Page 2 - Requesting a Declaration of Conformity
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: S Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 60950 Third Edition S EU Directives: 73/23/EEC, Council Directive on equipment designed for use with...
Page 3 - Class A EMC Statements; VCCI Notice
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interferencewhen the equipment is operated in a co...
Page 4 - Special Symbols; RISK OF ELECTRIC SHOCK; - Indicates that a risk of electric shock is present and the
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to importantinformation: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your op...
Page 5 - Table of Contents
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality i Table of Contents 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Warnings 2 . . . . . . . . . . . . . . . . . . . . . . . ....
Page 6 - Operation
TABLE OF CONTENTS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality ii Startup for Hardwired Units 71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Initial Startup Parameters 74 . . . . . . ...
Page 7 - The Eaton
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 1 Chapter 1 Introduction The Eaton ® 9170 + uninterruptible power system (UPS) is a modular UPS that contains battery modules and power control modules (referred to aspower modules). These modules plug into a rack ...
Page 8 - Safety Warnings; IMPORTANT SAFETY INSTRUCTIONS
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation andmaintenance of the UPS and batteries. P...
Page 9 - Consignes de Sécurité; CONSIGNES DE SÉCURITÉ IMPORTANTES; Les modules de batterie à utiliser dans le système Eaton 9170+
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 3 Consignes de Sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de touteprocédure d'installation ...
Page 10 - Advertencias de Seguridad; INSTRUCCIONES DE SEGURIDAD IMPORTANTES
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 4 Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES Este manual contiene instrucciones importantes que debe seguir durante la instalación y elmantenimiento del...
Page 11 - Physical Features; Front Cover
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 5 Physical Features The Eaton 9170+ UPS is available in four cabinet sizes. Figure 1 throughFigure 6 show the 3-slot and 9-slot configurations and identify basicEaton 9170+ system features. Six-slot an...
Page 12 - Front Panel Display
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 6 Front Panel Display Front Cover Cabinet Base Figure 3. Nine-Slot Cabinet (Front View)
Page 13 - DB-9 Communication Port
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 7 CommunicationSlots Power Outlets(optional) Input PowerCable (optional) DB-9 Communication Port Wiring Access Figure 4. Nine-Slot Cabinet (Rear View) Handle/LatchRelease Insertion/ExtractionCams Handl...
Page 15 - Setup, including clearances and location requirements; Equipment Clearances; ) at the sides of the UPS for
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 9 Chapter 2 Installation Setup This chapter explains how to set up and install the Eaton 9170+cabinets: S Setup, including clearances and location requirements S Caster cart installation (for 3- and 6-slot cabinets...
Page 16 - Location Requirements; Place the cabinet in its intended operating location.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 10 Location Requirements Install the Eaton 9170+ UPS as close as possible to the equipment orthe load distribution panel it will protect. If this distance is more than7.6m (25 ft), transient nois...
Page 17 - hex-style socket wrench to turn each bolt; Do not use the caster bolts to level the cabinet.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 11 5. If installing the 3- or 6-slot cabinet in a rack, see ”Rack-MountInstallation (Three- and Six-Slot Cabinets)” on page 14 to install thecabinet in the rack. 6. If you are installing an exter...
Page 18 - Caster Cart; Figure 7. Three-Slot Cabinet Being Lowered onto Caster Cart
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 12 5. If installing the 9- or 12-slot cabinet in a rack, follow the installationinstructions with the 9- and 12-slot rack-mount kit. 6. If you are installing an external battery cabinet, continue...
Page 19 - To install the caster cart:; customer-supplied screws; for the intended
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 13 To install the caster cart: 1. Place the caster cart (shipped separately from the UPS cabinet)under the cabinet before installing power and battery modules andbefore making connections to the ...
Page 20 - Stabilizer Bracket; Figure 8. Stabilizer Bracket Installation; containing brackets and required hardware, is available.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 14 4. Turn all four caster bolts counter-clockwise until the cabinet restson the floor. Place a plastic cap into each bolt access hole. NOTE If the floor is uneven and the cabinet is tilted or un...
Page 21 - Tab Slots; Figure 9. Metal Clip Nut and Tab Slot Locations
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 15 3. Carefully replace the UPS cabinet top cover and secure with thefour screws removed in Step 1. Position the cover lip to fit behindthe front panel display. 4. Install three metal clip nuts o...
Page 22 - Select the position for the UPS in the equipment rack.; Floor Anchor Kit Installation; Measurement
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 16 6. Select the position for the UPS in the equipment rack. 7. Select the proper holes in the rail that position the UPS at thedesired location in the rack. 8. With one person lifting each side ...
Page 23 - Figure 11. Floor Anchor Brackets Bolted to UPS Cabinet; Moving the Cabinets; Verify that the cabinet contains no power or battery modules.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 17 B A Floor AnchorBracket Figure 11. Floor Anchor Brackets Bolted to UPS Cabinet Moving the Cabinets C A U T I O N Do NOT attempt to raise the cabinet with the power or battery modules installed...
Page 24 - Pry the caps out of the bolt access holes.
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 18 4. Pry the caps out of the bolt access holes. 5. Use a 1/2 ” hex-style socket wrench to turn each of the four bolts clockwise. Doing so lowers the casters to allow the cabinet to rollon the ca...
Page 25 - through separate; — to the bypass switch, as shown in Figure 12.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 19 Chapter 3 UPS with Bypass Electrical Installation NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on page 61 for installing optional battery cabinets or to “UPS Startup” on pa...
Page 26 - External Batteries; Figure 12. Typical Installation with a Bypass Switch
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 20 External Bypass Switch Off Service Line Off Service Line UPS UPS Off Service Line UPS User-Supplied (if required) External Batteries (optional) Building Service Panel Load...
Page 27 - Input Current Ratings; UPS Capacity
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 21 Input Current Ratings Table 1 contains the required circuit breaker ratings for hardwiredinstallations. Circuit breaker ratings for units having an input line cord aredete...
Page 28 - Table 2. Recommended Wire Sizes; Input Circuit Breaker Size; This table lists the mm; Bypass Switches; The bypass switch has four positions as described in Table 3.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 22 See Table 2 for recommended conductor sizes to wire the input circuitbreakers. Table 2. Recommended Wire Sizes Input Circuit Breaker Size 75°C Copper Wire Size Conductor S...
Page 29 - Table 3. Bypass Switch Positions; Switch Position; LINE; Bypass Switch Operation
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 23 NOTE In the UPS or LINE position, AC input power is still connected to the input terminals inside the UPS. Table 3. Bypass Switch Positions Switch Position Description LIN...
Page 30 - Help
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 24 After turning the load position handle to the UPS position and releasingthe red button, the Eaton 9170+ UPS remains in Bypass mode. Forproper operation, return the UPS to ...
Page 31 - Table 4. Bypass Switch Specifications
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 25 Table 4. Bypass Switch Specifications Bypass Switch Models Rating, Continuous See Figure 13 Weight BBM MBB Height Width Depth Mounting Centers (A) (B) (C) (D) (E) BPE12BBM...
Page 32 - UPS Installation with an External Bypass Switch; To install the UPS with an external bypass switch:
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 26 UPS Installation with an External Bypass Switch W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform the electricalinstallation. ...
Page 33 - Entrance Panel
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 27 Entrance Panel Battery Cable Wiring Access Holefor Optional EPO andBypass Input Signals Wiring Access Hole foran Optional GeneratorInput Signal Figure 14. UPS Power Entran...
Page 34 - Figure 15. UPS Input and Output Terminals
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 28 6. Install the conduit adapters. AC input and AC output conductorsmust be run through separate conduits. UPS output circuits mustbe installed in dedicated conduit systems ...
Page 35 - Figure 16 shows a sample label.
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 29 7. Find the terminal strip inside the bypass switch cabinet. Using thelabel on the back of the bypass switch access cover and the properinstallation wiring diagram, make t...
Page 36 - Wire the UPS for the proper input voltage as shown in Figure 17.; GND; Figure 17. UPS Input Wiring
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 30 9. Wire the UPS for the proper input voltage as shown in Figure 17. Split-phase power modules (model ASY-0673, with brown labels onthe front) are capable of supplying two ...
Page 37 - Figure 19. Universal Power Modules
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 31 Figure 18 and Figure 19 describe output wiring configurations forvarious output voltages. You must also set the operatingmenu 4 2 4 for the required output voltage as show...
Page 38 - Plastic Cable Tie; Figure 20. Input Control Signal Wiring (for MBB Bypass Switch)
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 32 13. If the bypass switch is an MBB style, notice the cable routed out ofthe left side of the bypass switch cabinet. Connect the red andblack pair of wires (normally open) ...
Page 39 - Generator Set; Figure 21. Input Control Signal Wiring (for External Controls)
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 33 14. If any external hardwired control signals are required (EPO orGenerator On), connect the wiring as shown in Figure 21. C A U T I O N EPO and external bypass circuits a...
Page 40 - System Wiring Diagrams; Table 5. UPS with Bypass Wiring Diagrams
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 34 System Wiring Diagrams Select wiring diagrams from Table 5 based upon the installation voltage. Table 5. UPS with Bypass Wiring Diagrams UPS Input Voltage UPS Output Volta...
Page 41 - The customer must provide input overcurrent protection.; The customer must size the AC circuit conductors.; All AC circuit; The customer must provide output overcurrent protection.; See NEC
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 35 The following notes are referenced in the system wiring diagrams(Figure 22 through Figure 24). NOTE 1 The customer must provide input overcurrent protection. See NEC Secti...
Page 45 - Figure 25. Typical Installation without a Bypass Switch
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 39 Chapter 4 UPS Electrical Installation NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on page 61 for installing optional battery cabinets or to “UPS Startup” on page 67. W A R...
Page 47 - Table 7. Recommended Wire Sizes
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 41 See Table 7 for recommended conductor sizes to wire the input circuitbreakers. Table 7. Recommended Wire Sizes Input Circuit Breaker Size 75°C Copper Wire Size Conductor Screw Torque ...
Page 48 - UPS Electrical Installation; To install the UPS without an external bypass switch:
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 42 UPS Electrical Installation W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform the electricalinstallation. Risk of electrical shock. C A U ...
Page 50 - Figure 27. UPS Input and Output Terminals
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 44 3. Install the conduit adapters. AC input and AC output conductorsmust be run through separate conduits. UPS output circuits mustbe installed in dedicated conduit systems and not shar...
Page 51 - Wire the UPS for the proper input voltage as shown in Figure 28.; Figure 28. UPS Input Wiring
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 45 5. Wire the UPS for the proper input voltage as shown in Figure 28. Split-phase power modules (model ASY-0673, with brown labels onthe front) are capable of supplying two output volta...
Page 52 - Figure 30. Universal Power Modules
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 46 Figure 29 and Figure 30 describe output wiring configurations forvarious output voltages. You must also set the operatingmenu 4 2 4 for the required output voltage as shown in the wir...
Page 53 - Figure 31. Input Control Signal Wiring
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 47 8. If any external hardwired control signals are required (EPO orGenerator On), unscrew and remove the top rear cover of thecabinet and locate the terminal block (see Figure 31). C A ...
Page 54 - Table 8. Wiring Diagrams
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 48 System Wiring Diagrams Select wiring diagrams from Table 8 based upon the installation voltage. Table 8. Wiring Diagrams UPS Input Voltage UPS Output Voltage Output Wires Wiring Diagr...
Page 59 - Yes
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 53 Chapter 5 Isolated Output Wiring Diagrams NOTE This chapter is only for units manufactured before 2009. The wiring diagrams in this section are unique and specific toinstallations in which the output of the Eato...
Page 60 - Figure 35. Isolated Outputs – Single-Phase Voltages; with Isolated Output Option; Figure 36. Isolated Outputs – Derived Three-Phase Voltages; Neutral-to-Ground Bonding for Isolated Output
ISOLATED OUTPUT WIRING DIAGRAMS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 54 100, 110, 115, or 120 X2 50 or 60 Hz 100/200, 110/220, 115/230, or 120/240V Out with Isolated Output Option Menu 4 2 4 set to 200, 220, 230, or 240, as required. X1 X3 X X N-G Bon...
Page 67 - To install an external battery cabinet:
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 61 Chapter 6 Battery Cabinet Installation If you are not installing battery modules into a separate external batterycabinet, continue to “UPS Startup” on page 67. W A R N I N G Only qualified service personnel (suc...
Page 68 - Figure 42. UPS Power Entrance Panel
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 62 Entrance Panel Battery Cable Figure 42. UPS Power Entrance Panel 3. Use a pair of pliers to bend the narrow links (1 and 2 in Figure 43)between the outer edge of the lower breakaway ...
Page 69 - Cable Assembly; Figure 44. Bus-Bar Extension Installation
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 63 Cable Assembly Backplane Ring Terminal Compression Lug Bus-Bar Extension Assembly Figure 44. Bus-Bar Extension Installation 6. Remove the nuts holding the +DC and the –DC bus bars to...
Page 70 - Figure 45. Battery Cable Assembly Installation
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 64 Cable Assembly Figure 45. Battery Cable Assembly Installation 12. Align the screw holes of the cable assembly's entry plate withholes on the cabinet side cover as shown in Figure 45....
Page 71 - Figure 46. Battery Cable Installed in Battery Cabinet
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 65 ‒ + Figure 46. Battery Cable Installed in Battery Cabinet 17. Secure the + , the ‒ , and the conductors to the proper compression lugs on the battery cabinet backplane as shown inFig...
Page 72 - Figure 47. Connecting Additional Battery Cabinets
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 66 To UPS or PreviousBattery Cabinet To NextBattery Cabinet Figure 47. Connecting Additional Battery Cabinets 20. Reinstall the remaining rear covers using the original screws. 21. Cont...
Page 73 - Power and Battery Module Installation; Insert the battery modules into the cabinet.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 67 Chapter 7 UPS Startup This section provides step-by-step instructions for starting your Eaton9170+ system. Follow these procedures closely to avoid potentialdamage to your equipment or the UPS and to protect you...
Page 74 - Figure 48. Inserting the Modules
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 68 NOTE All power modules in the Eaton 9170+ UPS cabinet must be of the same type: Split-phase power modules have brown labels; universal (single-phase) power modules haveblack labels. Do not mix brown ...
Page 75 - Startup for Plug-Receptacle Units; Figure 49. Communication Port
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 69 Startup for Plug-Receptacle Units To start a plug-receptacle unit: 1. Plug the power cable of the unit into an approved, functional poweroutlet. 2. If external battery cabinets are installed, check t...
Page 76 - Figure 50. Balancing Receptacle Loads
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 70 6. If applicable, test proper operation of optional external controlsignals and computer communication before connecting the load.(See “DB-9 Communication Port” on page 92 for details.) 7. Plug the e...
Page 77 - Startup for Hardwired Units; To start a hardwired unit:
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 71 Startup for Hardwired Units To start a hardwired unit: 1. Confirm that an electrician has completed and tested theconnection to the proper power source. 2. If external battery cabinets are installed,...
Page 80 - Turn on the equipment that is connected to the UPS.; Initial Startup Parameters; and; ENTER PASSWORD
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 74 18. The UPS front panel display automatically turns on whenever inputpower is present and at least one power module is installed. Set upthe initial operating parameters through the front panel displa...
Page 81 - Set Time
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 75 2. Select the desired language for the display. Use the Y and B buttons to scroll between English, French, German, and Spanish.Enter your selection by pressing the button. 3. Set the clock for the lo...
Page 82 - Set Redundancy; or; No; Press the ON button on this screen to start the UPS.
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 76 6. The system signals an alarm when the required output cannot bemaintained with the loss of redundant power modules. The alarm isessentially disabled with a redundancy level set at 0. If you want th...
Page 83 - Double Conversion; Figure 52. UPS Operating Modes Under Auto Mode Control
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 77 Chapter 8 Operation The Eaton 9170+ UPS operates in several different modes. Normally itoperates under internal control (Auto mode) to automatically protectloads connected to it. An operator can enable manual ov...
Page 84 - Figure 53 shows the basic functional elements of the UPS.
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 78 Off mode turns off the output and most internal circuitry. Within thismode, Sleep mode turns off all internal circuitry when AC line is notpresent and battery voltage drops to a low threshold. If AC in...
Page 85 - Turning the UPS On; Removing Input Power
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 79 Turning the UPS On The unit has no physical On/Off switch. Access the UPS On/Off functionthrough the front panel display. If the UPS is off, press the ON button through the front panel display toturn t...
Page 86 - Wout; Figure 54. UPS Front Panel; Item; A and B
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 80 Front Panel Display The front panel has an alphanumeric display, three LED indicators, andsix pushbuttons as described in Figure 54 and in Table 10. 1 2 9 USER #3 Wout watts 2.07 KW Slot Top ESC 2 3 4 ...
Page 87 - Using the Front Panel Display; Figure 55. Typical Front Panel Display
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 81 Using the Front Panel Display Figure 55 shows an example of the front panel display. The numbers inthe upper left corner (1 2 9 in Figure 55) indicate the menu level. Theword in the top center (USER) i...
Page 88 - Config OFF Menu
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 82 During normal operation, the display appears as shown in Figure 56: Md: Current UPS operating mode St: Operational state Mn Number of power modules Bn Number of battery module strings currently online ...
Page 89 - Parameters; Changing Parameter Settings
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 83 Parameters The parameters describe the UPS operation. Some useful parametersare input and output voltage, input and output current, and batteryvoltage, among others. Some are operator‐adjustable, such ...
Page 90 - Reading the Eaton 9170+ System Logs; Inverter Log; button to; Figure 57. Inverter Log Entry; Message; Line Fault
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 84 Reading the Eaton 9170+ System Logs The Eaton 9170+ system makes an entry in its logs each time it soundsan alarm or runs on battery power. This information can help indiagnosing power problems. You ca...
Page 91 - Alarm Log; Low Battery; Figure 58. Alarm Log Entry; Open Cell; Figure 59. Alarm Entry for Specific Slot Number
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 85 Alarm Log The alarm log is in menu 2 2. Move through the menu structure bypressing the Menu button and pressing the B button to move down to menu 2. Press and then press the B button to move down to su...
Page 92 - Table 12 lists the alarm log messages.; Battery Test
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 86 Table 12 lists the alarm log messages. Table 12. Alarm Log Messages Message Explanation Open Cell Battery failure caused by open cell. Weak Battery Battery failure caused by load test. Phase Error Inte...
Page 93 - Menu Map
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 87 Menu Map Figure 60 shows all the Eaton 9170+ system parameters. The menustructure has six primary-level menus, System Status Menu (1) throughService Menu (6). Each primary menu has secondary items numb...
Page 95 - Power Management and Protection Software
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 89 Chapter 9 Communication Eaton offers several methods of communicating with your Eaton 9170+system in addition to the front panel display: S Power Management and Protection Software S Optional interface kits S Co...
Page 96 - ConnectUPS; Dedicated Input Signals; Connection to a facility Emergency Shutdown
COMMUNICATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 90 ConnectUPS t Web/SNMP Card (BD Model) The ConnectUPS-BD Web/SNMP Card provides the Eaton 9170+system with its own ethernet network connection, allowing it to beremotely monitored and controlled via...
Page 97 - An external signal can indicate that the input power is
COMMUNICATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 91 On-Generator: An external signal can indicate that the input power is being supplied by a generator. Closure of this contact causes the UPS tochange the following parameters to preset values that a...
Page 98 - Pin
COMMUNICATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 92 DB-9 Communication Port Table 13 explains the functions of the pins on the Eaton 9170+ DB-9communication port. This port is on the Eaton 9170+ UPS rear panel, asshown in Figure 49 on page 69. Table...
Page 99 - Maintenance; Routine Maintenance; Inspect and clean the cabinet.
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 93 Chapter 10 Maintenance Routine Maintenance NOTE Observe important safety precautions while performing these checks. NOTE Eaton recommends that you schedule preventive maintenance checks at least every six months...
Page 100 - Storage Temperature; shelf life if they are kept below +25; Battery Replacement; To replace battery modules in pairs:
MAINTENANCE Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 94 Storage Temperature Store the Eaton 9170+ battery modules (in the UPS or external batterycabinet) at –20 to +40 ° C (–4 to +104 ° F). Batteries will have a longer shelf life if they are kept below +2...
Page 101 - Pull the module out approximately 17 cm (7; Power Module Replacement; Remove the front cover.
MAINTENANCE Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 95 3. Pull the module out approximately 17 cm (7 ” ) to the secondary stop on top of the module. 4. Press down on the secondary stop release, pull the module outfarther, and support the module weight wi...
Page 102 - Replace the front cover.
MAINTENANCE Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 96 3. Use two hands to support the module. When fully extended, lowerthe front down slightly and lift the rear edge over the safety stop onthe center support rail. 4. Treat the original and replacement ...
Page 103 - Specifications; Electrical input and output; DC fuse and battery charger overvoltage limit network; Table 15. Application of Neutral to Ground Bonding
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 97 Chapter 11 Specifications This section provides the following specifications for the Eaton 9170+models: S Electrical input and output S Model specifications S Environmental and safety S Battery S Weights and dim...
Page 104 - NA
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 98 Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) Three-Slot Cabinet Optional Chargers UPS kVA/Watts Input Current (200V)* Output Current (100/200V, 110/220V, 120/240V) Recom...
Page 105 - CAUTION
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 99 Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued) Nine- and Twelve-Slot Cabinet CAUTION Do NOT install more than seven power and/or battery charger modules in a 9...
Page 110 - Table 18. Environmental and Safety; Optimal battery performance: 25
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 104 Table 18. Environmental and Safety Operating Temperature 0 ° C to 40 ° C (32 ° F to 104 ° F) Optimal battery performance: 25 ° C (77 ° F) Storage Temperature UPS with battery modules: –20 ° C to ...
Page 111 - Table 20. Weights and Dimensions; Cabinet Size; Optional floor anchor kit weighs 4 kg (9 lb)
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 105 Table 20. Weights and Dimensions Cabinet Size Height Width Depth Weight* 3-slot 45 cm (17.75 ” ) 43 cm (17.0 ” ) 65 cm (25.5 ” ) 30 kg (66 lb) 3-slot (with caster cart) 49.5 cm (19.5 ” ) 43 cm (1...
Page 113 - Troubleshooting; Table 21. Frequently Asked Questions; Answer; Turn off the alarm beeps?
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 107 Chapter 12 Troubleshooting The following table provides answers to commonly asked questions. Table 21. Frequently Asked Questions Question: “How do I... ” Answer Turn the UPS on? Verify that all power modules a...
Page 114 - To view or change the redundancy level, go to menu 4 2 5.
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 108 Answer Question: “How do I... ” Check the condition of thebatteries? The results of the most recent battery test are stored at menu 3 1 2 1. To run a test ofbattery condition, go to menu 3 1 1 a...
Page 115 - Alarms; S High AC Input; Figure 61. Typical System Active Alarm Display; M Batt Test Failed 1; Figure 62. Detailed Alarm Entry
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 109 Alarms Figure 61 shows a typical alarm display. Alarms are annunciated by aconstant Alarm LED and a constant beep. During alarm display,button (A) silences the audible alarm, button (B) clears t...
Page 116 - When an alarm occurs, follow these steps:; Table 22. Critical Alarm Messages; Alarm Message
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 110 When an alarm occurs, follow these steps: 1. Observe the display to see which alarm is active. NOTE To find out if more than one alarm is active, press . This switches the display between alarm ...
Page 117 - What to Do
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 111 What to Do What It Means Alarm Message P EPO The Emergency Power-off functionhas been activated. Deactivate the external EPO switch and restart theUPS by pressing the ON button through the front...
Page 119 - Service and Support; Local; Eaton Customer Support Center; Eaton; for the dealer or distributor nearest you.
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 113 Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Eaton Customer Support Center at one of the following telephone numbers. Available Supp...
Page 121 - Warranty; LIMITED WARRANTY PERIOD:
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 115 Chapter 13 Warranty Two-Year Limited Warranty (US and Canada) Eaton UPS Models: 9155, 9170+ and FERRUPS ® 4.3–18 kVA WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation Cor...
Page 122 - WHAT THIS LIMITED WARRANTY DOES NOT COVER:; LIMITATION OF LIABILITY:
WARRANTY Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 116 In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges forreturn of defective equipment and replacement of Warranted Items. Any returned Wa...
Page 123 - COSTS NOT RELATED TO WARRANTY:; Load Protection Guarantee (US and Canada); WHAT THIS GUARANTY COVERS:
WARRANTY Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 117 OTHER LIMITATIONS: Company's obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Compan...
Page 124 - WHAT THIS GUARANTY DOES NOT COVER:
WARRANTY Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 118 WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-User's equipment does not include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or da...