GEH-5734B

INSTRUCTIONS

H4 Hazardous Location Luminaire

READ THOROUGHLY BEFORE INSTALLING

WARNING: DANGEROUS VOLTAGES EXIST
WITHIN THESE UNITS AND ALL PRECAUTIONS
USUALLY OBSERVED IN HANDLING HIGH
VOLTAGE EQUIPMENT SHOULD BE OBSERVED.
MAKE CERTAIN POWER IS OFF BEFORE
STARTING INSTALLATION PROCEDURE OR
BEFORE SERVICING.

Caution: When installing the luminaire in hazardous

locations, check the operating temperature limits prior to

installation to be sure it conforms to the environmental

temperature restrictions and NEC classifications.

THIS FIXTURE SHOULD BE INSTALLED BY QUALIFIED

TECHNICIANS IN STRICT ACCORDANCE WITH THE NA-

TIONAL ELECTRICAL CODE AND ANY LOCAL REQUIRE-

MENTS.

INSTALLATION

Caution: To avoid electrical shock hazard.

1. Before installation or service of this fixture,

make sure that the circuit is deactivated.

2. This unit is furnished completely assembled.

Before installing, check the fixture label to
insure correct voltage and frequency.

3. Typical fixture installations are shown on

back of page.

OPERATIONAL DATA

Operate this fixture at its rated voltage. See fixture label for

data. To receive full benefit of rated lamp output and to

prolong ballast life, it is essential that voltage supply to the

fixture be maintained within the following limits:

NOMINAL

APPLIED VOLTAGE RANGE

VOLTAGE

MINIMUM

MAXIMUM

120

110

125

277

255

290

MAINTENANCE DATA

1. Although no routine maintenance is required to keep this

fixture functional, it should be checked perodically to ensure

that it is working properly and to look for any external

damage.

2. For optimum performance, keep light transimissions parts of

the fixture clean. Any commercial glass cleaner can be used

to clean the glass tubes.

3. Relamping Procedure:

A. Biaxial Lamp — Disconnect supply circuit. Remove the

lamp access cover (opposite conduit entrance side).

Using the relamp support, remove the lamp from the

fixture. Remove the lamp support and install on new

lamp. Install lamp and lamp access cover.

B. T8/T5 Lamp — Disconnect supply circuit. Remove

lamp access cover (either end of lamp). Loosen

lampholder bracket screws. Twist and remove

lampholder bracket. Remove lamp and install new lamp,

seating lamp in opposite lampholder. Replace

lampholder into position on the lamp. Twist slightly to

place lampholder bracket under screw heads, and tighten

screws. Reattach lamp access cover.

4. In the event of glass tube breakage, it will be necessary to

replace the damaged unit with a factory sealed housing

assembly, in order to maintain the integrity of the fixture.

See the fixture parts list for ordering.

5. When replacing Ballast, it should be of Class-P, thermally-

protected type.

These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation or
maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred
to GE Lighting Solutions.

g

GE
Lighting Solutions

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Was this manual helpful?

Helpful for 3 of 3 readers

About this manual

Brand
GE
Model
H4
Document type
Installation Manual
Language(s)
English
Pages
2
File size
82.8 KB
Format
PDF

Ask a question

Up to 3 photos. Max 5 MB each. Formats: JPG, JPEG, PNG, WebP.