Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: S Harmonized Standards: EN 50091-1-1 and EN 50091-2; IEC 60950 Third Edition S EU Directives: 73/23/EEC, Council Directive on equipment designed for use with...
Class A EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interferencewhen the equipment is operated in a co...
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to importantinformation: RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated warning should be observed. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your op...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality i Table of Contents 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Warnings 2 . . . . . . . . . . . . . . . . . . . . . . . ....
TABLE OF CONTENTS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality ii Startup for Hardwired Units 71 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Initial Startup Parameters 74 . . . . . . ...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 1 Chapter 1 Introduction The Eaton ® 9170 + uninterruptible power system (UPS) is a modular UPS that contains battery modules and power control modules (referred to aspower modules). These modules plug into a rack ...
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation andmaintenance of the UPS and batteries. P...
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 3 Consignes de Sécurité CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de touteprocédure d'installation ...
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 4 Advertencias de Seguridad INSTRUCCIONES DE SEGURIDAD IMPORTANTES GUARDE ESTAS INSTRUCCIONES Este manual contiene instrucciones importantes que debe seguir durante la instalación y elmantenimiento del...
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 5 Physical Features The Eaton 9170+ UPS is available in four cabinet sizes. Figure 1 throughFigure 6 show the 3-slot and 9-slot configurations and identify basicEaton 9170+ system features. Six-slot an...
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 6 Front Panel Display Front Cover Cabinet Base Figure 3. Nine-Slot Cabinet (Front View)
INTRODUCTION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 7 CommunicationSlots Power Outlets(optional) Input PowerCable (optional) DB-9 Communication Port Wiring Access Figure 4. Nine-Slot Cabinet (Rear View) Handle/LatchRelease Insertion/ExtractionCams Handl...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 9 Chapter 2 Installation Setup This chapter explains how to set up and install the Eaton 9170+cabinets: S Setup, including clearances and location requirements S Caster cart installation (for 3- and 6-slot cabinets...
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 10 Location Requirements Install the Eaton 9170+ UPS as close as possible to the equipment orthe load distribution panel it will protect. If this distance is more than7.6m (25 ft), transient nois...
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 11 5. If installing the 3- or 6-slot cabinet in a rack, see ”Rack-MountInstallation (Three- and Six-Slot Cabinets)” on page 14 to install thecabinet in the rack. 6. If you are installing an exter...
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 12 5. If installing the 9- or 12-slot cabinet in a rack, follow the installationinstructions with the 9- and 12-slot rack-mount kit. 6. If you are installing an external battery cabinet, continue...
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 13 To install the caster cart: 1. Place the caster cart (shipped separately from the UPS cabinet)under the cabinet before installing power and battery modules andbefore making connections to the ...
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 14 4. Turn all four caster bolts counter-clockwise until the cabinet restson the floor. Place a plastic cap into each bolt access hole. NOTE If the floor is uneven and the cabinet is tilted or un...
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 15 3. Carefully replace the UPS cabinet top cover and secure with thefour screws removed in Step 1. Position the cover lip to fit behindthe front panel display. 4. Install three metal clip nuts o...
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 16 6. Select the position for the UPS in the equipment rack. 7. Select the proper holes in the rail that position the UPS at thedesired location in the rack. 8. With one person lifting each side ...
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 17 B A Floor AnchorBracket Figure 11. Floor Anchor Brackets Bolted to UPS Cabinet Moving the Cabinets C A U T I O N Do NOT attempt to raise the cabinet with the power or battery modules installed...
INSTALLATION SETUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 18 4. Pry the caps out of the bolt access holes. 5. Use a 1/2 ” hex-style socket wrench to turn each of the four bolts clockwise. Doing so lowers the casters to allow the cabinet to rollon the ca...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 19 Chapter 3 UPS with Bypass Electrical Installation NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on page 61 for installing optional battery cabinets or to “UPS Startup” on pa...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 20 External Bypass Switch Off Service Line Off Service Line UPS UPS Off Service Line UPS User-Supplied (if required) External Batteries (optional) Building Service Panel Load...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 21 Input Current Ratings Table 1 contains the required circuit breaker ratings for hardwiredinstallations. Circuit breaker ratings for units having an input line cord aredete...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 22 See Table 2 for recommended conductor sizes to wire the input circuitbreakers. Table 2. Recommended Wire Sizes Input Circuit Breaker Size 75°C Copper Wire Size Conductor S...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 23 NOTE In the UPS or LINE position, AC input power is still connected to the input terminals inside the UPS. Table 3. Bypass Switch Positions Switch Position Description LIN...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 24 After turning the load position handle to the UPS position and releasingthe red button, the Eaton 9170+ UPS remains in Bypass mode. Forproper operation, return the UPS to ...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 25 Table 4. Bypass Switch Specifications Bypass Switch Models Rating, Continuous See Figure 13 Weight BBM MBB Height Width Depth Mounting Centers (A) (B) (C) (D) (E) BPE12BBM...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 26 UPS Installation with an External Bypass Switch W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform the electricalinstallation. ...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 27 Entrance Panel Battery Cable Wiring Access Holefor Optional EPO andBypass Input Signals Wiring Access Hole foran Optional GeneratorInput Signal Figure 14. UPS Power Entran...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 28 6. Install the conduit adapters. AC input and AC output conductorsmust be run through separate conduits. UPS output circuits mustbe installed in dedicated conduit systems ...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 29 7. Find the terminal strip inside the bypass switch cabinet. Using thelabel on the back of the bypass switch access cover and the properinstallation wiring diagram, make t...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 30 9. Wire the UPS for the proper input voltage as shown in Figure 17. Split-phase power modules (model ASY-0673, with brown labels onthe front) are capable of supplying two ...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 31 Figure 18 and Figure 19 describe output wiring configurations forvarious output voltages. You must also set the operatingmenu 4 2 4 for the required output voltage as show...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 32 13. If the bypass switch is an MBB style, notice the cable routed out ofthe left side of the bypass switch cabinet. Connect the red andblack pair of wires (normally open) ...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 33 14. If any external hardwired control signals are required (EPO orGenerator On), connect the wiring as shown in Figure 21. C A U T I O N EPO and external bypass circuits a...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 34 System Wiring Diagrams Select wiring diagrams from Table 5 based upon the installation voltage. Table 5. UPS with Bypass Wiring Diagrams UPS Input Voltage UPS Output Volta...
UPS WITH BYPASS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 35 The following notes are referenced in the system wiring diagrams(Figure 22 through Figure 24). NOTE 1 The customer must provide input overcurrent protection. See NEC Secti...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 39 Chapter 4 UPS Electrical Installation NOTE If you have a plug-receptacle unit, continue to “Battery Cabinet Installation” on page 61 for installing optional battery cabinets or to “UPS Startup” on page 67. W A R...
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 41 See Table 7 for recommended conductor sizes to wire the input circuitbreakers. Table 7. Recommended Wire Sizes Input Circuit Breaker Size 75°C Copper Wire Size Conductor Screw Torque ...
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 42 UPS Electrical Installation W A R N I N G Only qualified service personnel (such as a licensed electrician) should perform the electricalinstallation. Risk of electrical shock. C A U ...
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 44 3. Install the conduit adapters. AC input and AC output conductorsmust be run through separate conduits. UPS output circuits mustbe installed in dedicated conduit systems and not shar...
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 45 5. Wire the UPS for the proper input voltage as shown in Figure 28. Split-phase power modules (model ASY-0673, with brown labels onthe front) are capable of supplying two output volta...
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 46 Figure 29 and Figure 30 describe output wiring configurations forvarious output voltages. You must also set the operatingmenu 4 2 4 for the required output voltage as shown in the wir...
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 47 8. If any external hardwired control signals are required (EPO orGenerator On), unscrew and remove the top rear cover of thecabinet and locate the terminal block (see Figure 31). C A ...
UPS ELECTRICAL INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 48 System Wiring Diagrams Select wiring diagrams from Table 8 based upon the installation voltage. Table 8. Wiring Diagrams UPS Input Voltage UPS Output Voltage Output Wires Wiring Diagr...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 53 Chapter 5 Isolated Output Wiring Diagrams NOTE This chapter is only for units manufactured before 2009. The wiring diagrams in this section are unique and specific toinstallations in which the output of the Eato...
ISOLATED OUTPUT WIRING DIAGRAMS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 54 100, 110, 115, or 120 X2 50 or 60 Hz 100/200, 110/220, 115/230, or 120/240V Out with Isolated Output Option Menu 4 2 4 set to 200, 220, 230, or 240, as required. X1 X3 X X N-G Bon...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 61 Chapter 6 Battery Cabinet Installation If you are not installing battery modules into a separate external batterycabinet, continue to “UPS Startup” on page 67. W A R N I N G Only qualified service personnel (suc...
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 62 Entrance Panel Battery Cable Figure 42. UPS Power Entrance Panel 3. Use a pair of pliers to bend the narrow links (1 and 2 in Figure 43)between the outer edge of the lower breakaway ...
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 63 Cable Assembly Backplane Ring Terminal Compression Lug Bus-Bar Extension Assembly Figure 44. Bus-Bar Extension Installation 6. Remove the nuts holding the +DC and the –DC bus bars to...
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 64 Cable Assembly Figure 45. Battery Cable Assembly Installation 12. Align the screw holes of the cable assembly's entry plate withholes on the cabinet side cover as shown in Figure 45....
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 65 ‒ + Figure 46. Battery Cable Installed in Battery Cabinet 17. Secure the + , the ‒ , and the conductors to the proper compression lugs on the battery cabinet backplane as shown inFig...
BATTERY CABINET INSTALLATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 66 To UPS or PreviousBattery Cabinet To NextBattery Cabinet Figure 47. Connecting Additional Battery Cabinets 20. Reinstall the remaining rear covers using the original screws. 21. Cont...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 67 Chapter 7 UPS Startup This section provides step-by-step instructions for starting your Eaton9170+ system. Follow these procedures closely to avoid potentialdamage to your equipment or the UPS and to protect you...
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 68 NOTE All power modules in the Eaton 9170+ UPS cabinet must be of the same type: Split-phase power modules have brown labels; universal (single-phase) power modules haveblack labels. Do not mix brown ...
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 69 Startup for Plug-Receptacle Units To start a plug-receptacle unit: 1. Plug the power cable of the unit into an approved, functional poweroutlet. 2. If external battery cabinets are installed, check t...
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 70 6. If applicable, test proper operation of optional external controlsignals and computer communication before connecting the load.(See “DB-9 Communication Port” on page 92 for details.) 7. Plug the e...
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 71 Startup for Hardwired Units To start a hardwired unit: 1. Confirm that an electrician has completed and tested theconnection to the proper power source. 2. If external battery cabinets are installed,...
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 74 18. The UPS front panel display automatically turns on whenever inputpower is present and at least one power module is installed. Set upthe initial operating parameters through the front panel displa...
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 75 2. Select the desired language for the display. Use the Y and B buttons to scroll between English, French, German, and Spanish.Enter your selection by pressing the button. 3. Set the clock for the lo...
UPS STARTUP Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 76 6. The system signals an alarm when the required output cannot bemaintained with the loss of redundant power modules. The alarm isessentially disabled with a redundancy level set at 0. If you want th...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 77 Chapter 8 Operation The Eaton 9170+ UPS operates in several different modes. Normally itoperates under internal control (Auto mode) to automatically protectloads connected to it. An operator can enable manual ov...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 78 Off mode turns off the output and most internal circuitry. Within thismode, Sleep mode turns off all internal circuitry when AC line is notpresent and battery voltage drops to a low threshold. If AC in...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 79 Turning the UPS On The unit has no physical On/Off switch. Access the UPS On/Off functionthrough the front panel display. If the UPS is off, press the ON button through the front panel display toturn t...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 80 Front Panel Display The front panel has an alphanumeric display, three LED indicators, andsix pushbuttons as described in Figure 54 and in Table 10. 1 2 9 USER #3 Wout watts 2.07 KW Slot Top ESC 2 3 4 ...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 81 Using the Front Panel Display Figure 55 shows an example of the front panel display. The numbers inthe upper left corner (1 2 9 in Figure 55) indicate the menu level. Theword in the top center (USER) i...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 82 During normal operation, the display appears as shown in Figure 56: Md: Current UPS operating mode St: Operational state Mn Number of power modules Bn Number of battery module strings currently online ...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 83 Parameters The parameters describe the UPS operation. Some useful parametersare input and output voltage, input and output current, and batteryvoltage, among others. Some are operator‐adjustable, such ...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 84 Reading the Eaton 9170+ System Logs The Eaton 9170+ system makes an entry in its logs each time it soundsan alarm or runs on battery power. This information can help indiagnosing power problems. You ca...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 85 Alarm Log The alarm log is in menu 2 2. Move through the menu structure bypressing the Menu button and pressing the B button to move down to menu 2. Press and then press the B button to move down to su...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 86 Table 12 lists the alarm log messages. Table 12. Alarm Log Messages Message Explanation Open Cell Battery failure caused by open cell. Weak Battery Battery failure caused by load test. Phase Error Inte...
OPERATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 87 Menu Map Figure 60 shows all the Eaton 9170+ system parameters. The menustructure has six primary-level menus, System Status Menu (1) throughService Menu (6). Each primary menu has secondary items numb...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 89 Chapter 9 Communication Eaton offers several methods of communicating with your Eaton 9170+system in addition to the front panel display: S Power Management and Protection Software S Optional interface kits S Co...
COMMUNICATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 90 ConnectUPS t Web/SNMP Card (BD Model) The ConnectUPS-BD Web/SNMP Card provides the Eaton 9170+system with its own ethernet network connection, allowing it to beremotely monitored and controlled via...
COMMUNICATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 91 On-Generator: An external signal can indicate that the input power is being supplied by a generator. Closure of this contact causes the UPS tochange the following parameters to preset values that a...
COMMUNICATION Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 92 DB-9 Communication Port Table 13 explains the functions of the pins on the Eaton 9170+ DB-9communication port. This port is on the Eaton 9170+ UPS rear panel, asshown in Figure 49 on page 69. Table...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 93 Chapter 10 Maintenance Routine Maintenance NOTE Observe important safety precautions while performing these checks. NOTE Eaton recommends that you schedule preventive maintenance checks at least every six months...
MAINTENANCE Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 94 Storage Temperature Store the Eaton 9170+ battery modules (in the UPS or external batterycabinet) at –20 to +40 ° C (–4 to +104 ° F). Batteries will have a longer shelf life if they are kept below +2...
MAINTENANCE Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 95 3. Pull the module out approximately 17 cm (7 ” ) to the secondary stop on top of the module. 4. Press down on the secondary stop release, pull the module outfarther, and support the module weight wi...
MAINTENANCE Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 96 3. Use two hands to support the module. When fully extended, lowerthe front down slightly and lift the rear edge over the safety stop onthe center support rail. 4. Treat the original and replacement ...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 97 Chapter 11 Specifications This section provides the following specifications for the Eaton 9170+models: S Electrical input and output S Model specifications S Environmental and safety S Battery S Weights and dim...
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 98 Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) Three-Slot Cabinet Optional Chargers UPS kVA/Watts Input Current (200V)* Output Current (100/200V, 110/220V, 120/240V) Recom...
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 99 Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued) Nine- and Twelve-Slot Cabinet CAUTION Do NOT install more than seven power and/or battery charger modules in a 9...
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 104 Table 18. Environmental and Safety Operating Temperature 0 ° C to 40 ° C (32 ° F to 104 ° F) Optimal battery performance: 25 ° C (77 ° F) Storage Temperature UPS with battery modules: –20 ° C to ...
SPECIFICATIONS Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 105 Table 20. Weights and Dimensions Cabinet Size Height Width Depth Weight* 3-slot 45 cm (17.75 ” ) 43 cm (17.0 ” ) 65 cm (25.5 ” ) 30 kg (66 lb) 3-slot (with caster cart) 49.5 cm (19.5 ” ) 43 cm (1...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 107 Chapter 12 Troubleshooting The following table provides answers to commonly asked questions. Table 21. Frequently Asked Questions Question: “How do I... ” Answer Turn the UPS on? Verify that all power modules a...
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 108 Answer Question: “How do I... ” Check the condition of thebatteries? The results of the most recent battery test are stored at menu 3 1 2 1. To run a test ofbattery condition, go to menu 3 1 1 a...
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 109 Alarms Figure 61 shows a typical alarm display. Alarms are annunciated by aconstant Alarm LED and a constant beep. During alarm display,button (A) silences the audible alarm, button (B) clears t...
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 110 When an alarm occurs, follow these steps: 1. Observe the display to see which alarm is active. NOTE To find out if more than one alarm is active, press . This switches the display between alarm ...
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 111 What to Do What It Means Alarm Message P EPO The Emergency Power-off functionhas been activated. Deactivate the external EPO switch and restart theUPS by pressing the ON button through the front...
TROUBLESHOOTING Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 113 Service and Support If you have any questions or problems with the UPS, call your Local Distributor or the Eaton Customer Support Center at one of the following telephone numbers. Available Supp...
Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 115 Chapter 13 Warranty Two-Year Limited Warranty (US and Canada) Eaton UPS Models: 9155, 9170+ and FERRUPS ® 4.3–18 kVA WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation Cor...
WARRANTY Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 116 In any case, Company will provide shipping instructions and will pay its designated carrier for all shipping charges forreturn of defective equipment and replacement of Warranted Items. Any returned Wa...
WARRANTY Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 117 OTHER LIMITATIONS: Company's obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Compan...
WARRANTY Eaton 9170 + UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality 118 WHAT THIS GUARANTY DOES NOT COVER: Any reimbursement or repair to End-User's equipment does not include reimbursement for or restoration of any data loss. This Guaranty does not cover any defects or da...
Eaton Manuals
-
Eaton 10000L(XL)
Manual
-
Eaton Magnum Transfer Switch
Manual
-
Eaton 9155
Manual
-
Eaton 110
Manual
-
Eaton PVH57
Manual
-
Eaton 9130
Manual
-
Eaton 3105 UPS
Manual
-
Eaton 9140
Manual
-
Eaton IM01005012E
Manual
-
Eaton 10640205
Manual
-
Eaton TR3
Manual
-
Eaton ETN2000
Manual
-
Eaton APR48
Manual
-
Eaton PVH63
Manual
-
Eaton 9390
Manual
-
Eaton ASY0529
Manual
-
Eaton 9135
Manual
-
Eaton 1000
Manual
-
Eaton ESWA0800SC
Manual
-
Eaton 9170+
Manual