Greenheck DFD Series - Manual

Greenheck DFD Series

Greenheck DFD Series – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
Page: / 1
Loading the manual

These instructions apply to 1

1⁄2

hour rated combination

fire smoke dampers and dynamic rated multi-blade
fire dampers mounted in masonry, block, or metal or
wood stud walls.

Note: This installation is intended

for underfloor applications where the damper/duct is
directly above (4 in. [101mm] or less) the rated concrete
floor (see Figure 2). No duct impact test was conducted.

Specific requirements in these instructions are mandatory.
These instructions meet the requirements of UL 555.
Installation shall comply with the requirements of NFPA
90A (Standard for the Installation of Air Conditioning and
Ventilating Systems) and UL Classification R13317.
Fire and Combination Fire/Smoke dampers up to a
maximum size of 72 in. W x 96 in. H (1828mm x 2438mm)
may be installed as instructed below.

1. Expansion Clearance - Fire damper and sleeve

assemblies expand during periods of intense heat.
Therefore, it is essential that openings in walls or
floors be larger than the fire or fire/smoke damper and
sleeve assembly to allow for this expansion. Minimum
clearances required between the outside of fire or fire/
smoke damper sleeve assemblies and wall openings
are:

• Galvanized steel fire dampers and sleeves:

1

8

in.

(3mm) per foot of damper width and height with a
minimum clearance of

1

4

in. (6mm), maximum of 1

1

2

in. (38mm).

Recommended

clearances, for width

and/or height dimensions of:

1) 48 in. (1219mm) or less:

1

2

in. (13mm)

clearance

2) More than 48 in. (1219mm) and 96 in.

(2438mm) or less: 1 in. (25mm) clearance

3) More than 96 in.(2438mm): 1

1

2

in. (38mm)

clearance

• Stainless steel fire/smoke dampers and stainless

steel or galvanized sleeves:

3

16

in. (4.7mm) per

foot of damper width and height with a minimum
clearance of 1/4 in. (6mm) , maximum of 2 in.
(51mm)

®

Copyright © 2008 Greenheck Fan Corporation

Firestop Material IOM Rev 2 Mar 2008

Part number 469419

Firestop Material

INSTALLATION INSTRUCTION SUPPLEMENT

Refer to:
‘Installation Instructions for FSD-XXX, DFD-XXX,
SSFSD-XXX & CFSD-XXX Series Fire & Combination Fire
Smoke Dampers’ (Part #461336)

DFD Series

1

1

/

2

Hour Multi-Blade Fire Dampers

and

FSD Series

1

1

/

2

Hour Combination Fire Smoke

Dampers-Vertical Mount

Recommended

clearances, for width and/or height dimen-

sions of:

1) 48 in. (1219mm) or less:

3

4

in. (19mm) clearance

2. Packing (optional) - Polyethylene backer rod, recessed from

surfaces of wall to accommodate the required thickness of
fill material.

3. Fill Material - Hilti Corporation - FS-One fire stop caulk

applied to a minimum 5/8 in. (16mm) thickness within the
annular space and flush with both surfaces of the wall
with a 1 in. (25mm) overlap onto the gypsum board. If the
damper/sleeve assembly comes into contact with the wall,
a minimum of 3/8 in. (10mm) diameter bead shall be applied
to the interface between the sleeve and contact surface.
Firestop should be installed according to manufacturers
instructions and firestop instructions given in the 2007 UL
Fire Resistance Directory Volume 2B, page 4471.

4. Retaining Clip - Retaining clip 1 in. x 2 in. x 2 in. x 16 gauge

(25mm x 51mm x 51mm x 1.5mm) is attached to one side of
the wall with 1 1/2 in. (38mm) long #8 sheet metal screws or
masonry screws in the masonry wall. The 1 in. (25mm) leg of
the clip shall be attached to the damper sleeve with 1/2 in.
(13mm) long #10 sheet metal screws. The retaining clips are
required to be spaced a maximum of 6 in. (152mm) from the
top of the sleeve and spaced a maximum of 12 in. (305mm)
on center on the sides of the unit only.

Floor tiles

Rated wall

Fill material

Fill material

Ductwork

max. 4 in. (102mm)

Rated masonry floor

Retaining
clip

(one side only on bottom)

Figure 1

Figure 2

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Other Greenheck Models

All Greenheck Other