Greenheck DFD-M210 - Manual

Greenheck DFD-M210

Greenheck DFD-M210 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
Page: / 6

Table of Contents:

  • Page 2 – Pressure Drop Data; AMCA Test Figures
  • Page 3 – AMCA 5.2 Pressure Drop
  • Page 4 – AMCA 5.3 Pressure Drop
  • Page 5 – AMCA 5.5 Pressure Drop; VELOCITY VS. PRESSURE DROP
  • Page 6 – Damper Sizing Information; Specifications; GREENHECK
Loading the manual

Application

Model DFD-M210 is a multi-blade fire damper with 3V style blades.

The DFD-M210 has been qualified to 10.2 m/s (2000 fpm) and 1.0kPa

(4 in. wg.) for operation and dynamic closure in emergency fire

situations. Model DFD-M210 may be installed vertically (with blades

running horizontal) or horizontally and is rated for airflow in either

direction.

Model DFD-M210 has also been tested in accordance with BS476 to

4 hours at Warrrington Fire, UK, and is approved for fire partitions of 4

hours or less where British Standards are required.

Ratings

UL 555 Fire Resistance Rating

Fire Rating:

1

1

2

Hours

Dynamic Closure Rating:

Actual limits are size dependent

Maximum Velocity:

10.2 m/s (2000 fpm)

Maximum Pressure:

1 kPa (4 in. wg)

BS476 Fire Resistance Rating

Fire Rating:

4 hours

Standard Construction

Frame:

127mm x 25 mm (5 in. x 1 in.) 1.5mm

(16 gauge) galvanized steel hat

channel with reinforced corners. A

low profile head and sill are used on

sizes less than 432mm (17 in.) high to

maximize free area and performance.

Blades:

1.5mm (16 gauge) galvanized steel,

reinforced with 3 longitudinal

structurally designed vee’s.

Seals:

Flexible stainless steel jamb seals.

Linkage:

Concealed in jamb.

Fusible Link:

UL listed 74ºC (165°F)

Axles:

13mm (

1

2

in.) dia. plated steel.

Bearings:

Bronze sleeve type.

Actuator:

Manual quadrant.

Size Limitations

Minimum Size:

203mm W x 152mm H

(8 in. W x 6 in. H)

Maximum Size:

Single Section:

914mm W x 914mm H

(36 in. W x 36 in. H) or

813mm W x 1270mm H

(32 in. W x 50 in. H)

Multi Section:

1626mm W x 1270mm H

(64 in. W x 50 in. H)

Optional Features

•100ºC (212° F), 141ºC (286°F), and 177ºC (350°F) fusible links (UL only)
• 69°C (155°F) fusible links (BS476)
• Factory mounted sleeves
• Retaining angles
• Sleeve with integral flange on both sides

Model DFD-M210

Multi-Blade

FIRE DAMPER

Steel 3V Blades

UL 555 1

1

/

2

Hour Fire Resistance Rating

4 hour Fire Resistance Rating (BS476)

* W & H dimensions furnished approximately 6mm (

1

/

4

in.) undersize.

(Add sleeve thickness for overall sleeved damper dimension)

H

W

LH

RH

“UL CLASSIFIED (see complete marking on

product)”

“UL CLASSIFIED to Canadian safety standards

(see complete marking on product)”

Standard 555 (Listing #R13317)

Model DFD-M210 is intended for installation in

accordance with fire damper requirements

established by:

National Fire Protection Association

NFPA Standards 80, 90A & 101

ICBO Uniform Building Codes
IBC International Building Codes
SBCCI Standard Building Codes

British Standard BS476

Tested to 4 hours at Warrington Fire, UK

R

Greenheck Kunshan Co. Ltd. and Greenheck Fan
Corporation certifies that the model DFD-M210
shown herein is licensed to bear the AMCA
Seal. The ratings shown are based on tests and
procedures performed in accordance with AMCA
Publication 511 and comply with the requirements
of the AMCA Certified Ratings Programs. The
AMCA Certified Ratings Seal applies to air
performance ratings only.

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 2 - Pressure Drop Data; AMCA Test Figures

Pressure Drop Data DFD-M210 This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of 1.201 kg/m3. Actual pressure drop found in any HVAC system is a combination of many ...

Page 3 - AMCA 5.2 Pressure Drop

AMCA 5.2 Pressure Drop DFD-M210 5D 6D 5D D = 4 (W) (H ) 3.14 Figure 5.3 Figure 5.2 Figure 5. 5 R Greenheck Kunshan Co. Ltd. and Greenheck Fan Corporation certifies that the model DFD-M210 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in...

Page 4 - AMCA 5.3 Pressure Drop

R Greenheck Kunshan Co. Ltd. and Greenheck Fan Corporation certifies that the model DFD-M210 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ra...

Other Greenheck Models