24 Vdc / 24 Vac / 120 Vac

Application & Design

An electro-pneumatic (EP) switch, also known as a three way solenoid valve, is used to electrically open and close a pneumatic
actuated damper. It is wired in series with a normally closed thermostat when used with a fire smoke damper (FSD) to initiate
closure at elevated temperatures. The EP switch can also be used on a smoke damper (SMD) to initiate closure when required in
a smoke control system.

Assembly

9

7

3

2

1

6

4

5

8

input signal:

24 Vdc

(specify) 24 Vac

120 Vac

item Qty. part # Description

Kit #

1

1

-

Valve

1

8

" NPT

2

1

-

Retaining Clip

3

1

452460 S/V 120 Vac

812441

-

1

380913 S/V 24 Vac

812442

-

1

381042 S/V 24 Vdc

812443

4

1

651371 Mounting Bracket

5

1

380850 2 x 4 x 1.875 Ext. Box

6

2

415555 #10 x 0.50 TEK Screw

7

1

380257 2 x 4 Blank Cover

8

1

415539 #10-32 HH Grounding

Screw (green)

9

1

454850 Label

Kit #s include appropriate voltage solenoid valve shown
under Item 3 and all other Item #s above.

Port 3
Exhaust

Port 2
Supply

Port 1
To Actuator

ASCO Solenoi d
Va lve Assembl y

Red

Red

TOR/RRL
Wiring
Har dware

Solenoid Va lve With TOR

Solenoid Valve

TOR

Brow n
Orange
Black
Blue
Red

Purpl e
Yello w

Red

Red

Orange

Black

Solenoid Va lve With RRL

Solenoid Valve

RRL

Red

Red

typical setup