Emerson DE - Manual

Emerson DE

Emerson DE – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.

1 Page 1
2 Page 2
3 Page 3
4 Page 4
5 Page 5
6 Page 6
7 Page 7
8 Page 8
9 Page 9
10 Page 10
11 Page 11
12 Page 12
13 Page 13
14 Page 14
15 Page 15
16 Page 16
17 Page 17
18 Page 18
19 Page 19
20 Page 20
21 Page 21
22 Page 22
23 Page 23
24 Page 24
25 Page 25
26 Page 26
27 Page 27
28 Page 28
29 Page 29
30 Page 30
31 Page 31
32 Page 32
33 Page 33
34 Page 34
35 Page 35
36 Page 36
37 Page 37
38 Page 38
39 Page 39
40 Page 40
41 Page 41
42 Page 42
43 Page 43
44 Page 44
45 Page 45
46 Page 46
47 Page 47
48 Page 48
49 Page 49
50 Page 50
51 Page 51
52 Page 52
53 Page 53
54 Page 54
55 Page 55
56 Page 56
57 Page 57
58 Page 58
59 Page 59
60 Page 60
61 Page 61
62 Page 62
63 Page 63
64 Page 64
65 Page 65
66 Page 66
67 Page 67
68 Page 68
69 Page 69
70 Page 70
71 Page 71
72 Page 72
73 Page 73
74 Page 74
75 Page 75
76 Page 76
77 Page 77
78 Page 78
79 Page 79
80 Page 80
Page: / 80

Table of Contents:

  • Page 3 – TABLE OF CONTENTS; GLYCOOL
  • Page 4 – ii
  • Page 5 – iii
  • Page 6 – iv
  • Page 9 – Introduction; NTRODUCTION; System Description
  • Page 11 – Initial Start-Up Procedure; NITIAL; breakers, open them instead of removing fuses.; Microprocessor Controls Setup; or to; Advanced Microprocessor with Graphics Control; Additional Considerations for Upflow Units; Consult Liebert Applications Engineering for more information.; WARNING
  • Page 12 – Advanced Microprocessor Controls Setup; DVANCED; section. For more control details refer to; cessor Controls; , and for more alarm information refer to; tions; Basics; . These keys are used to move through the menus as prompted on; Figure 2; displayed and may require a password, if enabled.; Figure 1; Display the Main Menu—AM Control
  • Page 14 – testing. Check the unit delivery date to see if this is the case.; NOTE
  • Page 15 – Analog; Setpoint
  • Page 16 – Setup Operation; IR Fill Rate; This feature will flush the respective coil for three; Table 2; Function; Cold Start Time Delay*
  • Page 17 – Select Options; password feature if set to OFF.; Table 3
  • Page 18 – Dehumidification with Normal or Delayed Reheat:; Select Control Type; INTELLIGENT; - Response by Control Type—Advanced Microprocessor Controls; Setup Alarms; CAUTION
  • Page 19 – you can create your own message.; Standard Alarm; Alarm
  • Page 20 – Standard Alarm Messages; For more information concerning alarms, see; Humidity Control Method; For installation of analog sensors, see; sor Controls; itor the sensor as follows:
  • Page 21 – Set Status Display; Device
  • Page 22 – Test Outputs; protected by a battery backup.
  • Page 23 – displayed, pressing the MENU/ESC key returns to the Status Display.; Load Control Features; operating conditions have been met.; Control Circuit Board; configuration. The jumpers should be placed as follows:; The LED backlighting on the text (4 x 20) display is always lit.
  • Page 24 – the LCD display and are also described in more detail in; Communications; monitoring system you are using.; Liebert Site Product Device; toring system; Table 6; LED
  • Page 26 – Advanced Microprocessor with Graphics Control Setup; described in this section. For more details on the control refer to; Advanced Microprocessor Controls; for details on the alarms refer to; and Solutions; Figure 3; . These keys are used to move through the menus as prompted on the LCD; Figure 4
  • Page 28 – Display the Main Menu—AG Control; shrinking water drop is shown next to the word “Dehumidification”.; See
  • Page 29 – Table 7
  • Page 30 – Selecting SETUP CUSTOM ALARMS will step to the following menu:; Standard Custom Alarm Mes-; Standard Custom Alarm Messages; Installation—LT750 DIP Switch Settings
  • Page 31 – control is calling for the system to do.
  • Page 32 – Cold Start Delay; units. Typically, only air cooled units need a “Winter; Auto Restart Delay; for which they can be programmed.; Table 9
  • Page 33 – will; PROPORTIONAL; Response by Control Type—Advanced Microprocessor Controls; Option
  • Page 36 – Dehumidification with Normal or Delayed Reheat; The date and time are backed up by a battery.; Number
  • Page 37 – Slope
  • Page 38 – or a custom text alarm. See; Load Control Features; Sequential Load Activation Control
  • Page 39 – Control Circuit Board; for other configurations
  • Page 40 – Proportional, Derivative and Integral Gains; Control output LEDs
  • Page 41 – rithm/control type selected in setting up the controls.; Temperature Control; Proportional Control; together three individual terms -; trol Features; Intelligent Control; would take if manually controlling the system (see; Intelligent Control on page 35
  • Page 42 – When GLYCOOL; Dual Cooling Source; water temperature is 3; Chilled Water Cooling
  • Page 43 – Humidity Control; Normal or Delayed Reheat (for Two-Stage Dehumidification Only); Switches
  • Page 44 – Dual Cooling Source Dehumidification; dehumidification system.; Chilled Water Dehumidification; ment for dehumidification from 0 to 100%.; System Activation; inputs are the usual setpoint and sensitivity adjustments.; PID Control; sional retuning is required for optimum performance.
  • Page 45 – Suggested System Tuning Procedure; same amplitude from one peak to the next).; time between peaks x peak amplitude x 4
  • Page 46 – that are susceptible to mechanical wear or cycling.
  • Page 47 – Short Cycle alarm could occur.
  • Page 48 – Analog Sensors; the appropriate jumpers on the control circuit board. See; and; Figure 6; to the terminals as follows:; Figure 5; Terminal; Additional connections available after unit delivery; No jumper on; Analog input jumper location; ENLARGED AREA
  • Page 49 – Physical Connections; for more information.
  • Page 50 – Calibration; position
  • Page 52 – Alarm Descriptions and Solutions; LARM; Setup Alarms on page 10; Standard Alarms
  • Page 53 – informed of the alarm function and corrective action required.; Infrared Humidifiers
  • Page 54 – nostics to make sure the humidifier system is working properly.
  • Page 55 – Optional/Custom Alarms; or fire, and follow appropriate emergency procedures.
  • Page 56 – Component Operation and Maintenance, Checks and Adjustments; System Testing; done by temporarily changing the setpoints.; Cooling; come on. Disregard it. Return setpoint to the desired temperature.; Heating; return the setpoint to the desired temperature.; Humidification; On Chilled Water, GLYCOOL
  • Page 57 – between terminals 1 and 2 at plug P39.
  • Page 58 – Filters; Consult the factory for more information.; determined and corrected before returning the unit to operation.; mounts will produce vibration that may damage the unit.
  • Page 59 – TURN OFF ALL POWER TO THE UNIT AT THE DISCONNECT.; programming of the variable speed drive parameters.; Refrigeration System; will absorb moisture.
  • Page 60 – sures are listed in the following table.; Operation; Suction pressures; System; Discharge pressures; System Design
  • Page 61 – expansion valve through the side outlet distributor (refer to; Figure 7; if a higher evaporator temperature is required.; Figure 7; for the new balance to take place.
  • Page 62 – inspect all refrigerant lines for signs of oil leaks.; Figure 8
  • Page 63 – Shell and Tube Condensers; to; Testing Function of Valve; ferent manufacturers.
  • Page 64 – Mechanical Failure; would cause a future failure.; long rubber gloves in handling contaminated parts.; under the terms of the warranty, and the WARRANTY WILL BE VOID.
  • Page 65 – Compressor Replacement Procedure; charging the system with recovered refrigerant.; Humidifier; for periodic checks and maintenance.; hotter than lukewarm.
  • Page 66 – Changing Humidifier Lamps; Figure 9; Autoflush Infrared Humidifier Cleaning System; Steps 3 and 4 repeat as long as humidification is required.; Humidifier lamps
  • Page 67 – units, and in the middle section of downflow units.; Figure 10 Steam generating humidifier; and goes to normal operation. No drain is permitted until then.; the canister must be replaced; immediately and replace the canister with the identical part.
  • Page 68 – Controls; Figure 11 Run/drain switch; Replacing the Canister
  • Page 69 – The canister is now ready to be removed.; Fault Descriptions
  • Page 70 – Circuit Board Adjustments; Capacity
  • Page 71 – Figure 12 Steam generating humidifier control board; Electric Reheat; DIP switch settings for steam generating humidifier; may be required to meet specific application requirements.
  • Page 72 – Troubleshooting; ROUBLESHOOTING; Use this section in troubleshooting your unit. Also refer to; . Suggestions are grouped by product function for convenience.; pressurized pipes and tubes.; Blower troubleshooting
  • Page 73 – Compressor and refrigeration system troubleshooting; Symptom
  • Page 75 – Dehumidification troubleshooting
  • Page 76 – Humidifier—steam generator troubleshooting
  • Page 77 – Humidifier—infrared troubleshooting
  • Page 78 – Maintenance Inspection Checklist—Monthly; AINTENANCE
  • Page 79 – Maintenance Inspection Checklist—Semiannual; NOTES
  • Page 80 – Precision Cooling
Loading the manual

Precision Cooling
For

Business-Critical Continuity™

Liebert Deluxe System/3

Operation and Maintenance Manual
50 and 60 Hz, 6-30 Ton DX Systems (DH/DE/VH/VE); 12-60 Ton CW Systems (FH/UH)

"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.

Summary

Page 3 - TABLE OF CONTENTS; GLYCOOL

i TABLE OF CONTENTS 1.0 I NTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.1 System Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1....

Page 4 - ii

ii 4.4 Main Menu (AG)—View/Set Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 4.4.1 Active Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 4.4.2 Alarm History Lo...

Page 5 - iii

iii 5.0 R ESPONSE BY C ONTROL T YPE —A DVANCED M ICROPROCESSOR C ONTROLS . . . . . . . . . . . 33 5.1 Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 5.1.1 Cooling/Heating Required, in Percent (%) . . . . . . . . ...

Other Emerson Models