Class A EMC Statements (Low Voltage Models over 1500 VA) FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interferencewhen...
Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonized standards and EU directives: S Harmonized Standards: IEC 61000-3-12 S EU Directives: 73/23/EEC, Council Directive on equipment designed for use within certain voltage limits93/68/EEC, Am...
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com i Table of Contents 1 Introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Safety Warnings 3 . . . . . . . . . . . . . . . . . . . . . . . . ....
TABLE OF CONTENTS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com ii Retrieving the Event Log 47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting Power Strategy 48 . . . . . . . . ....
TABLE OF CONTENTS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com iii 9 Warranty 107 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Two-Year Limited Warranty (US and Canada) 107 . . . . . . . . . ....
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 1 Chapter 1 Introduction The Eaton ® 9130 uninterruptible power system (UPS), part of the Powerware ® series, protects your sensitive electronic equipment from the most common power problems, including power failures, po...
INTRODUCTION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 2 Figure 1 shows the Eaton 9130 rackmount UPS, and Figure 2 shows theoptional rackmount EBM. Figure 1. The Eaton 9130 Rackmount UPS Figure 2. The Eaton 9130 Rackmount EBM Figure 3 shows the Eaton 9130 tower ...
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 3 Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation andmaintenance of the UPS and batteries. Please rea...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 4 C A U T I O N S Batteries can present a risk of electrical shock or burn from high short-circuit current.Observe proper precautions. Servicing should be performed by qualified servicepersonnel knowledge...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 5 A D V A R S E L S Batterierne kan give risiko for elektrisk stød eller brandsår forårsaget af højkortslutningsstrøm. Overhold gældende forsigtighedsregler. Servicering skal udføres afkvalificeret servic...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 6 S De uitgangsoverstroombeveiliging en de stroomonderbreker moeten door derden wordengeleverd. S Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de geheleapparatuur die op de ui...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 7 S Pienennä tulipalon vaaraa kytkemällä vain piiriin, jossa on 100 ampeerinmaksimihaarapiirin ylivirtasuoja kansallisen sähkölainsäädännön (ANSI/NFPA 70)mukaan. S Muiden on toimitettava lähdön ylivirtasu...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 8 S Afin de réduire les risques d'incendie, ne raccordez qu'à un circuit muni d'une protectionde surintensité du circuit de dérivation maximum de 100 ampères conformément au NEC(Code Électrique National) ...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 9 A C H T U N G S Dieses USV (Unterbrechungsfreies Stromversorgungssystem) enthält eine eigeneEnergiequelle (Batterien). Der USV-Ausgang kann Spannung führen, auch wenn das USVnicht an eine Wechselstromqu...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 11 Viktig Sikkerhetsinformasion VIKTIGE SIKKERHETSINSTRUKSJONER GJEM DISSE INSTRUKSJONENE Denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering ogvedlikehold av UPS-enheten o...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 12 Regulamentos de Segurança INSTRUÇÕES DE SEGURANÇA IMPORTANTES GUARDE ESTAS INSTRUÇÕES Este manual contém instruções importantes que devem ser seguidas durante a instalação emanutenção do no-break e das...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 13 Ïðåäóïðåæäåíèÿ ïî ìåðàì áåçîïàñíîñòè ÂÀÆÍÛÅ ÓÊÀÇÀÍÈß ÏÎ ÌÅÐÀÌ ÁÅÇÎÏÀÑÍÎÑÒÈ ÑÎÕÐÀÍÈÒÅ ÝÒÈ ÓÊÀÇÀÍÈß Â äàííîì ðóêîâîäñòâå ñîäåðæàòñÿ âàæíûå èíñòðóêöèè ïî óñòàíîâêå è îáñëóæèâàíèþ èñòî÷íèêà áåñïåðåáîéíîãî ...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 14 Î Ñ Ò Î Ð Î Æ Í Î S Âûñîêîå íàïðÿæåíèå, âûçâàííîå êîðîòêèì çàìûêàíèåì â áàòàðåå, ìîæåò ïðèâåñòè ê ïîðàæåíèþ ýëåêòðè÷åñêèì òîêîì èëè îæîãó. Ñîáëþäàéòå ìåðû ïðåäîñòîðîæíîñòè. Òåõíè÷åñêîå îáñëóæèâàíèå äîë...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 15 S La protección contra sobrecorriente de salida y el conmutador de desconexión debesuministrarse por parte de terceros. S Para cumplir con los estándares internacionales y las normas de instalación, la...
SAFETY WARNINGS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 16 S För att reducera faran för brand får anslutning endast utföras till en krets som skyddasmed överbelastningsskydd på maximalt 100 ampere i enlighet med NEC, ANSI/NFPA 70. S Utgående överbelastningssyd...
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 17 Chapter 3 Installation This section explains: S Equipment inspection S Unpacking the cabinet S Checking the accessory kit S Cabinet installation (rackmount and tower) S Wiring installation S Initial startup Inspecting...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 18 Unpacking the Cabinet C A U T I O N S Unpacking the cabinet in a low-temperature environment may cause condensation tooccur in and on the cabinet. Do not install the cabinet until the inside and outside o...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 19 Rackmount Installation The Eaton 9130 rackmount cabinet comes with all of the hardwarerequired for installation in a standard EIA or JIS seismic rackmountconfiguration with square and round mounting holes...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 20 Rackmount Setup C A U T I O N S The cabinet is heavy (see page 78). Removing the cabinet from its carton requires aminimum of two people. S If installing optional EBM(s), install the EBM(s) directly below...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 21 2. Select the proper holes in the rack for positioning the UPS in therack (see Figure 5). The rails occupy four positions on the front andrear of the rack. 3. Secure one rail assembly to the front of the ...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 22 NOTE There are two sets of four mounting holes on each side of the UPS: a forward position and a middle position. Choose the position that meets your configuration needs. MountingBracket M4 8 Flat-Head Sc...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 23 13. Optional. Insert a rear stop bracket through the inside of each rail behind the UPS. Rotate each bracket and slide the bracket until itfits tightly against the UPS's rear panel. Secure each bracket to...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 24 NOTE A ribbon cable connects the LCD control panel to the UPS. Do not pull on the cable or disconnect it. NOTE Leaveribbon cableconnected. Figure 9. Removing the UPS Right Front Cover C A U T I O N A smal...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 25 Up to 1500 VA Models 2000–3000 VA Models Figure 10. Connecting the UPS Internal Batteries 3. If you are installing EBMs, see the following section, “Connectingthe EBM(s),” before continuing with the UPS i...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 26 Connecting the EBM(s) To install the optional EBM(s) for a UPS: 1. On the bottom of the UPS right front cover, remove the EBM cableknockout (see Figure 11). NOTE Use care to protect the LCD control panel ...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 27 Bottom EBM Cable Knockout(underneath cover) Top EBM Cable Knockout EBM Cover Hook Figure 12. Removing the EBM Front Cover 3. For the bottom (or only) EBM, remove the EBM cable knockout onthe top of the EB...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 28 C A U T I O N A small amount of arcing may occur when connecting an EBM to the UPS. This is normaland will not harm personnel. Insert the EBM cable into the UPS battery connector quicklyand firmly. 5. Plu...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 29 7. Replace the EBM front cover. To replace the cover, verify that the EBM cables are routed throughthe EBM cover knockouts, then slide the cover from the left to theright until it connects with the cover ...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 30 Tower Wiring Installation This section explains: S Installing the UPS, including connecting the UPS internal batteries S Connecting any optional EBMs Installing the UPS NOTE Do not make unauthorized chang...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 31 C A U T I O N A small amount of arcing may occur when connecting the internal batteries. This is normaland will not harm personnel. Connect the cables quickly and firmly. 2. Connect the internal battery c...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 32 6. If you are installing power management software, connect yourcomputer to one of the communication ports or optionalconnectivity card (see page 53). For the communication ports, usean appropriate cable ...
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 33 1000–1500 VA Models 2000–3000 VA Models Remove cable retention clip. Plug in EBM cable. Rotate clip. Reinstall cable retentionclip. Figure 16. Connecting the EBMs
INSTALLATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 34 UPS Initial Startup To start up the UPS: NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an overload alarm. 1. Verify that the internal batteries are connected. Rack...
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 37 Chapter 4 Operation This chapter contains information on how to use the Eaton 9130,including front panel operation, operating modes, UPS startup andshutdown, transferring the UPS between modes, retrieving the EventLog...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 38 Table 1 shows the indicator status and description. Table 1. Indicator Descriptions Indicator Status Description Green On The UPS is operating normally. Flashing A new information message is active. Yellow O...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 39 Table 2 shows the basic menu structure. Table 2. Menu Map for Display Functions Main Menu Submenu Display Information or Menu Function UPS Status Main status (mode and load) / Notice or Alarm status (if any)...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 40 User Settings The following table displays the options that can be changed by the user. Table 3. User Settings Description Available Settings Default Setting Change Language [English] [French] [Spanish] [Ger...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 41 Table 3. User Settings (continued) Default Setting Available Settings Description Frequency Converter [Enabled] [Disabled]If Enabled, the UPS operates as a frequencyconverter, with bypass operation and allby...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 43 Table 3. User Settings (continued) Default Setting Available Settings Description Predictive Maintenance Notices [Enabled] [Disabled] Enabled Remote Emergency Power-off (REPO)Input Polarity [Open] [Closed] O...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 44 If battery capacity becomes low while in Battery mode, the indicator flashes slowly and the audible alarm beeps once every second. If the“Battery Low” alarm is set, the indicator also illuminates solid. This...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 45 Standby Mode When the UPS is turned off and remains plugged into a power outlet,the UPS is in Standby mode. The indicator is off, indicating that power is not available to your equipment. The battery recharg...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 46 5. Check the UPS front panel display for active alarms or notices.Resolve any active alarms before continuing. See“Troubleshooting” on page 101. If the indicator is on, do not proceed until all alarms are cl...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 47 UPS Shutdown To shut down the UPS: 1. Press the button on the front panel for three seconds. The UPS starts to beep and shows a status of “UPS off pending...”.The UPS then transfers to Standby mode, and the ...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 48 Setting Power Strategy On the High Efficiency setting, the UPS operates normally on Bypass,transfers to inverter in less than 10 ms when utility fails, and transfersback to Bypass in 1 minute after utility r...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 49 You can prohibit Bypass (”Never”) or always allow Bypass with nospecification checking (”Always”). For “Always on UPS Fault,” transferto Bypass is always made on UPS fault; otherwise, operation proceedsas wi...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 50 To set the restart and shutdown delay times for each load segment: 1. Press any button to activate the menu options, then selectSETTINGS, USER SETTINGS and AUTOMATIC START DELAY. 2. Set the restart delay for...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 51 Configuring Battery Settings Set the UPS for the number of EBMs installed, whether to run automaticbattery tests, and automatic restart configuration. Configuring the UPS for EBMs To ensure maximum battery r...
OPERATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 52 Running Automatic Battery Tests Automatic battery tests run approximately every 30 days, unlessdisabled. During the test, the UPS transfers to Battery mode anddischarges the batteries for 25 seconds under th...
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 53 Chapter 5 Communication This section describes the: S Communication ports (RS-232 and USB) S Connectivity cards S Remote Emergency Power-off (REPO) S Relay output contacts S Programmable signal inputs S Modem operatio...
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 54 Installing Communication Options and Control Terminals To install the communication options and control terminals: 1. Install the appropriate connectivity card and/or necessary cable(s)and connect the ca...
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 55 When the communication cable is installed, power managementsoftware can exchange data with the UPS. The software polls the UPSfor detailed information on the status of the power environment. If apower em...
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 56 Connectivity Cards Connectivity cards allow the UPS to communicate in a variety ofnetworking environments and with different types of devices. The Eaton9130 has one available communication bay for the fo...
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 57 NOTE For Europe, the emergency switch requirements are detailed in Harmonized document HD-384-48 S1, “Electrical Installation of the Buildings, Part 4: Protection for Safety,Chapter 46: Isolation and Swi...
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 58 Relay Output Contacts The UPS incorporates three programmable relay outputs with potentialfree contacts for remote alarm indications: a standard relay port and twooutputs in the RS-232 communication port...
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 59 Programmable Signal Inputs The UPS incorporates four programmable signal inputs: one RS-232input, two connectivity card inputs, and one REPO terminal input. SeeFigure 18 on page 53 for the locations of t...
COMMUNICATION Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 60 Modem Operation To configure the UPS and modem handling features for remotemonitoring and service, contact your service representative. Powerware LanSafe Power Management Software Each Eaton 9130 UPS shi...
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 61 Chapter 6 UPS Maintenance This section explains how to: S Care for the UPS and batteries S Replace the UPS internal batteries and Extended Battery Modules(EBMs) S Test new batteries S Recycle used batteries or UPS S U...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 62 Storing the UPS and Batteries If you store the UPS for a long period, recharge the battery every6 months by connecting the UPS to utility power. The internal batteriescharge to 90% capacity in less tha...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 63 S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to theskin and eyes and may be extremely toxic. S Determine if the battery is inadvertently grounded. If inadvertentl...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 64 NOTE Leaveribbon cableconnected. Figure 23. Removing the UPS Right Front Cover 2. Disconnect the internal battery connector (see Figure 24). 3. Up to 1500 VA models only. If the EBM cable is not connec...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 65 5. Carefully pull the handle on the battery tray and slide the batterypackage slowly out onto a flat, stable surface; use two hands tosupport the battery package. See “Recycling the Used Battery orUPS”...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 66 Replacing Tower UPS Internal Batteries C A U T I O N The UPS internal batteries are heavy (see page 78). Use caution when handling the heavybatteries. The internal batteries are located behind the UPS ...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 67 2. Remove and retain the two screws holding the internal batteryconnector. Disconnect the internal battery connector. SeeFigure 26. Battery Cover Plate InternalBatteryConnector Battery Tray Handle Figu...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 68 6. Replace the battery cover plate into the slots at left, threading thebattery connector through the access slot. Reinstall the retainedscrews. C A U T I O N A small amount of arcing may occur when co...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 69 Replacing Rackmount EBMs C A U T I O N The EBM is heavy (see page 78). Lifting the cabinet into the rack requires a minimum of twopeople. To replace the EBMs: 1. Remove the front cover of each EBM. See...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 71 10. Replace the EBM front cover. To replace the cover, verify that the EBM cables are routed throughthe EBM cover knockouts, then slide the cover from the left to theright until it connects with the co...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 72 5. For each cable retention clip removed, rotate the clip and install itunder each EBM cable connection using the retained screws. 6. Verify that the EBM connections are tight and that adequate bendrad...
UPS MAINTENANCE Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 73 Recycling the Used Battery or UPS Contact your local recycling or hazardous waste center for informationon proper disposal of the used battery or UPS. W A R N I N G S Do not dispose of the battery or b...
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 75 Chapter 7 Specifications Model Specifications This section provides the following specifications: S Communication options S Model lists S Weights and dimensions S Electrical input and output S Environmental and safety...
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 76 Table 10. UPS Model List (Rackmount Models) Model Power Level Rear Panel Diagram PW9130L700R-XL2U 700 VA / 630W Figure 28 on page 91 PW9130L1000R-XL2U 1000 VA / 900W Figure 28 on page 91 PW9130L1500R-XL...
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 78 Table 12. Weights and Dimensions (Rackmount Models) Model (Rackmount UPS) Dimensions (H W D) Weight PW9130L700R-XL2UPW9130L1000R-XL2UPW9130G1000R-XL2UPW9130i1000R-XL2UPW9130G1000R-XL2UEUPW9130G1000R-XL2...
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 90 Table 25. Battery Internal Batteries EBMs RackmountConfiguration 700–1000 VA models: 36 Vdc (3 12V, 9 Ah) 1500 VA models: 48 Vdc (4 12V, 9 Ah) 2000–3000 VA models: 72 Vdc (6 12V, 9 Ah) PW9130N1000R-EBM2...
SPECIFICATIONS Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 91 Rear Panels This section shows each model's rear panel. Receptacles in LoadSegment 1 are shaded. Table 10 on page 76 lists the rackmount models. Table 11 on page 77lists the tower models. Input and outp...
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 101 Chapter 8 Troubleshooting The Eaton 9130 is designed for durable, automatic operation and alsoalerts you whenever potential operating problems may occur. Usuallythe alarms shown by the control panel do not mean that ...
TROUBLESHOOTING Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 102 To check the Event Log for a history of conditions: 1. Press any button on the front panel display to activate the menuoptions. 2. Press the button until EVENT LOG displays. 3. Press the Enter button ...
TROUBLESHOOTING Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 103 Action Possible Cause Alarm or Condition Overload LED is on.1 beep every second. Power requirements exceed theUPS capacity (greater than100% of nominal; see page 84 forspecific output overloadranges)....
TROUBLESHOOTING Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 105 Silencing the Alarm Press any button on the front panel display to silence the alarm. Checkthe alarm condition and perform the applicable action to resolve thecondition. If the alarm status changes, t...
Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 107 Chapter 9 Warranty Two-Year Limited Warranty (US and Canada) Powerware UPS Models: 3105, 9120, 9125, 9130, 9140, and FERRUPS ® up to 3.1 kVA WARRANTOR: The warrantor for the limited warranties set forth herein is Eat...
WARRANTY Eaton ® 9130 UPS (700–3000 VA) User's Guide S 164201718 Rev 2 www.powerware.com 111 OTHER LIMITATIONS: Company's obligations under this Warranty are expressly conditioned upon receipt by Company of all payments due to it (including interest charges, if any). During such time as Company has ...
Eaton Manuals
-
Eaton 10000L(XL)
Manual
-
Eaton ASY0567
Manual
-
Eaton Magnum Transfer Switch
Manual
-
Eaton 9155
Manual
-
Eaton 110
Manual
-
Eaton PVH57
Manual
-
Eaton 3105 UPS
Manual
-
Eaton 9140
Manual
-
Eaton IM01005012E
Manual
-
Eaton 10640205
Manual
-
Eaton TR3
Manual
-
Eaton ETN2000
Manual
-
Eaton APR48
Manual
-
Eaton PVH63
Manual
-
Eaton 9390
Manual
-
Eaton ASY0529
Manual
-
Eaton 9135
Manual
-
Eaton 1000
Manual
-
Eaton ESWA0800SC
Manual
-
Eaton 9170+
Manual