVE