- Page 2 – Serial Communications; INSTALLATION; label holder labels; Mounting; Outline and Installation; Connecting Slave ATS Annunciators; Outline
- Page 3 – Power Wiring; To prevent damage do not; Communication Wiring; Located on right side of circuit board.; Networks for Interconnecting ATS Annunciators and ATSs
- Page 4 – SETTING UP THE ATS ANNUNCIATORS; Set Number of Masters and Master Address; ON; Set Number of Slaves
- Page 7 – Note
- Page 8 – Serial No. and Catalog No. from the transfer switch nameplate.
381333–063 B
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
telephone 519 758–8450, fax 519 758–0876, for service call 1 888 234–2726 (ASCO) www.asco.ca
Owner’s
Manual
ATS Annunciator
Catalog 214A400, 214A401, 214A404
DANGER is used in this manual to warn of high
voltages capable of causing shock, burns, or death.
WARNING is used in this manual to warn
of possible personal injury.
!
CAUTION is used in this manual to warn
of possible equipment damage.
!
Master ATS Annunciator
Catalog 214A400, 214A404
Catalog 214A401
Slave ATS Annunciator
An experienced licensed electrician must install the ATS
Annunciator.
General
There are three types of ATS (Automatic Transfer
Switch) Annunciators. They are identified as follows:
Catalog 214A400 Master Unit
Catalog 214A404 Master Unit
used with a Network Supervisor
Catalog 214A401 Slave Unit
Each installation must have a master unit; each
master unit can support two slave units. Each unit can
annunciate four ATSs. Therefore a master and two
slave units can annunciate up to twelve ATSs. To
annunciate more ATSs, additional masters and slaves
can be added.
ASCO Catalog 214A400, 214A404, and 214A401
ATS Annunciators are designed to provide remote
visual status reporting and push button testing of ASCO
automatic transfer switches. Each ATS must have a
Group 1*, 5, 6, or 7 Microprocessor Controller with
Accessory 72A Serial Communication Interface Option
installed.
*
Note
: Group 1 Controller must have version 8 or
lower software (dash number on microprocessor).
Ratings
Nominal Input Voltage
16 V ac 50 or 60 Hz,
. . . . . . . .
or 12 or 24 V dc
. . . . . . . . . . . .
Volt-Ampere Burden
➀
10 VA max @ 16 V ac
. . . . . . .
0.5 A max @ 24 V dc
. . . . . . .
Environmental Temperature Range --- 20
˚
C. to +70
˚
C.
Transient Withstand
per NEMA ICS 1 --- 109
. . . . . . . .
Surge Withstand (SWC)
IEEE Std 472 --- 1974
. . . . . . .
ANSI C37.90A --- 1974
. . . . . .
Max total distance for Communication Line 4000 ft
➁
➀
(Master with 2 Slaves)
➁
For greater distances contact ASCO.
Table of Contents
section-page
Iinstallation
1-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Up the ATS Annunciator
3-5
. . . . . . . . . . .
Operation and ATS Testing
6
. . . . . . . . . . . . . . . .
Troubleshooting
7
. . . . . . . . . . . . . . . . . . . . . . . . . .
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
1 Serial Communications Serial communications permits large amounts of information to be processed over a few wires. In the serial communications systems used by ASCO, each individual device in the system --- automatic transfer switch, bypass-isolation switch, ATS annunciator, etc. --- has a unique ...
2 INSTALLATION (continued) Power Wiring The Master ATS Annunciator can be powered by either an ac or dc source (but not both) as shown on the Outline and Installation drawing 387797 and in Figure 3. For ac wiring use a Class 2 bell transformer with a 120 V ac primary and a 16 V ac secondary (12 VA m...
3 SETTING UP THE ATS ANNUNCIATORS Catalog 214A400, 214A404 Master ATS Annunciators Catalog 214A401 Slave ATS Annunciator Master ATS Annunciator factory default settings Slave ATS Annunciator factory default settings Figure 5. DIP switches in Master. Figure 6. DIP switches in Slave. Before applying p...