Page 3 - Reference Manual; NOTICE
Reference Manual 00809-0100-4021, Rev DANovember 2004 Rosemount 3144P www.rosemount.com Rosemount 3144P Temperature Transmitter Rosemount 3144P Temperature Transmitter may be protected by one or more U.S. Patents Pending. Other foreign patents pending. NOTICE Read this manual before working with the...
Page 5 - Table of Contents
Reference Manual 00809-0100-4021, Rev DANovember 2004 Rosemount 3144P www.rosemount.com Table of Contents SECTION 1Introduction Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...
Page 9 - Section 1; OVERVIEW
Reference Manual 00809-0100-4021, Rev DANovember 2004 Rosemount 3144P www.rosemount.com Section 1 Introduction Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2Ret...
Page 10 - CONSIDERATIONS; Electrical
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 1-2 Appendix A: Specifications and Reference Data • Specifications • Dimensional drawings • Ordering Information Appendix B: Approvals • Product Certifications • Installation Drawings Safety Instrumented System (SIS) – HART only ...
Page 11 - Temperature Effects
Reference Manual 00809-0100-4021, Rev DANovember 2004 1-3 Rosemount 3144P Environmental Temperature Effects The transmitter will operate within specifications for ambient temperatures between –40 and 185 °F (–40 and 85 °C). Heat from the process is transferred from the thermowell to the transmitter ...
Page 12 - NOTE; Mounting; Terminal Side of Electronics Housing; Software Compatibility
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 1-4 NOTE Each transmitter is marked with a tag indicating the approvals. Install the transmitter in accordance with all applicable installation codes and approval and installation drawings (see Appendix B: Product Certifications)...
Page 15 - Section 2; SAFETY MESSAGES
Reference Manual 00809-0100-4021, Rev DANovember 2004 Rosemount 3144P www.rosemount.com Section 2 Installation Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-2Mounting ...
Page 18 - Write Protect Switch (HART and F; 3 for high alarm; MOUNTING
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-4 Table 2-1. Transmitter Switch Locations. Write Protect Switch (HART and F OUNDATION Fieldbus) The transmitter is equipped with a write-protect switch that can be positioned to prevent the accidental or deliberate change of co...
Page 20 - fitting threads with teflon
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-6 INSTALLATION Typical North American Installation 1. Attach the thermowell to the pipe or process container wall. Install and tighten thermowells and sensors. Apply process pressure to perform a leak test. 2. Attach necessary ...
Page 21 - Attach a connection head to the thermowell.
Reference Manual 00809-0100-4021, Rev DANovember 2004 2-7 Rosemount 3144P Typical European Installation 1. Mount the thermowell to the pipe or the process container wall. Install and tighten thermowells and sensors. Apply pressure and perform a leak check before starting the process. 2. Attach a con...
Page 23 - Off
Reference Manual 00809-0100-4021, Rev DANovember 2004 2-9 Rosemount 3144P LCD Display Transmitters ordered with the LCD display option (code M5) are shipped with the LCD display installed. After-market installation of the LCD display on a conventional 3144P transmitter requires a small instrument sc...
Page 24 - Field Wiring
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-10 Multichannel Installation (HART / 4–20 mA only) You can connect several transmitters to a single master power supply (see Figure 2-7). In this case, the system may be grounded only at the negative power supply terminal. In m...
Page 26 - Power/Current Loop Connections; ON
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-12 Power/Current Loop Connections Use copper wire of a sufficient size to ensure that the voltage across the transmitter power terminals does not go below 12.0 V dc. 1. Connect the current signal leads as shown in Figure 2-10. ...
Page 27 - Fieldbus; Fieldbus Field Wiring Diagram
Reference Manual 00809-0100-4021, Rev DANovember 2004 2-13 Rosemount 3144P F OUNDATION Fieldbus Figure 2-11. Transmitter Terminal Block Figure 2-12. F OUNDATION Fieldbus Field Wiring Diagram Sensor Terminals (1 – 5) Ground Power Terminals 3144P Single-Sensor Connections Diagram 3144P Dual-Sensor Con...
Page 28 - RTD or Ohm Inputs; POWER SUPPLY; HART
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-14 Sensor Connections Figure 2-9 on page 2-11 (HART) and Figure 2-12 on page 2-13 (F OUNDATION fieldbus) shows the correct sensor wiring connections to the transmitter sensor terminals. To ensure an adequate sensor connection, ...
Page 29 - fieldbus; fieldbus with standard fieldbus power supplies.; fieldbus are polarity; Grounding; Sensor Shielding
Reference Manual 00809-0100-4021, Rev DANovember 2004 2-15 Rosemount 3144P NOTE Do not allow the voltage to drop below 12.0 V dc at the transmitter terminals when changing transmitter configuration parameters, or permanent damage to the transmitter could result. Figure 2-13. Load Limits. F OUNDATION...
Page 30 - Shielding Recommendations
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 2-16 Shielding Recommendations The following are recommended practices are from API Standard 552 (Transmission Standard) section 20.7 and from field and laboratory testing. If more than one recommendation is given for a sensor ty...
Page 31 - Option 3
Reference Manual 00809-0100-4021, Rev DANovember 2004 2-17 Rosemount 3144P Option 3 1. Ground the sensor wiring shield at the sensor, if possible. 2. Ensure the sensor wiring and signal wiring shields are electrically isolated form the transmitter housing and other fixtures that may be grounded. 3. ...
Page 33 - Section 3
Reference Manual 00809-0100-4021, Rev DANovember 2004 Rosemount 3144P www.rosemount.com HART Section 3 HART Commissioning Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . p...
Page 34 - YES
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-2 HART 375 FIELD COMMUNICATOR The Menu Tree and Fast Key sequences use the following device revisions: • Standard 3144P: Device Revision Dev v3, DD v2 • 3144P SIS: Device Revision Dev v2, DD v1 The 375 Field Communicator exchan...
Page 35 - Menu Tree
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-3 Rosemount 3144P HART Menu Tree Figure 3-1 displays a complete 3144P menu tree for use with the 375 Field Communicator. Options listed in bold type indicate that a selection provides other options. For 3144P SIS Safety Certified transmitter, s...
Page 36 - Fast Key Sequences
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-4 HART Fast Key Sequences Fast key sequences are listed below for common 3144P transmitter functions. NOTE: The fast key sequences assume that “Device Revision Dev v3, DD v2 is being used. Table 3-1 provides alphabetical functi...
Page 37 - AMS; sent
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-5 Rosemount 3144P HART AMS One of the key benefits of intelligent devices is the ease of device configuration. When used with AMS, the 3144P is easy to configure and provides instant and accurate alerts and alarms. The main configuration screen...
Page 38 - CHECK OUTPUT; Process Variables; CONFIGURATION; Variable Mapping
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-6 HART CHECK OUTPUT Before performing other transmitter online operations, review the configuration of the 3144P digital output parameters to ensure that the transmitter is operating properly. Process Variables The 3144P proces...
Page 44 - OK; Sensor Configuration, 1 Change Type and Conn, 3 Sensor 1 Setup; SEND; Sensor 2 Setup
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-12 HART Apply changes made (see “Apply AMS Changes” on page 3-5). Hot Backup Configuration The Config Hot BU command configures the transmitter to automatically use Sensor 2 as the primary sensor if Sensor 1 fails. With Hot Bac...
Page 45 - Average
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-13 Rosemount 3144P HART 10. From the Home screen, select 1 Device Setup, 3 Configuration, 3 Dual Sensor Configuration, 4 Configure Hot Backup to prepare to configure the transmitter for Hot Backup. 11. Select yes to enable Hot Backup. 12. Selec...
Page 49 - ENTER
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-17 Rosemount 3144P HART Example: The high alarm value has been set to 20.8 mA. Therefore, the low saturation level, S, must be as follows: 20.5 ≤ S ≤ 20.7 mA. Preset alarms can either be 1 Rosemount or 2 NAMUR-compliant . Use the failure mode s...
Page 50 - DEVICE INFORMATION; Tag
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-18 HART 2. Choose from Floating Precision or One- , Two- , Three- , or Four-Digit Precision by pressing F4, ENTER . Press F2 to send the information to the transmitter. To change the meter bar graph, perform the following steps...
Page 51 - wizard
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-19 Rosemount 3144P HART Message The Message variable provides the most specific user-defined means for identifying individual transmitters in multi-transmitter environments. It allows for 32 characters of information and is stored with the othe...
Page 53 - OFF
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-21 Rosemount 3144P HART Transmitter Behavior with Intermittent Sensor Detect OFF When the Intermittent Sensor Detect feature is switched OFF , the transmitter tracks all process temperature changes, even if they are the consequence of an interm...
Page 55 - HOME; Enter
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-23 Rosemount 3144P HART Loop Test The Loop Test command verifies the output of the transmitter, the integrity of the loop, and the operations of any recorders or similar devices installed in the loop. To initiate a loop test, perform the follow...
Page 58 - to return the control loop to automatic control.
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-26 HART NOTE Take careful note of the process variable output order. You must configure the HART Tri-Loop to read the variables in the same order. 5. Select OK to return the control loop to automatic control. AMS Right click an...
Page 59 - DIFFERENTIAL TE
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-27 Rosemount 3144P HART 3. Select temperature units for Channel 1 that match the differential temperature units of the transmitter. 4. Specify a range for the TV such as –100 to 100 °C. If the range is large, then a sensor drift of a few degree...
Page 60 - CALIBRATION; Calibration of the 3144P may include the following procedures:
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-28 HART CALIBRATION Calibrating the transmitter increases the precision of your measurement system. The user may use one or more of a number of trim functions when calibrating. To understand the trim functions, it is necessary ...
Page 61 - Sensor Input Trim
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-29 Rosemount 3144P HART Figure 3-6. Trim . Sensor Input Trim The Sensor Trim command allows the user to digitally alter the transmitter’s interpretation of the input signal as shown in Figure 3-6 on page 3-29. The sensor trim command trims, in ...
Page 62 - ENTER SNSR 1 TRIM
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-30 HART a. Select “No” if a sensor is connected to the transmitter b. Select “Yes” if using a calibration device. By selecting yes, the transmitter will be put into active calibration mode (see “Active Calibrator and EMF Compen...
Page 63 - Lower Only, 2 Upper Only; SELECT
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-31 Rosemount 3144P HART a. Select “No” if a sensor is connected to the transmitter b. Select “Yes” if using a calibration device. By selecting yes, the transmitter will be put into active calibration mode (see “Active Calibrator and EMF Compens...
Page 65 - Output Trim
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-33 Rosemount 3144P HART To disable the transmitter-sensor matching feature from the HOME screen select 1 Device Setup , 3 Configuration , 2 Sensor Confi g, 1 Change Type/Conn . Choose the appropriate sensor type from the ENTER SENSOR TYPE promp...
Page 66 - Scaled Output Trim
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-34 Rosemount 3144P HART 1. From the HOME screen, select 1 Device setup , 2 Diag/Service , 2 Calibration , 2 D/A trim . Set the control loop to manual and select OK . 2. Connect an accurate reference meter to the transmitter at the CONNECT REFER...
Page 67 - TROUBLESHOOTING
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-35 Rosemount 3144P HART TROUBLESHOOTING HART / 4–20 mA If a malfunction is suspected despite the absence of a diagnostics message on the 375 Field Communicator display, follow the procedures described in Table 3-1 to verify that transmitter har...
Page 70 - LCD Display; Process Variable
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 3-38 HART LCD Display The LCD display displays abbreviated diagnostic messages for troubleshooting the transmitter. To accommodate two-word messages, the display alternates between the first and second word. Some diagnostic messa...
Page 73 - AMS Screens; Alarms and Alerts
Reference Manual 00809-0100-4021, Rev DANovember 2004 3-41 Rosemount 3144P HART AMS Screens AMS provides advanced diagnostic messages, as well as help screens for the messages. Using the help screens can provide quick reference to remedying the situation. The trouble shooting section for this manual...
Page 75 - Fiel; Section 4
Reference Manual 00809-0100-4021, Rev DANovember 2004 Rosemount 3144P www.rosemount.com F OUNDATION Fiel dbus Section 4 F OUNDATION Fieldbus Configuration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1Safety Messages . . . . . . . . . . . . . . . . . ...
Page 76 - Device Description; fieldbus protocol is device revision 1.; Node Address; fieldbus host systems to automatically recognize the device and; Modes
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-2 F OUNDATION Fieldbus GENERAL BLOCK INFORMATION Device Description Before configuring the device, ensure the host has the appropriate Device Description file revision for this device. The device descriptor can be found on www....
Page 77 - Link Active Scheduler
Reference Manual 00809-0100-4021, Rev DANovember 2004 4-3 Rosemount 3144P F OUNDATION Fiel dbus NOTE When an upstream block is set to OOS, this will impact the output status of all downstream blocks. The figure below depicts the hierarchy of blocks: Link Active Scheduler The 3144P can be designated ...
Page 78 - Capabilities; Virtual Communication Relationship (VCRs); FIELDBUS; Sensor Transducer Block (index number 1100)
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-4 F OUNDATION Fieldbus Block instantiation is done by the host control system or configuration tool, but not all hosts are required to implement this functionality. Please refer to your specific host or configuration tool manua...
Page 79 - RESOURCE BLOCK; FEATURES
Reference Manual 00809-0100-4021, Rev DANovember 2004 4-5 Rosemount 3144P F OUNDATION Fiel dbus Analog Input Block (index number 1400, 1500, and 1600) The Analog Input Function Block (AI) processes the measurements from the sensor and makes them available to other function blocks. The output value f...
Page 81 - PlantWeb; Electronics
Reference Manual 00809-0100-4021, Rev DANovember 2004 4-7 Rosemount 3144P F OUNDATION Fiel dbus MAX_NOTIFY The MAX_NOTIFY parameter value is the maximum number of alert reports that the resource can have sent without getting a confirmation, corresponding to the amount of buffer space available for a...
Page 84 - Damping
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-10 F OUNDATION Fieldbus Table 4-4. Resource Block SUMMARY_STATUS messages Table 4-5. Resource Block RB.DETAILED_STATUS SENSOR TRANSDUCER BLOCK NOTE When the engineering units of the XD_SCALE in the associated AI Block are selec...
Page 88 - Simulation; Manual Mode; Configure the AI block; CHANNEL
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-14 F OUNDATION Fieldbus ANALOG INPUT (AI) Simulation Simulate replaces the channel value coming from the Sensor Transducer Block. For testing purposes, it is possible to manually drive the output of the Analog Input Block to a ...
Page 91 - Filtering; Process Alarms
Reference Manual 00809-0100-4021, Rev DANovember 2004 4-17 Rosemount 3144P F OUNDATION Fiel dbus AI2 as Terminal Temperature (body temperature) 1. Put the AI Block into OOS mode. a. Go to MODE_BLK.TARGET b. Choose OOS (0x80) 2. Go to CHANNEL a. Choose Body Temperature 3. Go to L_TYPE a. Choose Direc...
Page 92 - Status
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-18 F OUNDATION Fieldbus Alarm Priority Alarms are grouped into five levels of priority: Status When a PV is passed from one function block to another, it passes a STATUS along with the PV. The STATUS can be: GOOD, BAD, or UNCER...
Page 93 - Analog Input Diagnostics
Reference Manual 00809-0100-4021, Rev DANovember 2004 4-19 Rosemount 3144P F OUNDATION Fiel dbus Analog Input Diagnostics Table 4-10. AI BLOCK_ERR Conditions. Table 4-11. Troubleshooting the AI block Condition Number Condition Name and Description 0 Other 1 Block Configuration Error: the selected ch...
Page 94 - OPERATION; METHODS AND MANUAL OPERATION; Trim the Transmitter
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-20 F OUNDATION Fieldbus OPERATION Overview This section contains information on operation and maintenance procedures. METHODS AND MANUAL OPERATION Each F OUNDATION fieldbus host or configuration tool has different ways of displ...
Page 97 - SPM Configuration; Enter the Parameter Index of the parameter to be monitored.
Reference Manual 00809-0100-4021, Rev DANovember 2004 4-23 Rosemount 3144P F OUNDATION Fiel dbus Monitoring Phase The monitoring phase starts after the learning process is complete. The algorithm compares the current values to the baseline values of the mean and standard deviation. During this phase...
Page 99 - PROBLEMS WITH COMMUNICATIONS
Reference Manual 00809-0100-4021, Rev DANovember 2004 4-25 Rosemount 3144P F OUNDATION Fiel dbus TROUBLESHOOTING GUIDES Figure 4-2. 3144P troubleshooting flowchart Device does not appear on segment. Problem Identified? Yes No Perform Recommended Action, see Table 4-12. Check Segment, see “Device doe...
Page 101 - COMMUNICATIONS ESTABLISHED BUT HAVE
Reference Manual 00809-0100-4021, Rev DANovember 2004 4-27 Rosemount 3144P F OUNDATION Fiel dbus Figure 4-3. Problems with communications flowchart COMMUNICATIONS ESTABLISHED BUT HAVE “BLOCK_ERR” OR AN “ALARM” CONDITION. See “PlantWeb ™ Alerts” on page 4-7 Read the following parameters in the Resour...
Page 102 - fieldbus Troubleshooting
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 4-28 F OUNDATION Fieldbus F OUNDATION Fieldbus If a malfunction is suspected despite the absence of a diagnostics message, follow the procedures described in Table 4-13 to verify that transmitter hardware and process connections ...
Page 105 - Section 5
Reference Manual 00809-0100-4021, Rev DANovember 2004 Rosemount 3144P www.rosemount.com Section 5 Maintenance Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-2 SAFETY ...
Page 106 - Removing the Electronics Module
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 5-2 MAINTENANCE The 3144P transmitter has no moving parts and require a minimum amount of scheduled maintenance. The transmitter features a modular design for easy maintenance. If a malfunction is suspected, check for an external...
Page 107 - the transmitter housing.
Reference Manual 00809-0100-4021, Rev DANovember 2004 5-3 Rosemount 3144P 3. Loosen the two screws that anchor the electronics module assembly to the transmitter housing. 4. Firmly grasp the screws and assembly and pull it straight out of the housing, taking care not to damage the interconnecting pi...
Page 109 - Certified SIS; Section 6; The 3144P is certified by T
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www.rosemount.com Certified SIS Section 6 Certified Safety Instrumented System (SIS) 4–20 mA only Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6-1Certification . . . . . . . . . . . . . ....
Page 110 - INSTALLATION; Damping and Alarm Levels
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 6-2 Certified SIS INSTALLATION No special installation is required in addition to the standard installation practices outlined in this document. Always ensure a proper seal by installing the electronics housing cover(s) so that m...
Page 111 - SIS Additions
Reference Manual 00809-0100-4021, Rev DA November 2004 6-3 Rosemount 3144P Certified SIS Security Switch Position the security switch to the “ON” position to prevent accidental or deliberate change of configuration data during normal operation. SIS Additions In addition to the dual sensor configurat...
Page 114 - Proof Test; Abbreviated Proof Test
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 6-6 Certified SIS OPERATION AND MAINTENANCE Proof Test The following proof tests are recommended. In the event that an error is found in the safety functionality, proof test results and corrective actions taken must be documented...
Page 117 - Prior Use SIS; Section 7; Refer to the 3144P SIS FMEDA report for failure rate data.
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P www.rosemount.com Prior Use SIS Section 7 Prior Use (PU) Safety Instrumented System 4–20 mA only Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7-1Safe Failure Fraction . . . . . . . ....
Page 118 - Failure Mode Switch
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P 7-2 Prior Use SIS SAFE FAILURE FRACTION The Safe Failure Fraction calculation for the combination of the 3144P and the process sensor must consider the effects of the transmitter’s process sensor diagnostics. The following is an ...
Page 121 - Appendix A; HART AND F; FIELDBUS SPECIFICATIONS; Physical Specifications; Electronics Housing
Reference Manual 00809-0100-4021, Rev DANovember 2004 Rosemount 3144P www.rosemount.com Appendix A Reference Data HART and Foundation Fieldbus Specifications . . . . . . . . page A-1HART / 4–20 mA Specifications . . . . . . . . . . . . . . . . . . . . . page A-6Foundation Fieldbus Specifications . ....
Page 122 - The 3144P maintains a specification conformance of at least 3
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-2 Mounting Transmitters may be attached directly to the sensor. Optional mounting brackets (codes B4 and B5) permit remote mounting. See “Optional Transmitter Mounting Brackets” on page A-12. Weight Enclosure Ratings NEMA 4X, C...
Page 123 - External Ground Screw Assembly
Reference Manual 00809-0100-4021, Rev DANovember 2004 A-3 Rosemount 3144P External Ground Screw Assembly The external ground screw assembly can be ordered by specifying code G1 when an enclosure is specified. However, some approvals include the ground screw assembly in the transmitter shipment, henc...
Page 124 - Accuracy
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-4 Accuracy Reference Accuracy Example (HART only) When using a Pt 100 ( α = 0.00385) sensor input with a 0 to 100 °C span: Digital Accuracy would be ±0.10 °C, D/A accuracy would be ±0.02% of 100 °C or ±0.02 °C, Total = ±0.12 °C...
Page 125 - Ambient Temperature Effect
Reference Manual 00809-0100-4021, Rev DANovember 2004 A-5 Rosemount 3144P Ambient Temperature Effect Table A-1. Ambient Temperature Effect Transmitters may be installed in locations where the ambient temperature is between –40 and 85 °C (–40 and 185 °F).To maintain excellent accuracy performance, ea...
Page 126 - S Wave 8
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-6 HART / 4–20 MA SPECIFICATIONS Power Supply External power supply required. Transmitters operate on 12.0 to 42.4 V dc transmitter terminal voltage (with 250 ohm load, 18.1 V dc power supply voltage is required). Transmitter po...
Page 127 - Temperature Limits
Reference Manual 00809-0100-4021, Rev DANovember 2004 A-7 Rosemount 3144P Temperature Limits HART Communicator Connections 375 Field Communicator connections are permanently fixed to power/signal block. Failure Mode The 3144P features software and hardware failure mode detection. An independent circ...
Page 128 - Power Supply; Fieldbus with standard fieldbus power supplies.
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-8 F OUNDATION FIELDBUS SPECIFICATIONS Power Supply Powered over F OUNDATION Fieldbus with standard fieldbus power supplies. Transmitters operate on 9.0 to 32.0 V dc, 11 mA maximum. Transmitter power terminals are rated to 42.4 ...
Page 129 - Fieldbus Parameters; Function Blocks
Reference Manual 00809-0100-4021, Rev DANovember 2004 A-9 Rosemount 3144P Status If self-diagnostics detect a sensor burnout or a transmitter failure, the status of the measurement will be updated accordingly. The status may also send the PID output to a safe value. F OUNDATION Fieldbus Parameters S...
Page 130 - Instantiable Function Blocks; DIMENSIONAL DRAWINGS; Transmitter Exploded View
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P A-10 Instantiable Function Blocks • All the function blocks used by the transmitter are instantiable, meaning the total number of function blocks is only limited by the physical memory available in the transmitter. Since only the...
Page 131 - Transmitter Dimensional Drawing for Conduits with
Reference Manual 00809-0100-4021, Rev DANovember 2004 A-11 Rosemount 3144P Transmitter Dimensional Drawing Top View Side View Dimensions are in inches (millimeters) Transmitter Dimensional Drawing for Conduits with M20 x 1.5, PG 13.5, and JIS G 1 / 2 Entries Top View Front View Dimensions are in inc...
Page 133 - Fieldbus Wiring Diagram
Reference Manual 00809-0100-4021, Rev DANovember 2004 A-13 Rosemount 3144P FIGURE 1. HART / 4–20 mA Wiring Diagram 3144P Single-Sensor Connections Diagram 3144P Dual-Sensor Connections Diagram * Transmitter must be configured for a 3-wire RTD in order to recognize an RTD with a compensation loop. **...
Page 137 - option codes are selected.
Reference Manual 00809-0100-4021, Rev DANovember 2004 A-17 Rosemount 3144P To custom configure the 3144P with the dual-sensor option transmitter for one of the applications described below, indicate the appropriate option code in the model number. If a sensor type is not specified, the transmitter w...
Page 139 - Appendix B; Rosemount Temperature GmbH – Germany
Reference Manual 00809-0100-4021, Rev DANovember 2004 Rosemount 3144P www.rosemount.com Appendix B Product Certifications Rosemount 3144P With HART / 4–20 mA . . . . . . . . . . . . . page B-1Rosemount 3144P With Foundation fieldbus . . . . . . . . . page B-6Installation Drawings . . . . . . . . . ....
Page 141 - II 3 G; II 1 G; Australian Certifications
Reference Manual 00809-0100-4021, Rev DANovember 2004 B-3 Rosemount 3144P N1 CENELEC / ATEX Type n Approval (Zone 2) Certificate Number: BAS01ATEX3432XATEX Category Marking II 3 G EEx nL IIC T6 (T amb = –40 to 50 °C) EEx nL IIC T5 (T amb = –40 to 75 °C) U i = 55V Special Conditions for Safe Use (X):...
Page 142 - Brazilian Certifications
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-4 N7 Type N Approval Certificate Number: AUS Ex 02.3794XEx n IIC T6 (T amb = –60 to 50 °C) Ex n IIC T5 (T amb = –60 to 75 °C) IP66U n = 55 V P n = 1.3 W I7 Intrinsic Safety Approval Certificate Number: AUS Ex 02.3794XEx ia IIC ...
Page 143 - Additional Certifications
Reference Manual 00809-0100-4021, Rev DANovember 2004 B-5 Rosemount 3144P Additional Certifications American Bureau of Shipping (ABS) Type Approval ABS Type Approval for temperature measurements in hazardous locations on ABS Classed Vessels, Marine and Offshore Installations. Type Approval is based ...
Page 145 - Canadian Standards Association (CSA) Approvals
Reference Manual 00809-0100-4021, Rev DANovember 2004 B-7 Rosemount 3144P Temperature codes: T5 (T amb = – 60 to 75 °C), T6 (T amb = – 60 to 50°C) Canadian Standards Association (CSA) Approvals I6 CSA Intrinsic Safety / FISCO and Division 2 Intrinsically Safe / FISCO for use in Class I, Division 1, ...
Page 146 - Special Conditions for Safe Use:
Reference Manual 00809-0100-4021, Rev DA November 2004 Rosemount 3144P B-8 Table B-4. Input Entity Parameters Special Conditions for Safe Use (x): 1. The apparatus enclosure may contain light metals. The apparatus must be installed in such a manner as to minimize the risk of impact or friction with ...