Emerson 185 - Manual
Emerson 185 – Manual, read for free online in PDF format. We hope this helps you resolve any issues you may have. If you have further questions, please contact us through the contact form.
Table of Contents:
- Page 2 – Nameplate; The Transfer Switch nameplate includes data for; Catalog Number Identification; A typical Catalog Number is shown below with its
- Page 3 – INSTALLATION; NOTICE
- Page 4 – CONTROLLER; Before using the transfer test button, be sure that
- Page 5 – Table A. Generator Start Connections; Clock Battery; Exercise with or without Load; Table B. Generator Exercise Settings; To Set Exerciser; Set Engine Exerciser; To Cancel an Active Exercise Period; Bypass Time Delay
- Page 6 – Table C. Time Delay Settings
- Page 7 – Remote test; Table F. Remote transfer to generator; Bypass load transfer to utility time delay; Table G. Bypass load transfer to utility delay; Load disconnect feature; Table H. Factory Settings – Summary
- Page 8 – FUNCTIONAL TEST; ALL POWER OFF
- Page 10 – TROUBLESHOOTING; ELECTROCUTION FLASH HAZARD Do not work; Problem
- Page 12 – INDEX
381333–319 E
50 Hanover Road, Florham Park, New Jersey 07932–1591 USA
For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
Operator’s
Manual
Series 185
Automatic Transfer Switches
100 through 400 ampere sizes
DANGER is used in this manual to warn of a
hazard situation which, if not avoided, will result in
death or serious injury.
WARNING is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION is used in this manual to warn of a
hazardous situation which, if not avoided, could
result in minor or moderate injury.
An experienced licensed electrician must install the ATS.
100–230 ampere sizes
Refer to the outline and wiring drawings provided with
your ASCO Series 185 ATS for all installation details.
ASCO Series 185 Automatic Transfer Switches (ATSs) are
Listed under Underwriter’s Laboratories Standard for
Transfer Switch Equipment, UL–1008. They are intended
for use only in optional standby systems in accordance with
the National Electrical Code, NEC/NFPA 70, Article 702.
This ATS is for use with 2–wire automatic–start generators
only.
Refer to Application Information 381339–292 to confirm
that you have selected the appropriate product for the
intended installation.
This automatic transfer switch is intended for standby
power applications in residential / light commercial use
only.
This product is not intended for emergency
or life–support systems.
If you have more stringent application requirements contact
ASCO Power Technologies for other products suitable for
critical applications.
Rating Label
Each automatic transfer switch contains a rating label to
define the loads and fault circuit withstand / closing ratings.
Refer to the label on the transfer switch for specific values.
Do not exceed the values on the rating label.
Exceeding the rating can cause person injury or
serious equipment damage.
TABLE OF CONTENTS
page
INSTALLATION
1
. . . . . . . . . . . . . . . . . . . . . . . . . .
CONTROLLER
2–5
. . . . . . . . . . . . . . . . . . . . . . . .
FUNCTIONAL TEST
6
. . . . . . . . . . . . . . . . . . . . . .
SEQUENCE OF OPERATION
7
. . . . . . . . . . . . .
TROUBLESHOOTING
8–9
. . . . . . . . . . . . . . . . . .
INDEX
10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
"Loading the manual" means you need to wait until the file loads and becomes available for online reading. Some manuals are very large, and the time they take to appear depends on your internet speed.
Summary
Series 185 381333–319 E Nameplate The Transfer Switch nameplate includes data for each specific ASCO Series 185 ATS. Use the ATS only within the limits shown on this nameplate. Catalog Number Identification A typical Catalog Number is shown below with its elements explained. The example is for a D–d...
INSTALLATION Series 185 1 381333–319 E Installation of the ASCO Series 185 automatic transfer switch (ATS) must be performed by a licensed electrician.It must be installed according to the National Electrical Code (NEC) and all local electrical code requirements. Remove the enclosure cover and inspe...
CONTROLLER Series 185 2 381333–319 E The Group 4 digital Controller is used in ASCO Series 185 automatic transfer switches. It provides the sensing,timing, and control functions for the ATS. This micro– processor–based controller includes built–in control buttons and status lights for control of the...